TOSHIBA RS4003Z VF-S11 RS485 Built-In Board Option
NOTICE
- Make sure that this instruction manual is delivered to the end user of the RS485 built-in option board.
- Read this manual before installing or operating the RS485 built-in board option. And keep it in a safe place for reference.
- All information contained in this manual are subject to change without notice. Please confirm the latest information on our website www.inverter.co.jp
Safety precautions
On the inverter and in its instruction manual, important information is contained for preventing injuries to users and damages to assets and for proper use of the device. Read the instruction manual attached to VF-S11 along with this instruction manual for completely understanding the safety precautions, the symbols, and the indications shown below. Please adhere to the contents of these manuals at all times.
Explanation of markings
Marking | Meaning of marking |
Warning |
Indicates that errors in operation may lead to death or serious injury. |
Caution |
Indicates that errors in operation may lead to injury (*1) to people or that these errors may cause damage to physical property. (*2) |
- Such things as injury, burns or shock that will not require hospitalization or long periods of outpatient treatment.
- Physical property damage refers to wide-ranging damage to assets and materials.
Meanings of symbols
Marking | Meaning of marking |
![]() |
Indicates prohibition (Do not do it).
What is prohibited will be described in or near the symbol in either text or picture form. |
![]() |
Indicates something mandatory (must be done).
What is mandatory will be described in or near the symbol in either text or picture form. |
![]() |
Indicates warning.
What is warned will be described in or near the symbol in either text or picture form. Indicates caution. What the caution should be applied to will be described in or near the symbol in either text or picture form. |
Limitation of use
Safety precaution: Never use this unit with any device other than TOSVERT VF-S11 series inverters. Doing so may cause an accident.
Handling in general
Warning | |
Never Disassemble |
Disassembling the product could cause electric shocks, fire or injuries. For repairs, call your agency. |
Prohibited |
|
Mandatory |
Neglect of these conditions could lead to fire. For repairs, call your agency. |
Transportation and installation
Warning | |
Prohibited |
Operating a defective inverter could lead to electric shocks or fire. For repairs, call your agency.
It could catch fire if the product sparks because of a breakdown and the like.
It could lead to electric shocks or fire. |
Mandatory |
it could lead to breakdown. |
![]() Caution |
|
Wiring
Warning | |
Mandatory |
|
About operation
Warning | |
Prohibited |
|
About disposal of the product
Caution | |
Mandatory |
If the collection, transport and disposal of industrial waste is done by someone who is not licensed for that job, it is a punishable violation of the law. (Laws in regard to cleaning and processing of waste materials) (*) Persons who specialize in the processing of waste and known as “industrial waste product collectors and transporters” or “industrial waste disposal persons.” |
Notes on use
NOTES | |
|
Introduction
Thank you for purchasing the “RS485 built-in board option (RS4003Z)” for the TOSVERT VF-S11 inverter. Installing this unit in the VF-S11 and using it together, data communication can be made with a host computer or other device via RS485. Please read the entire manual carefully before attempting to control your inverter via RS485 serial connection. Besides this instruction manual, the “VF-S11 Serial Communication Function Manual” is required to develop software communicating with VF-S11. In such a case, please get in touch with our branch offices or sales offices. (“VF-S11 Serial Communication Function Manual”: E6581222) This manual is also aimed at the operator using the ” RS485 built-in board option”, so please use it for future maintenance and inspection.
Explanation of model number of RS485 Option Unit
Check of accessories
RS485 built-in board option is shipped together with the following items in the package. Contact your sales agent if any of these is missing.
- (1) RS485 built-in board option …… 1 unit (RS4003Z)
- The instruction manual of RS485 built-in board option (Japanese)……1 copy (E6581229)
- The instruction manual of RS485 built-in board option (English)……1 copy (E6581230)
- RS485 built-in board option cabling label…… 1 pcs.
- Type form label 2 pcs.
- (Please refer to Page.8 about the label sticking positions)
Overview
Installing this option unit in VF-S11, a network of data communication with multiple inverters connected with a PLC, computer or other devices via RS485, can be configured. Up to 32 units of this option can be connected to the network.
Communication specifications
RS485 transmission specification
Item | Specifications |
Interface | Conforming to EIA RS485 standard |
Configuration | 4-wire/2-wire (switch selectable)
Bus type (A terminating resistor is required at both ends of the system) |
Transmission method | Half-duplex |
Maximum communication distance | 1,000m *Please refer to Page.12. |
Maximum number of connectable option units | 32 units (31 units when PC is connected) |
Communication line isolation method | No isolation |
Terminating resistor | Built-in resistors (110W) can be enable |
Communication speed | 1200/2400/4800/9600/19200 baud rates are selectable (parameter f800 is set) |
Inverter number | Settable from 1 to 15 using SW5
When SW5 is set to 0, the inverter number set with parameter f802 becomes valid. |
Common serial communication
Common serial option can be used. ( Please use the RS20035-1 as the RS232C communication cable. )
However, when common serial option is used, communication will be forcefully switched to the common serial option, thus communication via RS485 is disabled.
Warning | |
![]() Prohibited |
|
Names and functions
The external view of this option and the name of each part are shown below:
- SW1: Wiring method (Set the two switches to the same side.)
- 2: 2-wire method (RXA and TXA are shorted, and RXB and TXB are shorted.)
- 4: 4-wire method
- SW2: Terminating resistor setting (Connect terminating resistors only to both ends of each system.)
- R: Reception side
- T: Transmission side
- S: Terminating resistor connected (1/2W, 110Ω)
- O: Terminating resistor not connected
- SW3: SINK/SOURCE selection (Set the two switches on the same side.)
- SINK/SOURCE selection of input terminal can be made.
- SW4: VIA terminal function selection (VIA terminal function can be selected.)
- SOURCE: Logic input (Source), the internal pull-down resistor is inserted between the VIA terminal and the CC terminal.
- A: Analog input
- SINK: Logic input (Sink), the internal pull-up resistor is inserted between the VIA terminal and the P24 terminal.
- To use this as a logic input, it is necessary to set the parameters (3 or 4 of f109, f118).
- SW5: Inverter number setting
- Inverter numbers 1 to 15 can be set. When 0 is set, the setting of parameter f802 becomes valid.
- Common serial connector
- A common serial option can be used but when the common serial function is used (connected),
- communication via RS485 is disabled.
- Terminal blocks (Please refer to Page 10 for the function of each terminal block.)
- M3 screw (tightening torque: 0.5 N·m)
- Use a flat blade screwdriver with a 0.6 mm thick and 3.5 mm width blade.
Connection to the device
Installation method
Install the RS485 built-in board option to VF-S11 as follows:
- Turn off the input power of VF-S11 and wait for at least ten minutes and then check that the CHARGE lamp on VF-S11 is no longer lit.
- Open the VF-S11 front cover, remove the board fixing screw and take out the VF-S11 standard terminal block board.
- (Be careful not to lose the board fixing screw when removed since it may be used again.)
- Install the RS485 built-in board option and secure it with the board-fixing screw.
- (M3 tapping screw tightening torque: 0.7 to 0.8N・m)
- Stick the RS4003Z cabling label on the standard cabling label stuck on the back of the VF-S11 cover. And stick the RS4003Z type form label near the standard name plate. (Be careful not to coverslips on the VF-S11 main unit.
To install or remove the terminal block board, make it slide in or out in parallel with the board.
Description of terminals
Control circuit terminals
Termina l symbol | I/O type | Function | Electrical specifications |
F |
Input |
Multifunctional programmable contact input. Shorting across F-CC causes forward rotation; opening causes slowdown and stop. (When SINK logic is selected and ST is always ON.) |
No voltage contact input 24 VDC, 5mA or less
* SINK/SOURCE can be selected with SW3. |
R |
Input |
Multifunctional programmable contact input. Shorting across R-CC causes reverse rotation; opening causes slowdown and stop. (When SINK logic is selected and ST is always ON.) | |
RES |
Input |
Multifunctional programmable contact input. Shorting across RES-CC causes a held reset when the inverter protector function is operating. Note that when the inverter is operating normally, it will not operate even if there is a short across
RES-CC. (When SINK logic is selected.) |
|
VIA |
Input |
Multifunction programmable analog input. Factory default setting:
0~60Hz frequency setting with 0~10 VDC input. In addition, this terminal can be used as a multifunctional contact input using the parameters (f109 and f118) and SW4 selector switch. |
10VDC
Internal impedance: 30kW |
CC | Common to Input/Output | Control circuit’s equipotential terminal | |
P24 | Output | 24 VDC power supply output | 24VDC-100mA |
FLA FLB FLC |
Output |
Multifunctional programmable relay contact outputs The standard factory setting is set to detect the activation of the inverter protection function.
Contact across FLA-FLC is closed and FLB-FLC is opened during protection function operation. |
250VAC-1A
(cosφ=1) 30VDC-0.5A 250VAC-0.5A (cosφ=0.4A) |
TXA |
RS485 |
RS485 transmission data (+) terminal | |
TXB | RS485 transmission data (-) terminal | ||
RXA | RS485 reception data (+) terminal | ||
RXB | RS485 reception data (-) terminal | ||
SG | RS485 signal ground terminal | ||
SHLD |
RS485 shield terminal. This terminal is not connected to other circuits in this unit. Ground this terminal in a location separated from the ground of power line. |
For internal circuits, please refer to the VF-S11 Instructions Manual.
Warning | |
![]() Prohibited |
|
![]() Mandatory |
|
Initial settings
After reading the previous page for completely understanding the safety, set the initial according to below.
- Turn off the input power of VF-S11, wait for at least 10 minutes and then check that the CHARGE lamp on VF-S11 main unit is unlit.
- Open VF-S11 front cover and set the SINK/SOURCE of contact input with SW3 and SW4. (Check that the two switches of SW3 are on the same side.)
- Set the RS485 wiring method (4-wire/2-wire) using SW1. (Check that the two switches of SW1 are on the same side.) The wiring method of RS485 conversion units connected on the same line shall be set in the same way. (See Page 7.)
- Set the inverter number to SW5 of the RS485 built-in board option. (When the parameter f802 is used to set this number, set SW5 to zero.) Do not use the same inverter number on the same line. To connect multiple inverters, make sure to set numbers different from each other. (See Page 7.)
- Set a terminating resistor on both ends of the system. This RS485 built-in board option is equipped with terminating resistors. Terminating resistors can be connected by setting the SW2-R (receiving terminal side) and SW2-T (transmission terminal side) to S sides. (See Page 7.)
- Connect a control cable and a RS485 cable to the terminal block. (See Pages 12 and 13.) In this case, be careful not to short-circuit between the adjacent terminals with core wires stuck out.
- Connect the shield of a shielded twisted pair cable to the SHLD terminal of each RS485 built-in board option to form 1-point grounding as a transmission system. At this time, ground the transmission system at a point sufficiently away from the grounded point of power line (host computer side is recommended). (See Page 13.)
- When the switch settings and cable connections are completed, close the front cover and turn on the power of VF-S11.
- Set the parameters of VF-S11. (See Page 14.)
- When the parameters are changed, turn off the power of VF-S11 and then turn on again.
- In this unit, transmission/reception is automatically selected. Note that using this unit, only half-duplex transmission can be made.
- Observe the following precautions when sending data from host computer to VF-S11:
After return data is received from VF-S11, provide an interval equivalent to 1 data bit or more before sending the next data. Time equivalent to 1 data bit = 1 / communication speed (Example) “baud rate = 19200 bps; 1b / 19200bps = 52μs”
Wiring
Observe the following when wiring
- Separate the control/communication cables and the main circuit wiring of 20 cm or more without bundling. Wiring them close the one to each other may lead to malfunction due to noise.
- Use 0.3 to 1.5 mm2 solid/stranded wire (AWG 22 to 16) for control cables.
The interface between the programmable controller and inverter
When the operation is to be controlled using a programmable controller which is the open collector output type, if the programmable controller is turned off with the inverter is on, the difference between each control power potential will cause wrong signals to the inverter as shown in below figure. Be sure to provide an interlock so that the programmable controller cannot be turned off when the inverter is on.
Use shielded twisted cables of 0.2 to 1.5 mm2 (AWG 24 to16) for communication cables. Select wire size depending on the transmission distance referring to the table below.
- Use the same type of wires inside the system.
Recommended RS485 transmission cable
Item | Specification | ||
Transmission
cable |
Shielded twisted cable | ||
Connection method | Twisted RXA and RXB wires and twisted TXA and TXB.
Twisted RXA (or TXA) and RXB (or TXB) wires for 2-wire system. Note: Connect a terminating resistor at both ends of wires. |
||
Cable length |
Cable type | Cable length | Recommended maker |
CPEV-CU
1.2 mmj (single wire) |
1000 m or less |
SHOWA WIRE & CABLE Co. Ltd., |
|
KMPEV-SB
0.75 mm2 (twisted wire) |
700 m or less | ||
KMPEV-SB
0.5 mm2 (twisted wire) |
500 m or less | ||
GECLS-9004
AWG24 (0.2 mm2) (single wire) |
300 m or less |
- Remove the sheath of wire about 6 mm (7mm for FLA, FLB and FLC) from the end of wire.
- Use a flat-headed screwdriver with its blade 0.6 mm in thickness and 3.5 mm in width.
- Screw tightening torque for the terminal block screws should be 0.5 N·m.
RS485 communication cable connection
To connect cables to the terminal block, refer also to the items described in the preceding section.
- Do not connect the shielded wire grounding to the grounding of power line such as the inverter.
- Separate the transmission cable from the main circuit wiring of 20 cm or more.
Connection example in the case of a 4-wire system
Connection example in the case of a 2-wire system
- Since the terminal number on the host computer side differs depending on the model of the computer, read the manual of the computer carefully before connecting it.
VF-S11 communication parameters
Function | Parameter | Description |
Communication speed | f800 | For communication speed on the same line, set the same speed
for the inverter and host computer. |
Parity | f801 | For parity setting on the same line, set the same speed for the inverter and host computer. |
Inverter number |
f802 |
This is valid only when SW5 is set to zero. Do not use the same inverter number on the same line. To connect multiple inverters, make sure to set different numbers for inverters and set the inverter number in transmission format. |
- For details, please refer to the VF-S11 Instruction Manual and the Communication Function Manual (E6581222).
Specifications
Item | Specifications |
Part number | RS4003Z |
Service environment |
Indoors, altitude 1000 m or less, and the following are not allowed: direct sunshine, corrosive and/or explosive gases, steam, powder dust, dust, grinding liquid and grinding oil exposure. |
Ambient temperature | Conforms to VF-S11 |
Storage temperature | From -25°C to +65°C (-13°F to 149°F) |
Relative humidity | 20 to 93% (without condensation and steam) |
Vibration | 5.9 m/s2 (0.6G) or less (10 to 55 Hz) (Conforming to JIS C0040) |
Warranty
Any part of the RS485 built-in board option that happens to be defective will be repaired free of charge under the following conditions:
- If and when a trouble occurs on the option unit properly installed and handled within one year of delivery, and if the trouble is clearly attributable to defects inherent in our design and manufacturing, the product will be repaired free of charge.
- The warranty covers only the delivered option unit.
- Even in the term of the warranty, repair service will be charged for the following cases.
- Fault or damage resulting from misuse, unauthorized modification or repair.
- Fault or damage resulting from falling down of the product or traffic accident during transportation.
- Fault or damage originating from fire, saltwater/salty breezes, some kind of gas, earthquake, storm or flood, lightning, abnormal supply voltage, or other natural disasters.
- Fault or damage caused by improper use of this option unit as it is used for a purpose out of its original function.
- If another special warranty is contracted for this option unit, the special warranty has priority over this warranty.