rotronic CL11 CO2 Temperature Humidity_LogoRMS-LOG-L-D
Short instruction manual

rotronic RMS-LOG-L-D Data Logger with Display

GENERAL DESCRIPTION

Congratulations on your new RMS data logger. The data logger has an internal data memory of 44,000 measured-value pairs and transmits these values continuously to the RMS software by Ethernet. These short instructions describe the main functions of the device.
rotronic RMS-LOG-L-D Data Logger with Display - iconPlease read these short instructions and the instruction manual at https://service.rotronic.com/manual/ carefully scan the QR code to open the instruction manual directly.

rotronic RMS-LOG-L-D Data Logger with Display - QRhttps://rotronic.live/RMS-LOG-L-D

COMMISSIONING

The device is supplied with power as soon as the data logger is supplied with 24 V (terminal block: V+ / V-) or PoE. Only then can the data be transmitted. The data logger can be mounted easily with the wall bracket. Choose a suitable position for measurement. Avoid disruptive influences such as sunlight, heating elements, etc. The device is connected to the RMS software by pairing.
Cloud integration
Integration of LAN devices into the Rotronic Public Cloud requires for the local network Port 80 to be enabled and a DHCP server must assign an IP address to the LAN device. For all other integrations, please check the online manual.

INTEGRATION OF A DATA LOGGER (PAIRING) IN 6 STEPS

  1. If you do not want to connect the LAN device to the Rotronic Cloud, the server must be configured in the device.
    a. Connect the device to the local network and start the RMS configuration software.
    b. Search for the device under Device > Search > Network Device. The software finds all RMS devices in the local network.
    c. Enter the host (server address) and the URL of the software services under Settings. d. Finish configuration by clicking “Write”. Close the software.
  2. Log into the RMS software/Cloud. Select Tools > Setup > Device > New Wireless device or LAN device.
    rotronic RMS-LOG-L-D Data Logger with Display - fig1
  3. LAN device — Enter the serial number of the device.
    rotronic RMS-LOG-L-D Data Logger with Display - fig2
  4. Wait until the device flashes orange. Briefly press the button on the device as shown in the picture of the RMS software. The LED flashes green when the connection is successful.
    rotronic RMS-LOG-L-D Data Logger with Display - fig3
  5. Configure the device.
  6. Finish configuration.

rotronic RMS-LOG-L-D Data Logger with Display - fig4

LED INDICATORS

State

LED function

Meaning

Connected Flashes green Status OK, data transmitted
Flashes orange Device not connected to the Internet
Flashes red
  1. time: low battery, replace soonest
  2. times: no probe connected
Not connected Flashes orange Device waiting for integration into the software

ACCESSORIES

  • RMS-PS: Power supply, 24 VDC, 15 W
  • E2-OXA :Extension cable, various lengths

TECHNICAL DATA

General specifications

Measurement interval 10 s to 300 s
Startup time < 10 s
Software compatibility V1.3.0, from V2.1 all functions
Application range -20…70°C, non-condensing
Storage conditions -20…30 °C, non-condensing
Maximum altitude 2000 m ASL
Power supply 24 VDC ±10 %/ Battery: RMS-BAT (2xAA, LiSocl2)
Max. current consumption 50 mA
AC adapter requirements 24 VDC ±10 %, 4 W minimum, ) 5W Limited Power Source
PoE 802.3af-2003, Class 1

Device data

Order code RMS-LOG-L-D
Ethernet cable requirement Min. Cat 5, SFTP, max. 30 m
Interface Ethernet
Protocols HTTP / ModbusTCP
Number of measuring points 2
Battery life (@60 s & 600 s interval) HCD-S / HCD-IC: 7 d
CCD-S-XXX: 2.4 d
PCD-S-XXX: 15 d
Storage capacity 44,000 data points

Conformity with standards

Soldering material Lead free / RoHS conformity
FDA/GAMP directives 21 CFR Part 11 / GAMP 5

Housing / Mechanics

Housing material PC. ABS
Dimensions 105 x 113 x 38 mm
IP protection class IP65
Fire protection class UL94-V2
Weight 240 g

CONNECTIONS

rotronic RMS-LOG-L-D Data Logger with Display - CONNECTIONS

Marking

Function

Ethernet PoE / Ethernet interface
V+ Power supply +
V- Power supply –

DIMENSIONS

rotronic RMS-LOG-L-D Data Logger with Display - DIMENSIONS

DELIVERY PACKAGE

  • Data logger, with clamps
  • Short instruction manual
  • 2 batteries
  • Certificate
  • Velcro strips

Any changes or modifications to this device not expressly approved by the manufacturer could void your authorization to use the device.

rotronic CL11 CO2 Temperature Humidity_Logowww.rotronic.com
12.1264.010

Documents / Resources

rotronic RMS-LOG-L-D Data Logger with Display [pdf] Instruction Manual
RMS-LOG-L-D, Data Logger with Display, RMS-LOG-L-D Data Logger with Display, Data Logger

References

Leave a comment

Your email address will not be published. Required fields are marked *