SONBEST SM3720V Pipeline Temperature and Humidity Sensor

 

SONBEST SM3720V Pipeline Temperature and Humidity Sensor product image

Technical Parameters

Technical parameter Parameter value
Brand SONBEST
Temperature measuring range -30℃~80℃
Temperature measuring accuracy ±0.5℃ @25℃
Humidity measuring range 0~100%RH
Humidity accuracy ±3%RH @25℃
Interface RS485/4-20mA/DC0-5V/DC0-10V
Power DC12~24V 1A
Running temperature -40~80°C
Working humidity 5%RH~90%RH
Product Selection

Product DesignRS485,4 DesignRS485,4-20mA,DC0 DC0-5V,DC0 DC0-10VMultiple output methods, the products are divided into the following models depending on the output method.

Product model

output method

SM3720B RS485 总线
SM3720M 4-20mA
SM3720V5 DC0-5V
SM3720V10 DC0-10V
Product Size

fig 01

How to wiring?

how it use 1 how it use 2 how it use 3

Application solution

application sloution application sloution 2 application sloution 3 application sloution 4

How to use?

how it use

Communication Protocol

The product uses RS485 MODBUS RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device is shipped, the default baud rate is 9600, 8, n, 1

Read Data (Function id 0x03)

Inquiry frame (hexadecimal), sending example: Query 1# device 1 data, the host computer sends the command:01 03 00 00 00 02 C4 0B .

Device ID

Function id Start Address Data Length

CRC16

01 03 00 00 00 02 C4 0B

For the correct query frame, the device will respond with data:01 03 04 00 7A 00 00 DB EA , the response format is parsed as follows:

Device ID

Function id Data Length Data 1 Data 2

Check Code

01 03 04 00 79 00 7A DB EA

Data Description: The data in the command is hexadecimal. Take data 1 as an example. 00 79 is converted to a decimal value of 121. If the data magnification is 100, the actual value is 121/100=1.21. Others and so on.

Data Address Table

Address

Start Address Description Data type

Value range

40001 00 00 temperature Read Only 0~65535
40002 00 01 humidity Read Only 0~65535
40101 00 64 model code read/write 0~65535
40102 00 65 total points read/write 1~20
40103 00 66 Device ID read/write 1~249
40104 00 67 baud rate read/write 0~6
40105 00 68 mode read/write 1~4
40106 00 69 protocol read/write 1~10
read and modify device address
  1. Read or query device address
    If you don’t know the current device address and there is only one device on the bus, you can use the command FA 03 00 64 00 02 90 5F Query device address.

    Device ID

    Function id Start Address Data Length

    CRC16

    FA 03 00 64 00 02 90 5F

    FA is 250 for the general address. When you don’t know the address, you can use 250 to get the real device address, 00 64 is the device model register.
    For the correct query command, the device will respond, for example the response data is: 01 03 02 07 12 3A 79, the format of which is as shown in the following table:

    Device ID

    Function id Start Address Model Code

    CRC16

    01 03 02 55 3C 00 01 3A 79
  2. Change device address
    For example, if the current device address is 1, we want to change to 02, the command is:01 06 00 66 00 02 E8 14 .

    Device ID

    Function id Start Address Destination

    CRC16

    01 06 00 66 00 02 E8 14

    After the change is successful, the device will return information: 02 06 00 66 00 02 E8 27 , its format is parsed as shown in the following table:

    Device ID

    Function id Start Address Destination

    CRC16

    01 06 00 66 00 02 E8 27

    Response should be in the data, after the modification is successful, the first byte is the new device address. After the general device address is changed, it will take effect immediately. At this time, the user needs to change the query command of th e software at the same time.

 

Read and Modify Baud Rate
  1.  Read baud rate
    The device default factory baud rate is 9600. If you need to change it, you can change it according to the following table and the corresponding communication protocol . For example, read the current device’s baud rate ID, the command is:01 03 00 67 00 01 35 D5 , its format is parsed as follows.

    Device ID

    Function id Start Address Data Length

    CRC16

    01 03 00 67 00 01 35 D5

    Read the baud rate encoding of the current device. Baud rate encoding: 1 is 2400; 2 is 4800; 3 is 9600; 4 is 19200; 5 is 38400; 6 is 115200. For the correct query command, the device will respond, for example the response data is: 01 03 02 00 03 F8 45, the format of which is as shown in the following table:

    Device ID

    Function id Data Length Rate ID

    CRC16

    01 03 02 00 03 F8 45

    coded according to baud rate, 03 is 9600, ie the current device has a baud rate of 9600.

  2. Change the baud rate
    For example, changing the baud rate from 9600 to 38400, ie changing the code from 3 to 5, the command is: 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64 15 .

    Device ID

    Function id Start Address Target Baud Rate

    CRC16

    01 03 00 66 00 01 64 15

    Change the baud rate from 9600 to 38400, changing the code from 3 to 5. The new baud rate will take effect immediately, at which point the device will lose its response and the baud rate of the device should be queried accordingly. Modified.

Read Correction Value
  1. When there is an error between the data and the reference standard, we can reduce the display error by adjusting the correction value. The correction difference can be modified to be plus or minus 1000, that is, the value range is 0 1000 or 64535 65535. For example, when the display value is too small, we can correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the command 100 is hex 0x64 If you need to reduce, you can set a negative value, such as 100, corresponding t correction value starts from 00 6B. We take the first parameter as an example. The correction value is read an d modified in the same way for multiple parameter

Device ID

Function id Start Address Data Length

CRC16

01 03 00 6B 00 01 F5 D6

For the correct query command, the device will respond, for example the response data is: 01 03 02 00 64 B9 AF, the format of which is as shown in the following table:

Device ID

Function id Data Length Data value

CRC16

01 03 02 00 64 B9 AF

In the response data, the first byte 01 indicates the real address of the current device, and 00 6B is the first state quantity correction value register. If the device has multiple parameters, other parameters operate in this way. The same, the general temperature, humidity have this parameter, the light generally does not have this item.

Change correction value

For example, the current state quantity is too small, we want to add 1 to its true value, and the current value plus 100 correction operation command is:01 06 00 6B
00 64 F9 FD .

Device ID

Function id Start Address Destination

CRC16

01 06 00 6B 00 64 F9 FD
  1. temperature and current computing relationship
    For example, the range is 30~80 ℃℃, the analog output is 4~20mA current signal, temperature and current The calculation relationship is as shown in the formula: C = (A2 A1) * (X B1) / (B2 B1) + A1, where A2 is temperature range upper limit, A1 is the lower limit of the range, B2 is current output range upper limit, B1 is the lower limit, X is the currently read temperature value, and C is the calculated current value. The list of commonly used values is as follows:

    DC0-5Vvoltage(V)

    temperature Value (℃)

    Calculation Process

    0 -30 (80-(-30))*(0-0)÷(5-0)+-30
    1 -8 (80-(-30))*(1-0)÷(5-0)+-30
    2 14 (80-(-30))*(2-0)÷(5-0)+-30
    3 36 (80-(-30))*(3-0)÷(5-0)+-30
    4 58 (80-(-30))*(4-0)÷(5-0)+-30
    5 80 (80-(-30))*(5-0)÷(5-0)+-30
  2.  humidity and current computing relationship
    For example, the range is 0~100%RH, the analog output is 4~20mA current signal, humidity and current The calculation relationship is as shown in the formula: C = (A2 A1) * (X B1) / (B2 B1) + A1, where A2 is humidity range upper limit, A1 is the lower limit of the range, B2 is current output range upper limit, B1 is the lower limit, X is the currently read humidity value, and C is the calculated current value. The list of commonly used values is as follows:

    DC0-5Vvoltage(V)

    humidity Value (%RH)

    Calculation Process

    0 0.0 (100-0)*(0-0)÷(5-0)+0
    1 20.0 (100-0)*(1-0)÷(5-0)+0
    2 40.0 (100-0)*(2-0)÷(5-0)+0
    3 60.0 (100-0)*(3-0)÷(5-0)+0
    4 80.0 (100-0)*(4-0)÷(5-0)+0
    5 100.0 (100-0)*(5-0)÷(5-0)+0

    As shown in the above formula, when measuring 2.5V, current DC0 5Vvoltage is 50%RH

 

  1. Temperature and DC0 10Vvoltage computing relationship
    For example, the range is -30~80℃, the analog output is 0~10V DC0-10Vvoltage signal, temperature and DC0-10Vvoltage The calculation relationship is as shown in the formula: C = (A2 -A1) * (X-B1) / (B2-B1) + A1, where A2 is temperature range upper limit, A1 is the lower limit of the range, B2 is DC0-10Vvoltage output range upper limit, B1 is the lower limit, X is the currently read temperature value, and C is the calculated DC0-10Vvoltage value. The list of commonly used values is as follows:

    DC0-10Vvoltage(V)

    temperature Value (℃)

    Calculation Process

    0 -30 (80-(-30))*(0-0)÷(10-0)+-30
    1 -19 (80-(-30))*(1-0)÷(10-0)+-30
    2 -8 (80-(-30))*(2-0)÷(10-0)+-30
    3 3 (80-(-30))*(3-0)÷(10-0)+-30
    4 14 (80-(-30))*(4-0)÷(10-0)+-30
    5 25 (80-(-30))*(5-0)÷(10-0)+-30
    6 36 (80-(-30))*(6-0)÷(10-0)+-30
    7 47 (80-(-30))*(7-0)÷(10-0)+-30
    8 58 (80-(-30))*(8-0)÷(10-0)+-30
    9 69 (80-(-30))*(9-0)÷(10-0)+-30
    10 80 (80-(-30))*(10-0)÷(10-0)+-30
  2.  humidity and DC0 5Vvoltage computing relationship
    For example, the range is 0~100%RH, the analog output is 0~5V DC0 5Vvoltage signal, humidity and DC0 5Vvoltage The calculation relationship is as shown in the formula: C = (A2 A1) * (X B1) / (B2 B1) + A1, where A2 is humidity range upper limit, A1 is the lower limit of the range, B2 is DC0 5Vvoltage output range upper limit, B1 is the lower limit, X is the currently read humidity value, and C is the calculated DC0 5Vvoltage value. The list of commonly used values is as follows:

    DC0-10Vvoltage(V)

    humidity Value (%RH)

    Calculation Process

    0 0.0 (100-0)*(0-0)÷(10-0)+0
    1 10.0 (100-0)*(1-0)÷(10-0)+0
    2 20.0 (100-0)*(2-0)÷(10-0)+0
    3 30.0 (100-0)*(3-0)÷(10-0)+0
    4 40.0 (100-0)*(4-0)÷(10-0)+0
    5 50.0 (100-0)*(5-0)÷(10-0)+0
    6 60.0 (100-0)*(6-0)÷(10-0)+0
    7 70.0 (100-0)*(7-0)÷(10-0)+0
    8 80.0 (100-0)*(8-0)÷(10-0)+0
    9 90.0 (100-0)*(9-0)÷(10-0)+0
    10 100.0 (100-0)*(10-0)÷(10-0)+0

    it value, and C is the calculated DC0-10Vvoltage value. The list of commonly used values is as follows: As shown in the above formula, when measuring 5V, current DC0 -10Vvoltage is 50%RH。

Disclaimer

This document provides all information about the product, does not grant any license to intellectual property, does not express or imply, and prohibits any other means of granting any intellectual property rights, such as the statement of sales terms and conditions of this product, other issues. No liability is assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use of this product, including the suitability for the specific use of the product, the marketability or the infringement liability for any patent, copyright or other intellectual property rights, etc. Product specifications and product descriptions may be modified at any time without notice.

Contact Us

Company: Shanghai Sonbest Industrial Co., Ltd

Address: Building 8,No.215 North east road,Baoshan District,Shanghai,China Web: http://www.sonbest.com
Web:    http://www.sonbus.com SKYPE: soobuu
Email: sale@sonbest.com
Tel: 86-021-51083595 / 66862055 / 66862075 / 66861077

Documents / Resources

SONBEST SM3720V Pipeline Temperature and Humidity Sensor [pdf] User Manual
SM3720V, Pipeline Temperature and Humidity Sensor, SM3720V Pipeline Temperature and Humidity Sensor

References

Leave a comment

Your email address will not be published. Required fields are marked *