VISIONIS VIS-AXESS-1D-ETL-PCB Network Access Control Panel
Specifications
- Working Voltage: DC 12V
- Working Current: Non-loaded
Product Information
The product is a device designed to operate at a working voltage of DC 12V. It is intended to be used with non-loaded current specifications.
Product Usage Instructions
- Power Supply:
Connect the device to a power source with a DC output of 12V. Ensure that the power supply meets the required specifications to avoid damage to the product. - Device Operation:
Once connected to the power supply, operate the device according to the specific functions outlined in the user manual or product guide provided. - Maintenance:
Regularly check for any signs of wear and tear, and follow maintenance guidelines provided by the manufacturer to ensure optimal performance and longevity of the product.
Frequently Asked Questions (FAQ)
Q: What should I do if the device does not power on?
A: Check the power supply connection and ensure that it is providing the correct voltage output. If the issue persists, contact customer support for further assistance.
Q: Can I use a power supply with a different voltage?
A: No, it is recommended to use a power supply with a DC output of 12V as using a different voltage may damage the device.
Device Parameter
- Working Voltage: DC 12V
- Working Current: Non-loaded <200mA
- Working Temperature: -20°C – 50°C (-4°F – 122°F)
- Working Humidity: 10° – 90°
- Power Consumption: <3W
- Size: 85x157x20mm (3.35×6.18×0.79in.)
- Communication Mode: TCP/IP
- Communication Rate: 10/100M (TCP/IP)
- Extension Communication: RS485
- Users Capacity: 20.000
- Records Capacity: 70.000
- Max. Doors: 2
- Dry Contact Input: 6
- Dry Contact Output: 3
- Access Group: 200 Groups
- Default IP Address: 192.168.0.245
- Default Communication Password: NULL
IMPORTANT: These access control panels (Version 2.0) are only compatible with access control panels (Version 2.0) and with the Titan VSAxess software. They are not compatible with access control panels (Version 1.0) nor with VSAxess software.
Basic Function
- First card open
- Multi-card open
- Anti-passback
- Multi-door interlock
- Card, password, card+password, card or password open mode
- Different time differente open mode
- Transmission encryption setup
- Self-checking function
- Remote control
- Wiegand format can be self-defined
- Add card without software
- Multi-channel connection (max. 3 channels)
- Real-time events active or passive upload
- Arm/disarm by card
- Arm/disarm by software
- Relieve alarm by software
- Multi-event linkage alarm
- One event related to multi-relay trigger
- Alarm delay turn off
- Capacity can be expanded
- Self-defined door lock relay
- Self-defined control door quantity
- Door latch mode
- Active door normal open mode by card
- Timed automatic normal open mode
- Timed invalid for exit button
- Normal open time
- Normal open holiday forbidden schedule
- Access time schedule
- Forbid access holiday schedule
- Door lock delay setup
- Access group setup
- Threaten code setup
- Force open/close door
- Open door by software
- Relieve normal open by card
- Relieve card and card valid date setup
- Expand RS485 communication
- Real-time monitoring door and relay state
Wiring Introduction
Wiring Position | Wire Model | Remark |
Power Supply – Access Controller | RVV2*1.0 | Distance < 100M |
Access Controller – Reader | RVV4*0.5 | Distance 60M, max. can not over 100M. |
Access Controller – Electric Lock | RVV4*1.0(Door-magnet feedback) | Distance < 150M |
Access Controller – Exit Button | RVV2*0.5 | Distance < 200M |
Access Controller – IR Alarm | RVV2*1.0 | Distance < 200M |
Access Controller – Sound-light Alarm | RVV2*1.0 | Distance < 150M |
RS485 Communication Cable | RVVP2*1.0 | Distance < 1000M, shield layer connect to ground |
TCP/IP Communication Cable | CAT-5 | Distance < 100M |
Connection
I/O | Device | Standard | Quantity | Setup |
Input | Reader | Wiegand 26-40 | 2 | as function |
Output | Electric Lock | Switch Signal | 1/2 | as doors |
Input | Door-magnet | Switch Signal | 1/2 | Support |
Output | Sound-light alarm | Switch Signal | 1/2 | |
Input | IR Sensor/Smoke Sensor/Others | Switch Signal | 2 | |
Input | Exit button | Switch Signal | 1/2 | Support |
Input | RS485 device | Communication | 1 |
LED&Button Instruction
LED | RL1 | RL2 | RL3 |
One-door | Lock1 | Magnet Alarm1 | Alarm Output1 |
Two-door | Lock1 | Lock2 | Magnet Alarm1 |
- Power: 12V power LED
- RUN: Device run LED
- RDOK: Read card status LED
- 2DOOR: The status LED of 2 doors
- RDOK + RUN: Device enter online upgrade mode.
- RESET Key: It is used to reboot device and clear communication password. After power off, power on device again and press RESET button for 3 seconds, then you can clear communication password
Disclaimer
The document provides information according to products specification. Visionis does not undertake any type of guarantee, express or implied warranties, including any implied merchantability, specific purposes or the infringement. The information in the document are changed without prior notice. Visionis and its associated sales agents special statement does not assume the result of the use of Visionis equipment of any and all direct, indirect, special, in general, by chance, inevitably, punitive damages. Any user’s improper operation or use of the environment problem caused by direct or indirect losses, user pays full responsibility, equipment manufacturers and related sales agents does not undertake any responsability.
Wiring Diagram of Access Controller
Quick Start
Notice
- Controller IP must be the same as you set.
- Controller model must be the same as device type. You can detect controller and check the device type in task report.
- Usually we can use ping command to test the device physical connection.
- Controller Address is only valid when use MS series controller or TCP/IP to RS485 connector, otherwise, the default is 0.
- Wrong time may no access and incorrect access record. Please adjust the time.
- Initialize the controller will clear the device records, please make sure the records are saved.
Notice
- If there are employees with the same name, you can separate them by code. Code is unique.
- Card number is decimal
- Default administrator access group can pass anywhere anytime, it is the top authority.
- Each employee can access with a separate 6-digit password.
- Impor from Excel can quick register employees.
Notice
- Search function is only valid in the same LAN, as adopt UDP communication protocol, across gateway will forbid communication.
- When connect network cable to device, Ethernet port green light is on, yellow light flash.
- Please note that IP address can not be the same.
- Domain name can be used in the software.
Notice
Once installed the Titan Vsaxess Login information is: Username: Administrator Password:
There is no default Password. Just click OK and you can login. You can set a Password under “Platform” and “Change password”.
The manual is a quick start for system, the user can refer to software help file or other technical files for details.
Documents / Resources
![]() |
VISIONIS VIS-AXESS-1D-ETL-PCB Network Access Control Panel [pdf] User Guide VIS-AXESS-1D-ETL-PCB, VIS-AXESS-1D-ETL-PCB Network Access Control Panel, Network Access Control Panel, Access Control Panel, Control Panel, Panel |