UNI-T UTE9802 Power Meter
Product Specification
IDN?
This query command reads the identification string of the instrument. Return value example:UTE9802,SN202111051001,V1.12,V0.02
MEAS:VOLT?
Read the measured voltage value. Return value example:220.0V,OL(Out of range, the same below)
MEAS:CURR?
Read the measured current value. Return value example:5.12A or 500.1mA
MEAS:POW?
Read the measured power value. Return value example:350.02W
MEAS:PF?
Read the measured power factor value. Return value example:0.501
MEAS:FREQ?
Read the measured frequency value. Return value example:50.01Hz
MEAS:ALL?
Read back all measured values at one time: measurement mode, voltage, current, power, power factor, frequency, separated by commas.
Example:AC,220.1V,5.01A,1103.2W,0.901,49.99Hz
Example:DC,220.1V,5.01A,1103.2W
Example:RMS,220.1V,5.01A,1103.2W,0.998,49.99Hz
MEAS:MODE?
Read the measurement mode. Return value example:AC,DC,RMS(AC+DC)
SET:MODE XXX
Set the measurement mode. Return value example:SUCCESS,ERR
RANG:VOLT?
Read the voltage range. Return value example:AUTO 、75V、150V、300V、600V
RANG:VOLT XXXX
Set the voltage range. Return value example:SUCC,ERR
RANG:CURR?
Read the current range. Return value example:AUTO 、500mA、2A、8A、20A
CURR XXXX
Set the current range. Return value example:SUCC,ERR
CURR:HIG XXXX
Set the upper limit of current alarm.
Example CURR:HIG 5A. Return value example:SUCC,ERR
CURR:HIG?
Read current alarm upper limit value.
CURR:LOW XXXX
Set the lower limit of current alarm.
Example:CURR: LOW 5A. Return value example:SUCC, ERR
CURR:LOW?
Read the lower limit value of current alarm.
POW:HIG XXXX
Set the upper limit of power alarm.
Example:POW:HIG 5W. Return value example:SUCC, ERR
POW:HIG?
Read the upper limit value of power alarm.
POW:LOW XXXX
Set the lower limit of power alarm.
Example:POW:LOW 5W. Return value example:SUCC,ERR
POW:LOW?
Read the lower limit value of power alarm.
ALAR:DELA?
Read the alarm delay value. Return value example:0.2S
ALAR:DELA XXX
Set the alarm delay value. Return value example:SUCC,ERR
STA?
Read alarm signs, return current and power alarm signs. Separated by commas. Example:
Return NOR,NOR,Indicates normal.
Return LOW,HIG,Indicates current lower limit alarm and power upper limit alarm.