QMARK-LOGO

QMARK QX Series Explosion Proof Convector

QMARK-QX-Series-Explosion-Proof-Convector-PROERUVT

  • JOB NAME:
  • LOCATION:
  • ARCHITECT:
  • ENGINEER:
  • CONTRACTOR:
  • SUBMITTED BY: DATE:
 

 

TAG/ITEM

 

 

QTY.

 

 

CATALOG NUMBER

HEATER  

 

AMPS

 

 

BUILT-IN CONTROLS

KW VOLTS Ø
 

 

ACCESSORIES AND CONTROLS

TAG/ITEM QTY. CATALOG NUMBER DESCRIPTION
SUBMITTED BY: DATE
APPROVED BY: DATE

ARCHITECT’S AND ENGINEER’S SPECIFICATIONS*

Electric explosion proof convection heater(s)
shall be supplied by QMark®, a Marley Engineered Products® Brand, Bennettsville, SC, USA, and shall be of the KW rating, voltage and phase specified in the schedule. They shall be convection type heating units, certified to cCSAus and ABS, and approved for Class I, Divisions 1 and 2, Group B, C and D; Class II, Divisions 1 and 2, Groups E, F and G; Class I, Zones 1 and 2, Group IIB and H2. These convection heaters have been designed and manufactured to provide a rugged and corrosion resistant heat source for areas where volatile flammable liquids or gases and vapors are present.

SAFETY

Convection heaters shall be outfitted a linear limit, automatic reset thermal cutout standard to every unit.

HEAT EXCHANGER

Grade A Nickel-Chromium heating coils are insulated with ceramics and magnesium oxide from the copper heater tube and fitted with large aluminum fins locked in place for optimal heat transfer.

ENCLOSURE
Heat exchanger and components to be enclosed in an industrial grade, corrosion-resistant all welded cabinet fabricated with polyester powder-coated, 14 gauge steel. The front cover shall be set at a 45° angle, discouraging the use of heater as a shelf or “step stool” and preventing objects from  being set on top of the convector, which can restrict airflow and cause overheating. Inlet and discharge air louvers shall be stamped and integrated into the front cover for additional rigidity.

CONSTRUCTION OPTIONS

Gas and Dust Atmospheres: Units are listed to cover the applications for both hazardous gases and vapors, as well as requirements for dust particles.
Wet Locations: All unit sizes available with iridite coated elements and powder-coated frames for NEMA 3 wet locations.
Stainless Steel cabinet construction

ELECTRICAL
Units are available in a wide selection of wattages from 500w–9,500w, single and three phase, and from 120v–600v.

MOUNTING

Cabinet should be mounted at least 6 inches (152 mm) above the floor. Factory-furnished wall brackets make installation easy.

OPTIONAL BUILT-IN CONTROLS

The following factory installed packages and prewired  control options are available: adjustable built-in thermostat, remote thermostat, and transformer and contactor bundles.
* QMark reserves the right to change specifications without prior notice.

Class I, Divisions 1 & 2, Groups B, C & D | Class I, Zones 1 & 2 Groups IIB + H2 | Ignition Temperature Code T2A, 536° F Models & Specifications:

ITEM INFORMATION

CATALOG NO.

ELECTRICAL DATA

UNITVOLTS           PHASE           TOTAL           KW             SIZE

AMPS

OPTIONAL BUILT-ON CONTROLS

CONTROLS                THERMOSTAT ONLY* OR ONLY     THERMOSTAT WITH CONTROLS

SHIP WT.**
QX-254-F0310052B 120 1 4.2  

 

0.5

 

 

1

1024754 13 lbs
QX-254-F0310052C 208 1 2.4 1024754 13 lbs
QX-254-F0310052J 240 1 2.1 1024754 13 lbs
QX-254-F0310052N 277 1 1.8 1024754 13 lbs
QX-254-F0310102B 120 1 8.3  

 

1.0

 

 

1

1024754 13 lbs
QX-254-F0310102C 208 1 4.8 1024754 13 lbs
QX-254-F0310102J 240 1 4.2 1024754 13 lbs
QX-254-F0310102N 277 1 3.6 1024754 13 lbs
QX-254-F0320182B 120 1 15.0  

 

 

 

 

1.8

 

 

 

 

 

2

Not Required S2 13 lbs
QX-254-F0320182C 208 1 8.7 Not Required S2 27 lbs
QX-254-F0320182J 240 1 7.5 Not Required S2 27 lbs
QX-254-F0320182N 277 1 6.5 Not Required S2 27 lbs
QX-254-F0320182I 347 1 5.2 B2 B3 27 lbs
QX-254-F0320182U 480 3 2.2 B2 B3 27 lbs
QX-254-F0320182Z 600 3 1.8 B2 B3 27 lbs
QX-254-F0320252C 208 1 12.0  

 

 

 

 

2.5

 

 

 

 

 

2

Not Required S2 27 lbs
QX-254-F0320252D 208 3 6.9 B2 B3 27 lbs
QX-254-F0320252J 240 1 10.4 Not Required S2 27 lbs
QX-254-F0320252N 277 1 9.0 Not Required S2 27 lbs
QX-254-F0320252I 347 1 7.2 B2 B3 27 lbs
QX-254-F0320252U 480 3 3.0 B2 B3 27 lbs
QX-254-F0320252Z 600 3 2.4 B2 B3 27 lbs
QX-254-F0330362C 208 1 17.3  

 

 

 

 

3.6

 

 

 

 

 

3

Not Required S2 36 lbs
QX-254-F0330362D 208 3 10.0 B2 B3 36 lbs
QX-254-F0330362J 240 1 15.0 Not Required S2 36 lbs
QX-254-F0330362N 277 1 13.0 Not Required S2 36 lbs
QX-254-F0330362I 347 1 10.4 B2 B3 36 lbs
QX-254-F0330362U 480 3 4.3 B2 B3 36 lbs
QX-254-F0330362Z 600 3 3.5 B2 B3 36 lbs
QX-254-F0330442D 208 3 12.2  

 

 

 

4.4

 

 

 

 

3

B2 B3 36 lbs
QX-254-F0330442J 240 1 18.3 Not Required S2 36 lbs
QX-254-F0330442N 277 1 15.9 Not Required S2 36 lbs
QX-254-F0330442I 347 1 12.7 B2 B3 36 lbs
QX-254-F0330442U 480 3 5.3 B2 B3 36 lbs
QX-254-F0330442Z 600 3 4.3 B2 B3 36 lbs
QX-254-F0340652D 208 3 18.0  

 

 

 

6.5

 

 

 

 

4

B2 B3 60 lbs
QX-254-F0340652J 240 3 27.1 B2 B3 60 lbs
QX-254-F0340652N 277 1 23.5 B2 B3 60 lbs
QX-254-F0340652I 347 1 18.7 B2 B3 60 lbs
QX-254-F0340652U 480 3 7.8 B2 B3 60 lbs
QX-254-F0340652Z 600 3 6.3 B2 B3 60 lbs
QX-254-F0340752D 208 3 20.8  

 

 

 

7.5

 

 

 

 

4

B2 B3 60 lbs
QX-254-F0340752J 240 1 31.3 B2 B3 60 lbs
QX-254-F0340752N 277 1 27.1 B2 B3 60 lbs
QX-254-F0340752I 347 1 21.6 B2 B3 60 lbs
QX-254-F0340752U 480 3 9.0 B2 B3 60 lbs
QX-254-F0340752Z 600 3 7.2 B2 B3 60 lbs
QX-254-F0340952D 208 3 26.4  

 

 

 

9.5

 

 

 

 

4

B2 B3 60 lbs
QX-254-F0340952J 240 1 39.6 B2 B3 60 lbs
QX-254-F0340952N 277 1 34.3 B2 B3 60 lbs
QX-254-F0340952I 347 1 27.4 B2 B3 60 lbs
QX-254-F0340952U 480 3 11.4 B2 B3 60 lbs
QX-254-F0340952Z 600 3 9.1 B2 B3 60 lbs
ITEM INFORMATION

 

CATALOG NO.

ELECTRICAL DATA

UNIT

VOLTS           PHASE           TOTAL           KW             SIZE

AMPS

OPTIONAL BUILT-ON CONTROLS

CONTROLS                THERMOSTAT ONLY* OR ONLY     THERMOSTAT WITH CONTROLS

 

SHIP WT.**

QX-254-F0310053B 120 1 4.2  

 

0.5

 

 

1

1007002 13 lbs
QX-254-F0310053C 208 1 2.4 1007002 13 lbs
QX-254-F0310053J 240 1 2.1 1007002 13 lbs
QX-254-F0310053N 277 1 1.8 1007002 13 lbs
QX-254-F0310103B 120 1 8.3  

 

1.0

 

 

1

1007002 13 lbs
QX-254-F0310103C 208 1 4.8 1007002 13 lbs
QX-254-F0310103J 240 1 4.2 1007002 13 lbs
QX-254-F0310103N 277 1 3.6 1007002 13 lbs
QX-254-F0320183B 120 1 15.0  

 

 

 

 

1.8

 

 

 

 

 

2

Not Required S1 27 lbs
QX-254-F0320183C 208 1 8.7 Not Required S1 27 lbs
QX-254-F0320183J 240 1 7.5 Not Required S1 27 lbs
QX-254-F0320183N 277 1 6.5 Not Required S1 27 lbs
QX-254-F0320183I 347 1 5.2 B2 B2S1 27 lbs
QX-254-F0320183U 480 3 2.2 B2 B2S1 27 lbs
QX-254-F0320183Z 600 3 1.8 B2 B2S1 27 lbs
QX-254-F0320253C 208 1 12.0  

 

 

 

 

2.5

 

 

 

 

 

2

Not Required S1 27 lbs
QX-254-F0320253D 208 3 6.9 B2 B2S1 27 lbs
QX-254-F0320253J 240 1 10.4 Not Required S1 27 lbs
QX-254-F0320253N 277 1 9.0 Not Required S1 27 lbs
QX-254-F0320253I 347 1 7.2 B2 B2S1 27 lbs
QX-254-F0320253U 480 3 3.0 B2 B2S1 27 lbs
QX-254-F0320253Z 600 3 2.4 B2 B2S1 27 lbs
QX-254-F0330363C 208 1 17.3  

 

 

 

 

3.6

 

 

 

 

 

3

Not Required S1 36 lbs
QX-254-F0330363D 208 3 10.0 B2 B2S1 36 lbs
QX-254-F0330363J 240 1 15.0 Not Required S1 36 lbs
QX-254-F0330363N 277 1 13.0 Not Required S1 36 lbs
QX-254-F0330363I 347 1 10.4 B3 B3S1 36 lbs
QX-254-F0330363U 480 3 4.3 B2 B2S1 36 lbs
QX-254-F0330363Z 600 3 3.5 B2 B2S1 36 lbs
QX-254-F0330443D 208 3 12.2  

 

 

 

4.4

 

 

 

 

3

B2 B2S1 36 lbs
QX-254-F0330443J 240 1 18.3 Not Required S1 36 lbs
QX-254-F0330443N 277 1 15.9 Not Required S1 36 lbs
QX-254-F0330443I 347 1 12.7 B2 B3S1 36 lbs
QX-254-F0330443U 480 3 5.3 B2 B2S1 36 lbs
QX-254-F0330443Z 600 3 4.3 B2 B2S1 36 lbs
QX-254-F0340653D 208 3 18.0  

 

 

 

6.5

 

 

 

 

4

B2 B2S1 60 lbs
QX-254-F0340653J 240 1 27.1 B2 B2S1 60 lbs
QX-254-F0340653N 277 1 23.5 B2 B2S1 60 lbs
QX-254-F0340653I 347 1 18.7 B2 B2S1 60 lbs
QX-254-F0340653U 480 3 7.8 B2 B2S1 60 lbs
QX-254-F0340653Z 600 3 6.3 B2 B2S1 60 lbs
QX-254-F0340753D 208 3 20.8  

 

 

 

7.5

 

 

 

 

4

B2 B2S1 60 lbs
QX-254-F0340753J 240 1 31.3 B2 B2S1 60 lbs
QX-254-F0340753N 277 1 27.1 B2 B2S1 60 lbs
QX-254-F0340753I 347 1 21.6 B2 B2S1 60 lbs
QX-254-F0340753U 480 3 9.0 B2 B2S1 60 lbs
QX-254-F0340753Z 600 3 7.2 B2 B2S1 60 lbs
QX-254-F0340953D 208 3 26.4  

 

 

 

9.5

 

 

 

 

4

B2 B2S1 60 lbs
QX-254-F0340953J 240 1 39.6 B2 B2S1 60 lbs
QX-254-F0340953N 277 1 34.3 B2 B2S1 60 lbs
QX-254-F0340953I 347 1 27.4 B2 B2S1 60 lbs
QX-254-F0340953U 480 3 11.4 B2 B2S1 60 lbs
QX-254-F0340953Z 600 3 9.1 B2 B2S1 60 lbs
ITEM INFORMATION

 

CATALOG NO.

ELECTRICAL DATA

UNIT

VOLTS           PHASE           TOTAL           KW             SIZE

AMPS

OPTIONAL BUILT-ON CONTROLS

CONTROLS                THERMOSTAT ONLY* OR ONLY     THERMOSTAT WITH CONTROLS

 

SHIP WT.**

QX-254-F0610052B 120 1 4.2  

 

0.5

 

 

1

1024754 13 lbs
QX-254-F0610052C 208 1 2.4 1024754 13 lbs
QX-254-F0610052J 240 1 2.1 1024754 13 lbs
QX-254-F0610052N 277 1 1.8 1024754 13 lbs
QX-254-F0620142B 120 1 11.7  

 

 

1.4

 

 

 

2

Not Required S2 27 lbs
QX-254-F0620142C 208 1 6.7 Not Required S2 27 lbs
QX-254-F0620142J 240 1 5.8 Not Required S2 27 lbs
QX-254-F0620142N 277 1 5.1 Not Required S2 27 lbs
QX-254-F0620142I 347 1 4.0 B2 B3 27 lbs
QX-254-F0630232B 120 1 19.2  

 

 

 

 

 

2.3

 

 

 

 

 

 

3

Not Required S2 36 lbs
QX-254-F0630232C 208 1 11.1 Not Required S2 36 lbs
QX-254-F0630232D 208 3 6.4 B2 B3 36 lbs
QX-254-F0630232J 240 1 9.6 Not Required S2 36 lbs
QX-254-F0630232N 277 1 8.3 Not Required S2 36 lbs
QX-254-F0630232I 347 1 6.6 B2 B3 36 lbs
QX-254-F0630232U 480 3 2.8 B2 B3 36 lbs
QX-254-F0630232Z 600 3 2.2 B2 B3 36 lbs
QX-254-F0640322C 208 1 15.4  

 

 

 

 

3.2

 

 

 

 

 

4

Not Required S2 60 lbs
QX-254-F0640322D 208 3 8.9 B2 B3 60 lbs
QX-254-F0640322J 240 1 13.3 Not Required S2 60 lbs
QX-254-F0640322N 277 1 11.6 Not Required S2 60 lbs
QX-254-F0640322I 347 1 9.2 B2 B3 60 lbs
QX-254-F0640322U 480 3 3.8 B2 B3 60 lbs
QX-254-F0640322Z 600 3 3.1 B2 B3 60 lbs
QX-254-F0640502D 208 3 13.9  

 

 

 

5.0

 

 

 

 

4

B2 B3 60 lbs
QX-254-F0640502J 240 1 20.8 Not Required S2 60 lbs
QX-254-F0640502N 277 1 18.1 Not Required S2 60 lbs
QX-254-F0640502I 347 1 14.4 B2 B3 60 lbs
QX-254-F0640502U 480 3 6.0 B2 B3 60 lbs
QX-254-F0640502Z 600 3 4.8 B2 B3 60 lbs
ITEM INFORMATION

 

CATALOG NO.

ELECTRICAL DATA

UNIT

VOLTS           PHASE           TOTAL           KW             SIZE

AMPS

OPTIONAL BUILT-ON CONTROLS

CONTROLS                THERMOSTAT ONLY* OR ONLY     THERMOSTAT WITH CONTROLS

 

SHIP WT.**

QX-254-F0610053B 120 1 4.2  

 

0.5

 

 

1

1007002 13 lbs
QX-254-F0610053C 208 1 2.4 1007002 13 lbs
QX-254-F0610053J 240 1 2.1 1007002 13 lbs
QX-254-F0610053N 277 1 1.8 1007002 13 lbs
QX-254-F0620143B 120 1 11.7  

 

 

1.4

 

 

 

2

Not Required S1 27 lbs
QX-254-F0620143C 208 1 6.7 Not Required S1 27 lbs
QX-254-F0620143J 240 1 5.8 Not Required S1 27 lbs
QX-254-F0620143N 277 1 5.1 Not Required S1 27 lbs
QX-254-F0620143I 347 1 4.0 B2 B2S1 27 lbs
QX-254-F0630233B 120 1 19.2  

 

 

 

 

 

2.3

 

 

 

 

 

 

3

Not Required S1 36 lbs
QX-254-F0630233C 208 1 11.1 Not Required S1 36 lbs
QX-254-F0630233D 208 3 6.4 B2 B2S1 36 lbs
QX-254-F0630233J 240 1 9.6 Not Required S1 36 lbs
QX-254-F0630233N 277 1 8.3 Not Required S1 36 lbs
QX-254-F0630233I 347 1 6.6 B2 B2S1 36 lbs
QX-254-F0630233U 480 3 2.8 B2 B2S1 36 lbs
QX-254-F0630233Z 600 3 2.2 B2 B2S1 36 lbs
QX-254-F0640323C 208 1 15.4  

 

 

 

 

3.2

 

 

 

 

 

4

Not Required S1 60 lbs
QX-254-F0640323D 208 3 8.9 B2 B2S1 60 lbs
QX-254-F0640323J 240 1 13.3 Not Required S1 60 lbs
QX-254-F0640323N 277 1 11.6 Not Required S1 60 lbs
QX-254-F0640323I 347 1 9.2 B2 B2S1 60 lbs
QX-254-F0640323U 480 3 3.8 B2 B2S1 60 lbs
QX-254-F0640323Z 600 3 3.1 B2 B2S1 60 lbs
QX-254-F0640503D 208 3 13.9  

 

 

 

5.0

 

 

 

 

4

B2 B2S1 60 lbs
QX-254-F0640503J 240 1 20.8 Not Required S1 60 lbs
QX-254-F0640503N 277 1 18.1 Not Required S1 60 lbs
QX-254-F0640503I 347 1 14.4 B2 B2S1 60 lbs
QX-254-F0640503U 480 3 6.0 B2 B2S1 60 lbs
QX-254-F0640503Z 600 3 4.8 B2 B2S1 60 lbs

Convectors are 60/50 Hz rated *Thermostat only is load carrying or remote. **Without controls.

ITEM INFORMATION

 

CATALOG NO.

ELECTRICAL DATA

UNIT

VOLTS           PHASE           TOTAL           KW             SIZE

AMPS

OPTIONAL BUILT-ON CONTROLS

CONTROLS                THERMOSTAT ONLY* OR ONLY     THERMOSTAT WITH CONTROLS

 

SHIP WT.**

QX-254-F0810054B 120 1 4.2  

 

0.5

 

 

1

1007002 13 lbs
QX-254-F0810054C 208 1 2.4 1007002 13 lbs
QX-254-F0810054J 240 1 2.1 1007002 13 lbs
QX-254-F0810054N 277 1 1.8 1007002 13 lbs
QX-254-F0820104B 120 1 8.3  

 

 

1.0

 

 

 

2

Not Required S1 27 lbs
QX-254-F0820104C 208 1 4.8 Not Required S1 27 lbs
QX-254-F0820104J 240 1 4.2 Not Required S1 27 lbs
QX-254-F0820104N 277 1 3.6 Not Required S1 27 lbs
QX-254-F0820104I 347 1 2.9 B2 B2S1 27 lbs
QX-254-F0830174B 120 1 14.2  

 

 

 

 

 

1.7

 

 

 

 

 

 

3

Not Required S1 36 lbs
QX-254-F0830174C 208 1 8.2 Not Required S1 36 lbs
QX-254-F0830174D 208 3 4.7 B2 B2S1 36 lbs
QX-254-F0830174J 240 1 7.1 Not Required S1 36 lbs
QX-254-F0830174N 277 1 6.1 Not Required S1 36 lbs
QX-254-F0830174I 347 1 4.9 B2 B2S1 36 lbs
QX-254-F0830174U 480 3 2 B2 B2S1 36 lbs
QX-254-F0830174Z 600 3 1.6 B2 B2S1 36 lbs
QX-254-F0840324C 208 1 15.4  

 

 

 

 

3.2

 

 

 

 

 

4

Not Required S1 36 lbs
QX-254-F0840324D 208 3 8.9 B2 B2S1 60 lbs
QX-254-F0840324J 240 1 13.3 Not Required S1 60 lbs
QX-254-F0840324N 277 1 11.6 Not Required S1 60 lbs
QX-254-F0840324I 347 1 9.2 B2 B2S1 60 lbs
QX-254-F0840324U 480 3 3.8 B2 B2S1 60 lbs
QX-254-F0840324Z 600 3 3.1 B2 B2S1 60 lbs

Dimensions and Clearances:

QMARK-QX-Series-Explosion-Proof-Convector (2)

Electrical Package Options

All single-phase heaters rated over 22 amps or 277 volts and all three-phase heaters require a magnetic contactor. Some electrical combinations will also require a control transformer. To simplify field installation, these accessories are factory-mounted on the heater cabinet and factory pre-wired (not available on Size 1 convectors).

CATALOG NO. OPTION DESCRIPTION
B2 Electric Control Option* (without thermostat) Classes I and II, Groups B, C, E, D, F and G includes contactor and transformer (as required). Required for all three-phase and singlephase heaters over 22 amps or 277 volts
B2S1 Thermostat & Controls* Classes I and II, Groups C, D, E, F and G includes thermostat, contactor and transformer (as required).
B3 Thermostat & Controls (Group B)* Classes I and II, Groups B, C, D, E, F and G includes thermostat, contactor and transformer (as required). Thermostat has internal set point.
S1 Thermostat Only* Classes I and II, Groups C, D, E, F and G single-phase heaters rated up to 22 amps at 120-277 volts. Use remote room thermostat Catalog Number 1007002 for Size 1 convectors.
 

S2

 

Thermostat Only (Group B)*

Classes I and II, Groups B, C, D, E, F and G single-phase heaters rated up to 22 amps at 120-277 volts. Thermostat has internal set point. Use remote room thermostat Catalog Number 1024754 for Size 1 convectors.

Custom Options:

CATALOG NO. OPTION                                                                                       DESCRIPTION
C1 Wet Locations Type 3 rated construction. Includes Iridite coated element assembly and gasketed terminal box. Not available with options B2/S1, S1, or S2.
 

C2

 

Corrosive-Resistant Stainless Steel Construction

Type 3 rated construction with addition of stainless steel cabinet. Includes Iridite coated element assembly and gasketed terminal box. Not available with options B2/S1, S1, or S2. ONLY the cabinet is upgraded to stainless steel.

Accessory Remote Thermostats:

CATALOG NO. SWITCH TYPE TYPE RATING TEMP RANGE DESCRIPTION
1007002 Bimetal SPDT 125-277V, 22A 50°–90°F (10°–32°C) Class 1, Div. 1, Groups C & D Class II, Div. 1, Groups E, F, & G
QX-1024754 Bulb and Capillary with Internal Set Point Adjustment SPDT 120-240V, 25A

277V, 22A

40°–120°F (5°–49°C) Class 1, Div. 1, Groups B, C & D Class II, Div. 1, Groups E, F, & G
QX-1025396 SPST Corrosion-Resistant Class 1, Div. 1, Groups B, C, & D Class II, Div. 1, Groups E, F & G

Thermostat Options

QMARK-QX-Series-Explosion-Proof-Convector (3)

How to Order

QMARK-QX-Series-Explosion-Proof-Convector (4)

  • From 0.1-99.9 kW, rounded to the nearest 1/10 kW. Varies by Temperature and Class Rating.
  • For custom requests, contact Marley sales representative for assistance and additional detail
  • Not available on Size 1 Convectors.
  • Contact Marley Sales Representative for additional configuration details

No matter the industry or application, Marley Engineered Products has a robust portfolio of innovative, reliable, high-performance comfort heating and ventilation solutions for all your heating needs.
For more information or assistance on your next project, contact Technical Services at 800-642-4328

Scan the QR code to access additional specs and features

QMARK-QX-Series-Explosion-Proof-Convector (1)

Documents / Resources

QMARK QX Series Explosion Proof Convector [pdf] User Manual
QX-254-F0310052B, QX-254-F0310052C, QX-254-F0310052J, QX Series Explosion Proof Convector, QX Series, Explosion Proof Convector, Proof Convector, Convector

References