softing CommModule MBP Evaluation Kit

Overview
The commModule MBP Evaluation Kit is designed around a surface-mountable, single-sided commModule MBP to access the Fieldbus Foundation. It provides a carrier board with internal/external interfaces, EMC protection, and current limitation, and includes an enclosure with a removable cover and front-visible status LEDs.
Specifications
| Category | Specification |
|---|---|
| Operating temperature range | -40 °C to +85 °C (unless otherwise noted) |
| Digital port signals (HART) | RXD, TXD, RTS, CTS |
| Digital inputs (Vcc = 3.2 V ±4%) | VIL: min -0.3, max Vcc × 0.2 (unit V); VIH: min Vcc × 0.8, max Vcc + 0.3 (unit V) |
| Digital outputs (Vcc = 3.2 V ±4%) | VOL @ IOL = -1 mA: max Vcc × 0.2; VOH @ IOH = +1 mA: min Vcc × 0.8 |
| Output rails | 3V_OUT and 6V2_OUT (power rails supply connected system from fieldbus) |
| Adjustable fieldbus power budget (software) | Rated fieldbus current adjustable from 10 mA to 26 mA (Pomax ≈ 80 mW); power budget available in sum on two power rails |
| 3V_OUT output budget (Cload < 2 F) | V values specified for Io = 1 mA, 10 mA, 20 mA (min/max range listed in source) |
| 6V2_OUT output budget (Cload < 2 F, internal series resistance 10 Ω) | V values specified for Io = 1 mA, 10 mA, 16 mA (min/max range listed in source) |
| Fieldbus supply voltage | Powered from fieldbus: 9 V to 32 V |
| Fieldbus physical layer | IEC 61158-2 types 1 and 3, voltage mode, 31.25 kBit/s |
| Rated current / commModule MBP setting | Adjusted from In = 10 mA up to 26 mA |
Note: The source includes detailed min/max voltage values for 3V_OUT and 6V2_OUT under specific load currents and capacitance limits; see the table in the original manual section for the exact numbers.
Setup & Basic Use
- Mount the commModule MBP Evaluation Kit hardware as required for your application. The commModule MBP itself is surface mountable and single-sided with a minimum footprint.
- To access internal interfaces: unscrew two screws from the top and carefully remove the top cover.
- Connect external interfaces:
- Fieldbus: connect the polarity-independent fieldbus to the 3-pol screw connector (Pin 1 and Pin 2 reserved for fieldbus; Pin 3 for cable shield).
- HART/Modbus: connect using the Phoenix mini combicon connector; use the pin assignment for RXD/TXD/RTS/CTS and power rails as described below.
- Configure jumper-dependent behavior: review and set jumpers for shield/capacitor options, current limiter enable/disable (X204), user boot mode (X205), protocol select (X206), simulate enable (X207), and 6V2-out select (X209).
- Verify LED behavior: when the FF stack is executed, LED L1 (green) indicates token ring status (lit in token ring mode); LED L2 is user-programmable.
Introduction
About this document
- The commModule MBP is a surface-mountable, single-sided communication module with minimum footprint designed to access the Fieldbus Foundation.
Target group
- This document is addressed to HART device developers and software engineers. Basic knowledge of HART and FF technology and HART device descriptions is assumed to ensure that the steps and processes described in this document are implemented correctly.
Related documentation
- For further details about the commModule MBP and the configuration workflow of the firmware see the CommScripter user guide and commModule MBP hardware guide available by download.
Conventions used
- The following conventions are used throughout Softing customer documentation:
- CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
- Note This symbol is used to call attention to notable information that should be followed during installation, use, or servicing of this device.
- Hint This symbol is used when providing you with helpful user hints.
Document history

Scope of delivery
- The Evaluation Kit consists of the commModule MBP board with minimum footprint, packed with two interface connectors into a box with LED and removable cover.
CommModule MBP Evaluation Kit
- The commModule MBP is a surface-mountable, single-sided communication module with minimum footprint. It is mounted on a carrier board which exhibits internal and external interfaces along with additional circuitry like EMC protection and current limitation.
CAUTION
- The commModule MBP Evaluation Kit must not be used in hazardous areas.
Block diagram
The block diagram of the commModule MBP Evaluation-Kit is shown below:
Internal interfaces
- To access the internal interfaces, the enclosure must be opened. Unscrew two screws from top and carefully remove top cover.

Connectors
- X201 fieldbus input connector
- X208 HART / Modbus connector
- X202 Renesas E2/Lite Debug connector
Jumpers
Shield capacitor X200
- Connect Shield Pin X201 connected directly to earth
- Connect Shield Pin X201 connected via a 4n7 capacitor to earth
LED Jumper X203
- If connected, the corresponding LED is connected to the module’s I/O pin.
Current Limit 6V2 X204
- 5-6 connected, 3-4/1-2 open current limit circuit is disabled
- 1-2 and 3-4 connected current limit circuit is enabled
- User Boot Mode Off X205
Not used, always leave open
- Protocol Select X206
- 1-2 connected Profibus PA is selected
- 1-2 open FF is selected
Simulate Enable Jumper X207
- 1-2 connected Simulate Enable active
- 1-2 open Simulate Enable inactive
- 6V2 out select X209 Jumper
- 1-2 connected nCTS3 is routed to pin 5 of X208
- 2-3 connected 6V2 is routed to pin 5 of X208
Current limiter circuit on 6V2 output
- The 6V2 output of X208 incorporates an output current limitation circuit. This circuit is used to limit the inrush current into any circuitry that is connected to the 6V2 power rail. The current limit is set to 16mA. The bus current used by the commModule MBP has to be set accordingly in the commScripter data. The delivered setting for the commModule MBP is 26 mA.
Note At present, the 3V15 output does not feature an output current limit circuit.
For reference, see the current output limitation circuit below:
Programming connector
Connect Renesas E1 emulator for flash programming and debugging on connector X202 as shown below:

External interfaces
The commModule-MBP Evaluation-Kit exhibits following external interfaces:

Fieldbus
- The polarity-independent fieldbus interface connects the fieldbus to a 3-pol screw connector, where Pin 1 and Pin 2 are reserved for fieldbus, and Pin 3 for the cable shield.
Connector:
- Phoenix Mini Combicon type: MC 1:5/3-STF-3:81
HART/Modbus
Connector: Phoenix mini combicon type: MC 1.5/6-STF-3:81

LED
- The two LEDs L1 and L2 (both red/green) are visible through LED pipes on the front cover.
- When the FF stack is executed L1 (green) indicates the token ring status. It is lit when the device is in token ring mode. L2 is user-programmable.
Electrical specifications
Operating conditions
- Unless otherwise noted, all specifications apply over the specified operating temperature.
- The normal operating temperature range from -40°C to + 85°C.
Input and output
- Digital port input/output specifications (HART):
- Signals RXD, TXD, RTS, CTS
- With Vcc = 3.2V± 4%

Output power specification (HART):
- Signals 3V_OUT, 6V2_OUT
- The power budget to supply a connected system from fieldbus is limited. It depends on the rated current drawn from the fieldbus, which is adjustable in software from 10mA to 26mA (Pomax = approx. 80mW). This power budget is available in sum on two power rails.

Fieldbus
- Powered from fieldbus 9V to 32V.
- Physical layer according to IEC 61158-2 types 1 and 3 voltage mode, 31.25kBit/s.
- Rated current of commModule MBP adjusted to In = 10mA up to 26mA.
Appendix
- Circuit diagram of the commModule MBP Evaluation Kit.

More Information
- + 49 89 45 656-340
- info.automation@softing.com
- support.automation@softing.com

Troubleshooting
- No/incorrect fieldbus behavior: confirm the fieldbus and HART/Modbus connector wiring using the documented pin assignments (RXD/TXD/RTS/CTS and power rails) and verify protocol selection via jumper X206 (Profibus PA selected vs. FF selected).
- 6V2 power rail current limiting issues: check jumper X204 settings for the 6V2 current limiter circuit. The 6V2 output includes an output current limitation circuit intended to limit inrush current; the current limit is set to 16 mA, and the bus current used by the commModule MBP must be set accordingly in the commScripter data. The delivered setting is 26 mA.
- LED indicators not matching expectations: ensure the FF stack is executed to get L1 (green) token ring status indication. Remember L2 is user-programmable.
- Enclosure access required: if you need to inspect or adjust internal interfaces or jumpers, open the enclosure by unscrewing two screws from the top and removing the top cover.
Documents / Resources
![]() | CommModule MBP Evaluation Kit |
References
- industrial.softing.comindustrial.softing.com
- industrial.softing.com/en/products/embedded-module/fast-and-easy-implementation-of-foundation-fieldbus-into-hart-field-devices.htmlindustrial.softing.com
- industrial.softing.com/support/support-formindustrial.softing.com
- opensource.softing.com/opensource.softing.com
- User Manualmanual.tools