zennio logo

Zennio ZNIO-QUADP QUAD Plus Analogue/Digital Input Module

Zennio ZNIO-QUADP QUAD Plus Analogue Digital Input Module

DOCUMENT UPDATES

Version Changes Page(s)
 

 

[1.6]_a
Changes in the application program:

 

·         Optimisation of the thermostat and motion detector modules.

 

 

  [1.5]_a Changes in the application program:

·         Minor corrections.

 

  [1.3]_a Changes in the application program:

 

·         Optimisation of the temperature probe module.

 

 

 

[1.2]_a
Changes in the application program:

 

·         Optimisation of the binary inputs, thermostat and motion detector modules.

 

 

INTRODUCTION

QUAD PLUS

 QUAD Plus is an updated, small-size version of the popular QUAD from Zennio. This module incorporates four digital / analogue separate inputs, each configurable as:

Binary Input.

Temperature  probe,  either  models  provided  by  Zennio  or  other      NTC temperature probes from other suppliers, being in that case possible to configure their parameters in ETS.

Motion detector.

Moreover, QUAD Plus implements four independent thermostats, which can be enabled and configured separately, as well as the Heartbeat function or periodical “still-alive” notification.

INSTALLATION

QUAD is connected to the KNX bus through the incorporated terminal connector, while the input lines need to be connected to QUAD Plus through the screw terminal block bundled in the device packaging. Once powered through the KNX bus, the device may be downloaded both an individual address or the application program.

Zennio ZNIO-QUADP QUAD Plus Analogue Digital Input Module fig 1

The main elements are described next:

Prog./Test Button (2): a short press on this button sets the device into the programming mode, making the associated LED (2) light in red. If this button is held at the same time of applying bus power to the device, the device will enter the Safe Mode. In such case, the LED will intermit in red.

Slots for the Input Lines  (3):  slots for the insertion of  the  optional    inputs terminal block (4). Alternatively, the stripped cables of the input lines can be directly screwed into the slots. Each accessory should be connected to one of the slots labelled 1 to 4 and, on the other hand, to any of the common slots, labelled as “C”.

To obtain further information about the technical features of QUAD Plus and  on security and installation procedures, please refer to the Datasheet of the device, bundled with the original packaging and also available at the Zennio website, http://www.zennio.com.

CONFIGURATION

 GENERAL

 After importing the corresponding database in ETS and adding the device into the topology of the desired project, the configuration process begins by entering the Parameters tab of the device.

ETS PARAMETERISATION

 The only parameterisable screen available by default is General. From this screen it is possible to activate/deactivate all the required functionality.

Zennio ZNIO-QUADP QUAD Plus Analogue Digital Input Module fig 2

Heartbeat (Periodical Alive Notification): this parameter lets the   integrator incorporate a 1-Bit object to the project (“[Heartbeat] Object to Send ‘1’”) that will be sent periodically with value “1” to notify that the device is still working (still alive).

Zennio ZNIO-QUADP QUAD Plus Analogue Digital Input Module fig 3

Note: The first sending after download or bus failure takes place with a delay of up to 255 seconds, to prevent bus overload. The following sendings match the period set

 Input  x:  sets  the  type  of  input  number  “x”:  “Binary  Input”, “Temperature Probe” or “Motion Detector”. If such input is not required, it can be left as “Disabled”.

Thermostat x: enables or disables thermostat number “x”.

One entry per input or thermostat will be included into the tab tree on the left.

INPUTS

 QUAD Plus incorporates four analogue/digital inputs, each configurable as a:

Binary input, for the connection of a pushbutton or a switch/sensor.

Temperature probe, to connect a temperature sensor from Zennio or NTC probes from third parties (the latter requires configuring their parameters in ETS).

Motion detector, to connect a motion detector from Zennio.

BINARY INPUT

Please refer to the specific user manual “Binary Inputs”, available in the QUAD Plus product section at the Zennio website, http://www.zennio.com.

TEMPERATURE PROBE

Please refer to the specific user manual “Temperature Probe”, available in the QUAD Plus product section at the Zennio website, http://www.zennio.com.

MOTION DETECTOR

It is possible to connect motion detectors from Zennio to the input ports of QUAD Plus. This brings the device with the possibility of monitoring motion and presence in the room, as well as the light level. Depending on the detection, different response actions can be parameterised.

Please refer to the “Motion Detector” user manual, available under the QUAD Plus product section at the Zennio website (www.zennio.com), for detailed information about the functionality and the configuration of the related parameters.

Notes:

The ZN1IO-DETEC-P motion detector is compatible with a variety of    Zennio devices. However, depending on the device it is actually being connected to, the functionality may differ slightly. Therefore, please refer specifically to the aforementioned user manual.

 When  connected  to  QUAD  Plus,  the  rear  micro-switch  of  model  ZN1IO- DETEC-P should be set to position “Type B.

THERMOSTATS

 QUAD  Plus  allows  independently  enabling  and configuring  up to four   thermostat functions, with independence of the number of the inputs that have been configured.

Please refer to the specific “Zennio Thermostat” user manual available under the QUAD Plus product section at the Zennio homepage (www.zennio.com) for detailed information about the functionality and the configuration of the related parameters.

ANNEX I. COMMUNICATION OBJECTS

 Functional range” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.

Number Size I/O Flags Data type (DPT) Functional Range Name Function
1 1 Bit   C T – – – DPT_Trigger 0/1 [Heartbeat] Object to Send ‘1’ Sending of ‘1’ Periodically
2 1 Byte I C – – W – DPT_SceneControl 0-63; 128-191 [Thermostat] Scene Input Scene Value
3, 33, 63, 93 2 Bytes I C – – W – DPT_Value_Temp -273.00º – 670760.00º [Tx] Temperature Source 1 External Sensor Temperature
4, 34, 64, 94 2 Bytes I C – – W – DPT_Value_Temp -273.00º – 670760.00º [Tx] Temperature Source 2 External Sensor Temperature
5, 35, 65, 95 2 Bytes O C T R – – DPT_Value_Temp -273.00º – 670760.00º [Tx] Effective Temperature Effective Control Temperature
 

 

6, 36, 66, 96

 

 

1 Byte

 

 

I

 

 

C – – W –

 

 

DPT_HVACMode

1=Comfort 2=Standby 3=Economy 4=Building Protection  

 

[Tx] Special Mode
 

 

1-byte HVAC Mode

 

7, 37, 67, 97

1 Bit I C – – W – DPT_Ack 0/1 [Tx] Special Mode: Comfort 0 = Nothing; 1 = Trigger
1 Bit I C – – W – DPT_Switch 0/1 [Tx] Special Mode: Comfort 0 = Off; 1 = On
 

8, 38, 68, 98

1 Bit I C – – W – DPT_Ack 0/1 [Tx] Special Mode: Standby 0 = Nothing; 1 = Trigger
1 Bit I C – – W – DPT_Switch 0/1 [Tx] Special Mode: Standby 0 = Off; 1 = On
 

9, 39, 69, 99

1 Bit I C – – W – DPT_Ack 0/1 [Tx] Special Mode: Economy 0 = Nothing; 1 = Trigger
1 Bit I C – – W – DPT_Switch 0/1 [Tx] Special Mode: Economy 0 = Off; 1 = On
 

10, 40, 70, 100

1 Bit I C – – W – DPT_Ack 0/1 [Tx] Special Mode: Protection 0 = Nothing; 1 = Trigger
1 Bit I C – – W – DPT_Switch 0/1 [Tx] Special Mode: Protection 0 = Off; 1 = On
11, 41, 71, 101 1 Bit I C – – W – DPT_Window_Door 0/1 [Tx] Window Status (Input) 0 = Closed; 1 = Open
12, 42, 72, 102 1 Bit I C – – W – DPT_Ack 0/1 [Tx] Comfort Prolongation 0 = Nothing; 1 = Timed Comfort
 

 

13, 43, 73, 103

 

 

1 Byte

 

 

O

 

 

C T R – –

 

 

DPT_HVACMode

1=Comfort 2=Standby 3=Economy 4=Building Protection  

 

[Tx] Special Mode Status
 

 

1-byte HVAC Mode

 

14, 44, 74, 104

2 Bytes I C – – W – DPT_Value_Temp -273.00º – 670760.00º [Tx] Setpoint Thermostat Setpoint Input
2 Bytes I C – – W – DPT_Value_Temp -273.00º – 670760.00º [Tx] Basic Setpoint Reference Setpoint
15, 45, 75, 105 1 Bit I C – – W – DPT_Step 0/1 [Tx] Setpoint Step 0 = -0.5ºC; 1 = +0.5ºC
16, 46, 76, 106 2 Bytes I C – – W – DPT_Value_Tempd -670760.00º – 670760.00º [Tx] Setpoint Offset Float Offset Value
 

17, 47, 77, 107

 

2 Bytes

 

O

 

C T R – –

 

DPT_Value_Temp

 

-273.00º – 670760.00º

  [Tx] Setpoint Status  

Current Setpoint

18, 48, 78, 108 2 Bytes O C T R – – DPT_Value_Temp -273.00º – 670760.00º [Tx] Basic Setpoint Status Current Basic Setpoint
19, 49, 79, 109 2 Bytes O C T R – – DPT_Value_Tempd -670760.00º – 670760.00º [Tx] Setpoint Offset Status Current Setpoint Offset
 

20, 50, 80, 110

1 Bit I C – – W – DPT_Reset 0/1 [Tx] Setpoint Reset Reset Setpoint to Default
1 Bit I C – – W – DPT_Reset 0/1 [Tx] Offset Reset Reset offset
21, 51, 81, 111 1 Bit I C – – W – DPT_Heat_Cool 0/1 [Tx] Mode 0 = Cool; 1 = Heat
22, 52, 82, 112 1 Bit O C T R – – DPT_Heat_Cool 0/1 [Tx] Mode Status 0 = Cool; 1 = Heat
23, 53, 83, 113 1 Bit I C – – W – DPT_Switch 0/1 [Tx] On/Off 0 = Off; 1 = On
24, 54, 84, 114 1 Bit O C T R – – DPT_Switch 0/1 [Tx] On/Off Status 0 = Off; 1 = On
25, 55, 85, 115 1 Byte O C T R – – DPT_Scaling 0% – 100% [Tx] Control Variable (Cool) PI Control (Continuous)
26, 56, 86, 116 1 Byte O C T R – – DPT_Scaling 0% – 100% [Tx] Control Variable (Heat) PI Control (Continuous)
27, 57, 87, 117 1 Bit O C T R – – DPT_Switch 0/1 [Tx] Control Variable (Cool) 2-Point Control
  1 Bit O C T R – – DPT_Switch 0/1 [Tx] Control Variable (Cool) PI Control (PWM)
28, 58, 88, 118 1 Bit O C T R – – DPT_Switch 0/1 [Tx] Control Variable (Heat) 2-Point Control
  1 Bit O C T R – – DPT_Switch 0/1 [Tx] Control Variable (Heat) PI Control (PWM)
29, 59, 89, 119 1 Bit O C T R – – DPT_Switch 0/1 [Tx] Additional Cool Temp >= (Setpoint+Band) => “1”
30, 60, 90, 120 1 Bit O C T R – – DPT_Switch 0/1 [Tx] Additional Heat Temp <= (Setpoint-Band) => “1”
31, 61, 91, 121 1 Bit O C T R – – DPT_Switch 0/1 [Tx] PI State (Cool) 0 = PI signal 0%; 1 = PI signal greater than 0%
32, 62, 92, 122 1 Bit O C T R – – DPT_Switch 0/1 [Tx] PI State (Heat) 0 = PI signal 0%; 1 = PI signal greater than 0%
123, 127, 131, 135 2 Bytes O C T R – – DPT_Value_Temp -273.00º – 670760.00º [Ix] Current Temperature Temperature Sensor Value
124, 128, 132, 136 1 Bit O C T R – – DPT_Alarm 0/1 [Ix] Overcooling 0 = No Alarm; 1 = Alarm
125, 129, 133, 137 1 Bit O C T R – – DPT_Alarm 0/1 [Ix] Overheating 0 = No Alarm; 1 = Alarm
126, 130, 134, 138 1 Bit O C T R – – DPT_Alarm 0/1 [Ix] Probe Error 0 = No Alarm; 1 = Alarm
139, 145, 151, 157 1 Bit I C – – W – DPT_Enable 0/1 [Ix] Input Lock 0 = Unlock; 1 = Lock
 

 

 

 

 

 

140, 146, 152, 158

1 Bit   C T – – – DPT_Switch 0/1 [Ix] [Short Press] 0 Sending of 0
1 Bit   C T – – – DPT_Switch 0/1 [Ix] [Short Press] 1 Sending of 1
1 Bit I C T – W – DPT_Switch 0/1 [Ix] [Short Press] 0/1 Switching Switching 0/1
1 Bit   C T – – – DPT_UpDown 0/1 [Ix] [Short Press] Move Up Shutter Sending of 0 (Up)
1 Bit   C T – – – DPT_UpDown 0/1 [Ix] [Short Press] Move Down Shutter Sending of 1 (Down)
1 Bit   C T – – – DPT_UpDown 0/1 [Ix] [Short Press] Move Up/Down Shutter Switching 0/1 (Up/Down)
1 Bit   C T – – – DPT_Step 0/1 [Ix] [Short Press] Stop/Step Up Shutter Sending of 0 (Stop/Step Up)
1 Bit   C T – – – DPT_Step 0/1 [Ix] [Short Press] Stop/Step Down Shutter Sending of 1 (Stop/Step Down)
  1 Bit   C T – – – DPT_Step 0/1 [Ix] [Short Press] Stop/Step Shutter (Switched) Switching of 0/1 (Stop/Step Up/Down)
 

 

 

 

 

 

 

 

4 Bit

   

 

 

 

 

 

 

 

C T – – –

 

 

 

 

 

 

 

 

DPT_Control_Dimming

0x0 (Stop)

0x1 (Dec. by 100%) 0x2 (Dec. by 50%) 0x3 (Dec. by 25%) 0x4 (Dec. by 12%) 0x5 (Dec. by 6%) 0x6 (Dec. by 3%) 0x7 (Dec. by 1%) 0x8 (Stop)

0x9 (Inc. by 100%) 0xA (Inc. by 50%) 0xB (Inc. by 25%) 0xC (Inc. by 12%) 0xD (Inc. by 6%) 0xE (Inc. by 3%) 0xF (Inc. by 1%)

 

 

 

 

 

 

 

 

[Ix] [Short Press] Brighter
 

 

 

 

 

 

 

 

Increase Brightness

 

 

 

4 Bit

   

 

 

C T – – –

 

 

 

DPT_Control_Dimming

0x0 (Stop)

0x1 (Dec. by 100%)

0x8 (Stop)

0x9 (Inc. by 100%)

0xF (Inc. by 1%)

 

 

 

[Ix] [Short Press] Darker
 

 

 

Decrease Brightness

 

 

 

4 Bit

   

 

 

C T – – –

 

 

 

DPT_Control_Dimming

0x0 (Stop)

0x1 (Dec. by 100%)

0x8 (Stop)

0x9 (Inc. by 100%)

0xF (Inc. by 1%)

 

 

 

[Ix] [Short Press] Brighter/Darker
 

 

 

Switch Bright/Dark

1 Bit   C T – – – DPT_Switch 0/1 [Ix] [Short Press] Light On Sending of 1 (On)
1 Bit   C T – – – DPT_Switch 0/1 [Ix] [Short Press] Light Off Sending of 0 (Off)
1 Bit I C T – W – DPT_Switch 0/1 [Ix] [Short Press] Light On/Off Switching 0/1
1 Byte   C T – – – DPT_SceneControl 0-63; 128-191 [Ix] [Short Press] Run Scene Sending of 0 – 63
1 Byte   C T – – – DPT_SceneControl 0-63; 128-191 [Ix] [Short Press] Save Scene Sending of 128 – 191
1 Bit I/O C T R W – DPT_Switch 0/1 [Ix] [Switch/Sensor] Edge Sending of 0 or 1
1 Byte   C T – – – DPT_Value_1_Ucount 0 – 255 [Ix] [Short Press] Constant Value (Integer) 0 – 255
1 Byte   C T – – – DPT_Scaling 0% – 100% [Ix] [Short Press] Constant Value (Percentage) 0% – 100%
2 Bytes   C T – – – DPT_Value_2_Ucount 0 – 65535 [Ix] [Short Press] Constant Value 0 – 65535
            (Integer)  
2 Bytes   C T – – – 9.xxx -671088.64 – 670760.96 [Ix] [Short Press] Constant Value (Float) Float Value
 

141, 150, 156, 162

1 Byte I C – – W – DPT_Scaling 0% – 100% [Ix] [Long Press] Dimming Status (Input) 0% – 100%
1 Byte I C – – W – DPT_Scaling 0% – 100% [Ix] [Long Press] Shutter Status (Input) 0% = Top; 100% = Bottom
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

142, 148, 154, 160

1 Bit   C T – – – DPT_Switch 0/1 [Ix] [Long Press] 0 Sending of 0
1 Bit   C T – – – DPT_Switch 0/1 [Ix] [Long Press] 1 Sending of 1
1 Bit I C T – W – DPT_Switch 0/1 [Ix] [Long Press] 0/1 Switching Switching 0/1
1 Bit   C T – – – DPT_UpDown 0/1 [Ix] [Long Press] Move Up Shutter Sending of 0 (Up)
1 Bit   C T – – – DPT_UpDown 0/1 [Ix] [Long Press] Move Down Shutter Sending of 1 (Down)
1 Bit   C T – – – DPT_UpDown 0/1 [Ix] [Long Press] Move Up/Down Shutter Switching 0/1 (Up/Down)
1 Bit   C T – – – DPT_Step 0/1 [Ix] [Long Press] Stop/Step Up Shutter Sending of 0 (Stop/Step Up)
1 Bit   C T – – – DPT_Step 0/1 [Ix] [Long Press] Stop/Step Down Shutter Sending of 1 (Stop/Step Down)
1 Bit   C T – – – DPT_Step 0/1 [Ix] [Long Press] Stop/Step Shutter (Switched) Switching of 0/1 (Stop/Step Up/Down)
 

 

 

4 Bit

   

 

 

C T – – –

 

 

 

DPT_Control_Dimming

0x0 (Stop)

0x1 (Dec. by 100%)

0x8 (Stop)

0x9 (Inc. by 100%)

0xF (Inc. by 1%)

 

 

 

[Ix] [Long Press] Brighter
 

 

 

Long Pr. -> Brighter; Release -> Stop

 

 

 

4 Bit

   

 

 

C T – – –

 

 

 

DPT_Control_Dimming

0x0 (Stop)

0x1 (Dec. by 100%)

0x8 (Stop)

0x9 (Inc. by 100%)

0xF (Inc. by 1%)

 

 

 

[Ix] [Long Press] Darker
 

 

 

Long Pr. -> Darker; Release -> Stop

 

 

 

4 Bit

   

 

 

C T – – –

 

 

 

DPT_Control_Dimming

0x0 (Stop)

0x1 (Dec. by 100%)

0x8 (Stop)

0x9 (Inc. by 100%)

0xF (Inc. by 1%)

 

 

 

[Ix] [Long Press] Brighter/Darker
 

 

 

Long Pr. -> Brighter/Darker; Release -> Stop

1 Bit   C T – – – DPT_Switch 0/1 [Ix] [Long Press] Light On Sending of 1 (On)
1 Bit   C T – – – DPT_Switch 0/1 [Ix] [Long Press] Light Off Sending of 0 (Off)
  1 Bit I C T – W – DPT_Switch 0/1 [Ix] [Long Press] Light On/Off Switching 0/1
1 Byte   C T – – – DPT_SceneControl 0-63; 128-191 [Ix] [Long Press] Run Scene Sending of 0 – 63
1 Byte   C T – – – DPT_SceneControl 0-63; 128-191 [Ix] [Long Press] Save Scene Sending of 128 – 191
1 Bit O C T R – – DPT_Alarm 0/1 [Ix] [Switch/Sensor] Alarm: Breakdown or Sabotage 1 = Alarm; 0 = No Alarm
2 Bytes   C T – – – 9.xxx -671088.64 – 670760.96 [Ix] [Long Press] Constant Value (Float) Float Value
2 Bytes   C T – – – DPT_Value_2_Ucount 0 – 65535 [Ix] [Long Press] Constant Value (Integer) 0 – 65535
1 Byte   C T – – – DPT_Scaling 0% – 100% [Ix] [Long Press] Constant Value (Percentage) 0% – 100%
1 Byte   C T – – – DPT_Value_1_Ucount 0 – 255 [Ix] [Long Press] Constant Value (Integer) 0 – 255
143, 149, 155, 161 1 Bit   C T – – – DPT_Trigger 0/1 [Ix] [Long Press/Release] Stop Shutter Release -> Stop Shutter
 

 

144, 147, 153, 159

1 Byte I C – – W – DPT_Scaling 0% – 100% [Ix] [Short Press] Shutter Status (Input) 0% = Top; 100% = Bottom
1 Byte I C – – W – DPT_Scaling 0% – 100% [Ix] [Short Press] Dimming Status (Input) 0% – 100%
163 1 Byte I C – – W – DPT_SceneNumber   [Motion Detector] Scene Input Scene Value
164 1 Byte   C T – – – DPT_SceneControl 0-63; 128-191 [Motion Detector] Scene Output Scene Value
165, 194, 223, 252 1 Byte O C T R – – DPT_Scaling 0% – 100% [Ix] Luminosity 0-100%
166, 195, 224, 253 1 Bit O C T R – – DPT_Alarm 0/1 [Ix] Open Circuit Error 0 = No Error; 1 = Open Circuit Error
167, 196, 225, 254 1 Bit O C T R – – DPT_Alarm 0/1 [Ix] Short Circuit Error 0 = No Error; 1 = Short Circuit Error
168, 197, 226, 255 1 Byte O C T R – – DPT_Scaling 0% – 100% [Ix] Presence State (Scaling) 0-100%
 

 

169, 198, 227, 256

 

 

1 Byte

 

 

O

 

 

C T R – –

 

 

DPT_HVACMode

1=Comfort 2=Standby 3=Economy 4=Building Protection  

 

[Ix] Presence State (HVAC)
 

Auto, Comfort, Standby, Economy, Building Protection

170, 199, 228, 257 1 Bit O C T R – – DPT_Occupancy 0/1 [Ix] Presence State (Binary) Binary Value
  1 Bit O C T R – – DPT_Ack 0/1 [Ix] Presence: Slave Output 1 = Motion Detected
171, 200, 229, 258 1 Bit I C – – W – DPT_Window_Door 0/1 [Ix] Presence Trigger Binary Value to Trigger the Presence Detection
172, 201, 230, 259 1 Bit I C – – W – DPT_Ack 0/1 [Ix] Presence: Slave Input 0 = Nothing; 1 = Detection from slave device
173, 202, 231, 260 2 Bytes I C – – W – DPT_TimePeriodSec   [Ix] Presence: Waiting Time 0-65535 s.
174, 203, 232, 261 2 Bytes I C – – W – DPT_TimePeriodSec   [Ix] Presence: Listening Time 1-65535 s.
175, 204, 233, 262 1 Bit I C – – W – DPT_Enable 0/1 [Ix] Presence: Enable According to parameters
176, 205, 234, 263 1 Bit I C – – W –     [Ix] Presence: Day/Night According to parameters
177, 206, 235, 264 1 Bit O C T R – – DPT_Occupancy 0/1 [Ix] Presence: Occupancy State 0 = Not Occupied; 1 = Occupied
178, 207, 236, 265 1 Bit I C – – W – DPT_Ack 0/1 [Ix] External Motion Detection 0 = Nothing; 1 = Motion detected by an
              external sensor
179, 184, 189, 208,

213, 218, 237, 242,

247, 266, 271, 276

 

1 Byte

 

O

 

C T R – –

 

DPT_Scaling

 

0% – 100%

  [Ix] [Cx] Detection State (Scaling)  

0-100%

180, 185, 190, 209,

214, 219, 238, 243,

248, 267, 272, 277

 

 

1 Byte

 

 

O

 

 

C T R – –

 

 

DPT_HVACMode

1=Comfort 2=Standby 3=Economy 4=Building Protection  

 

[Ix] [Cx] Detection State (HVAC)
 

Auto, Comfort, Standby, Economy, Building Protection

181, 186, 191, 210,

215, 220, 239, 244,

249, 268, 273, 278

 

1 Bit

 

O

 

C T R – –

 

DPT_Switch

 

0/1

  [Ix] [Cx] Detection State (Binary)  

Binary Value

182, 187, 192, 211,

216, 221, 240, 245,

250, 269, 274, 279

 

1 Bit

 

I

 

C – – W –

 

DPT_Enable

 

0/1

  [Ix] [Cx] Enable Channel  

According to parameters

183, 188, 193, 212,

217, 222, 241, 246,

251, 270, 275, 280

 

1 Bit

 

I

 

C – – W –

 

DPT_Switch

 

0/1

  [Ix] [Cx] Force State  

0 = No Detection; 1 = Detection

Join and send us your inquiries

about Zennio devices:

https://support.zennio.com

Zennio Avance y Tecnología S.L. C/ Río Jarama, 132. Nave P-8.11 45007 Toledo (Spain).

Tel. +34 925 232 002

www.zennio.com info@zennio.com

Documents / Resources

Zennio ZNIO-QUADP QUAD Plus Analogue/Digital Input Module [pdf] User Manual
ZNIO-QUADP, QUAD Plus Analogue Input Module, QUAD Plus Digital Input Module

References

Leave a comment

Your email address will not be published. Required fields are marked *