UBIBOT UB-DWT-N1 Dry and Wet Bulb Temperature Sensor

UBIBOT-UB-DWT-N1-Dry-and-Wet-Bulb-Temperature-Sensor-PRODUCT

Specifications:

  • Product Model: UB-DWT-N1
  • Power Supply: DC 5-12V
  • Measurement Data:
    • Dry Bulb Temperature
    • Wet Bulb Temperature
    • Atmospheric Humidity
    • Atmospheric Pressure
    • Dew Point Temperature
  • Working Environment: -40~60°C, 0~80%RH
  • Response Time: 1s
  • Communication Protocol: RS485 Modbus RTU Protocol
  • Baud Rate: 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s (default), 19200 bit/s

Product Usage Instructions

Installation:

  1. Mount the sensor in the desired location using the provided mounting bracket.
  2. Ensure the sensor is securely installed to prevent any movement during operation.

Data Retrieval:
To retrieve data from the sensor, follow the Modbus-RTU communication protocol as described below:

Communication Basic Parameters:

  • Coding System: 1-bit CRC Check
  • Baud Rate: 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s (default), 19200 bit/s

Data Frame Format:

The Modbus-RTU communication protocol format includes:

  • Address code: Default 0xC3
  • Function code: Support function codes 0x03 (read-only) and 0x06 (read/write)
  • Data area: N bytes of 16-bit data with high byte first
  • Error check: 16-bit CRC code

Register Address Definitions:

Address (hex) Description Data Length
0x0000 Wet Bulb Temperature (1 byte)
0x0001 Dew Point Temperature (1 byte)
0x0002 Dry Bulb Temperature (1 byte)
0x0003 Air Pressure (1 byte)
0x0004 – 0x0006 Relative Humidity, Absolute Humidity, Vapor Pressure (1 byte
each)
0x0007 Saturation (1 byte)
0x0008 Specific Volume (1 byte)
0x0009 – 0x0064 Specific Enthalpy, Slave Address (1 byte each)

Frequently Asked Questions (FAQ):

  • Q: What is the working voltage range for this sensor?
    A: The sensor works with a DC power supply ranging from 5-12V.
  • Q: What communication protocol does the sensor support?
    A: The sensor supports the Modbus-RTU protocol over RS485 communication.
  • Q: How can I calculate the wet bulb temperature using this sensor?
    A: The sensor provides the necessary data to calculate the wet bulb temperature based on the measured dry bulb temperature, humidity, and atmospheric pressure values.

Introduction

Dry and wet bulb temperature sensor adopts original imported sensor. It has stable measurement data, high precision, strong anti-interference ability and long service life.
It can accurately measure the dry bulb temperature, humidity and atmospheric pressure value, and also can calculate the wet bulb temperature, dew point temperature, relative humidity and other data.

Applications

It is suitable for environmental monitoring, agrometeorology and other monitoring environments.

Features

  • Multi-parameter in one, including dry bulb temperature, wet bulb temperature, humidity, atmospheric pressure and more.
  • With mounting bracket, easy to install and use.
  • Supporting Modbus-RTU protocol
  • DC 5-12V wide voltage supply

Specifications

Specification
Product Model UB-DWT-N1
Power Supply DC 5-12V
 

 

Measurement Data

Dry Bulb Temperature Range: -40~80℃, Accuracy: ±0.2℃ (@0~65℃)
Wet Bulb Temperature Range: -40~80℃, Accuracy: ±0.3℃
Atmospheric Humidity Range: 0-100%, Accuracy: ±2%RH (@10~90%RH)
Atmospheric Pressure Range: 26~126kPa, Accuracy: ±50Pa
Dew Point Temperature Range: -90℃~80℃, Accuracy: ±0.3℃
Working Environment -40~60℃,0%~80%RH
Response Time ≤1s
Communication Protocol RS485 Modbus RTU Protocol
RS485 Address 0xC3
Baud Rate 1200 bit/s,2400 bit/s, 4800 bit/s, 9600 bit/s(default), 19200

bit/s

Communication protocols

Communication Basic Parameter
Coding System 8–bit binary
Data Bit 8 bits
Parity Checking Bit none
Error Checking CRC Check
Baud Rate 1200 bit/s,2400 bit/s, 4800 bit/s, 9600 bit/s(default), 19200 bit/s

Communication basic parameters

Data Frame Format
The Modbus-RTU communication protocol is used in the following format:

  • Initial structure ≥ 4 bytes in time.
  • Address code: 1 byte, default 0xC3.
  • Function code: 1 byte, support function code 0x03 (read-only) and 0x06 (read/write).
  • Data area: N bytes, 16-bit data, high byte comes first.
  • Error check: 16-bit CRC code.
  • End structure ≥ 4 bytes of time
Request
Slave Address Function Code Register Address No. of Registers CRC LSB CRC MSB
1 byte 1 byte 2 bytes 2 bytes 1 byte 1 byte
Response
Slave Address Function Code No. of Bytes Content 1 Content 1 Content n CRC
1 byte 1 byte 1 byte 2 bytes 2 bytes 2 bytes 2 bytes

Register Address

Register Address
Address

(hex)

Content Data

Length

Function

Code

Description of definitions
0x0000 Wet Bulb

Temperature

1 byte 03 Signed 16-bit integer data, divided by 10 with one decimal place,

in [℃]

0x0001 Dew Point

Temperature

1 byte 03 Signed 16-bit integer data, divided by 10 with one decimal place,

in [℃]

0x0002 Dry Bulb

Temperature

1 byte 03 Signed 16-bit integer data, divided by 10 with one decimal place,

in [℃]

0x0003 Air Pressure 1 byte 03 Unsigned 16-bit integer data, divided by 100 with two decimal

places, in [kPa]

0x0004 Relative

Humidity

1 byte 03 Unsigned 16-bit integer data, divided by 10 with one decimal

place, in [0~100%]

0x0005 Absolute

Humidity

1 byte 03 Unsigned 16-bit integer data, divided by 100 with two decimal

places, in [gwater/kgAIR]

0x0006 Vapor Pressure 1 byte 03 Unsigned 16-bit integer data, actual value, in [kPa]
0x0007 Saturation 1 byte 03 Unsigned 16-bit integer data, divided by 100 with two decimal

places, in [-]

0x0008 Specific Volume 1 byte 03 Unsigned 16-bit integer data, divided by 1000 with three

decimal places, in [m3/kg]

0x0009 Specific

Enthalpy

4 bytes 03 IEEE75 standard 32-bit floating point number, in [J/kg]
0x0064 Slave Address 1 byte 06 1~255,default 195(0xC3)