YHDC SCT006L Split Core Current Transformer Owner’s Manual
YHDC SCT006L Split Core Current Transformer

Characteristics

Safety lock buckle, easy installation, cable output.

Technical index

  • Mounting type: Free hanging (In-Line)
  • Material of core: Ferrite
  • Applicable standards: GB20840-2014
  • Operating temperature: -25℃ ~ +60℃
  • Storage temperature: -30℃ ~ +90℃
  • Frequency range: 50Hz-1KHz
  • Waterproof grade: IP00
  • Dielectric strength: Input (bare conductor)/Output AC 800V/1min 50Hz
  • Output/housing AC 3.5KV/1min 50Hz

Electrical parameters: The following parameters are typical values. The actual values shall be subject to the actual measurement of the product

Rated input 1 5 10 20 A
Rated output 1 2.5 5 10 5 10 20 20 25 mA
Turns ratio 1:1000 1:2000 1:1000 1:500 1:2000 1:1000 1:500 1:1000 1:800
Sampling resistance 5 10 5 5 10 5 5 5 5 0
Accuracy 1 %
Weight 25 g

Specifications of cable:

2 x 0.2mm² two core sheathed wire.

The length of cable: 100cm~105cm

Cable

TVS: Transient Voltage Suppressor (7.5V)

Current output type

Secondary is not allowed to open circuit

Dimensions (in:mm±0.5)

Front view

Dimension

Side view

Dimension

Dimension
Dimension
Dimension
Dimension
Dimension
Dimension
Dimension
Dimension
Dimension
Dimension
Dimension
Dimension
Dimension
Dimension
Dimension
Dimension

Logo

 

Documents / Resources

YHDC SCT006L Split Core Current Transformer [pdf] Owner's Manual
SCT006L Split Core Current Transformer, SCT006L, Split Core Current Transformer, Core Current Transformer, Current Transformer, Transformer

References