ZUMTOBEL 2 TCI Litecom Touchpanel
Product Usage Instructions
- Connect the touch panel directly to a LITECOM CCD using an Ethernet cable.
- Ensure both the touch panel and LITECOM CCD are using their default IP addresses.
- Connect the voltage supply to the touch panel.
- Switch to the Network settings tab on the touch panel.
- Enable Static IP address.
- Set the IP address, subnet mask, default gateway, and DNS server of the touch panel to match the LITECOM CCD network.
- Apply changes and switch to the Homepage tab.
- Enter the IP address of the LITECOM CCD and confirm the changes.
Application area
- This touch panel is used to display the LITECOM web application. The touch panel has a Chromium browser that automatically establishes a connection to a LITECOM CCD.
Technical data
Supply line
Notes
- Attach to the Ethernet cable using the supplied split ferrite before installation.
- The touch panel must be installed as described in the manual.
- The manual can be downloaded here: http://www.zumtobel.com/24165702.
- The default IP address of the LITECOM CCD is: 10.10.40.254
- The default IP address of the touch panel is: 10.10.40.11
- The supply voltage on the touch panel must be between 22 and 26 V DC. Connect the touch panel only when the supply lines are disconnected from the power.
- Otherwise, the touch panel may start in an impermissible operating status. If this occurs, you will hear a beep or noise on the touch panel.
Commissioning version 1: touch panel directly connected to LITECOM CCD Requirements:
- Touch panel is directly connected to a LITECOM CCD via an Ethernet cable.
- Touch panel and LITECOM CCD each use their default IP address.
- Connect the voltage supply to the touch panel.
- Chromium browser starts in kiosk mode and automatically establishes a connection to the LITECOM CCD.
- The start page of the LITECOM web application is displayed
Commissioning version 2: touch panel connected to LITECOM CCD within a network
- Connect the voltage supply to the touch panel.
- The Chromium browser starts in kiosk mode.
- Tap the four corners of the touch panel, starting at the top left and following a U shape (top left, bottom left, bottom right, top right).
- The device settings are displayed.
- Switch to the Network settings tab.
- Enable Static IP address.
- Set the IP address, subnet mask, default gateway, and DNS server of the touch panel so that it is in the same network as the LITECOM CCD.
- Tap Apply changes.
- Switch to the Homepage tab.
- Enter the IP address of the LITECOM CCD.
- Tap the X icon at the top left.
- A connection to the LITECOM CCD is established.
- The start page of the LITECOM web application is displayed.
Notes
- You can also obtain the IP address automatically.
- To do this, enable DHCP in step 4.
- Information on the network settings can be requested from your IT manager.
CONTACT
- ZUMTOBEL LIGHTING GmbH
- Schweizer Strasse 30, A-6851 Dornbirn AUSTRIA
- www.zumtobel.com
FAQ
- Q: What should I do if the touch panel starts in an impermissible operating status?
- A: Ensure that all lines are disconnected from power. If you hear a beep or noise, it indicates an impermissible operating status.
- Q: How do I set up the touch panel within a network?
- A: Follow the steps for Commissioning Variant 2 mentioned above to connect the touch panel to a LITECOM CCD within a network.