This manual introduces LV-Hub from Pylontech. LV-Hub is a communication hub for US2000/US3000 Lithium-Ion Phosphate Battery storage system. Please read this manual before you install the battery and follow the instruction carefully during the installation process.

Introduction

LV-Hub is the CAN/RS485 communication hub for multiple 48V battery groups in parallel connection.
Fit Description: US2000 / US3000 / US2000C / US3000C / UP5000 / US5000.

LV-Hub-APYLONTECH LV-HUB Communication Hub - fig

No.  Item  Parameter 
1 Operating voltage range 48 Vdc
2 Communication CAN/RS485
3 System Consumption 2W
4 Size 442*190*44mm
5 Protection degree IP20
6 Weight 3.0kg
7 Operation Life 15 years
8 Working temperature -20~60℃
9 Storage temperature -40~80℃
10 CAN (Max 25 groups) Baud rate: 500K; terminal resistance: 0/120Ω
11 RS485 (Max 5 groups) Baud rate:9600/115200

2.1 Ports: PYLONTECH LV-HUB Communication Hub - fig 1

No. Part Silk-screen Function
1 Dry signal Function reserve
2 Reset Switch
Button
RESET Press 2 seconds and then system will restart.
3 Dip switch 1 – 6 Dip 6: Up: CAN OUT terminal resistance 120D Down: SD
4 RJ45 CAN OUT CAN output port (only upper port is for using);
5 RJ45 RS232 Debug
6 RJ45 CAN IN Connect to port 0 (only for CAN communication);
7 LED STATUS Please see 2.3.
8 LED NUMBER/BIN 1-4 Shows linked in battery group quantity with binary code. Please see 2.3.
9-16 RJ45 0; 1; 2; 3; 4; 5; 6; 7. Only uses 0-5. Please see 3.2.
17 Switch ON/OFF Turns the LV-HUB ON/OFF.
18 48VDC input 48V DC Power supply: take 48VDC power from outside (from AC/DC adaptor).
PYLONTECH LV-HUB Communication Hub - fig 2

2.2 Definition of RJ45 Port Pin

No.  CAN OUT  RS485  RS232 Pin  
1
2 GND
3 TX
4 CANH
5 CANL
6 GND RX
7 RS485A
8 RS485B GND

PYLONTECH LV-HUB Communication Hub - fig 32.3 LED Indicators Instructions 

Status PYLONTECH LV-HUB Communication Hub - icon 1 Only the HUB is turned ON, it lights once.
PYLONTECH LV-HUB Communication Hub - icon  No battery connected or at least one group is off line. When battery group is reduced it will alarm (in red), but when battery group is added in it will no alarm.
1 2 3 4 Green flash; connected battery groups number
PYLONTECH LV-HUB Communication Hub - icon 1 1 group
PYLONTECH LV-HUB Communication Hub - icon 1 2 groups
PYLONTECH LV-HUB Communication Hub - icon 1 PYLONTECH LV-HUB Communication Hub - icon 1 3 groups
PYLONTECH LV-HUB Communication Hub - icon 1 4 groups
PYLONTECH LV-HUB Communication Hub - icon 1 PYLONTECH LV-HUB Communication Hub - icon 1 5 groups
PYLONTECH LV-HUB Communication Hub - icon 1 PYLONTECH LV-HUB Communication Hub - icon 1 6 groups
PYLONTECH LV-HUB Communication Hub - icon 1 PYLONTECH LV-HUB Communication Hub - icon 1 PYLONTECH LV-HUB Communication Hub - icon 1 7 groups

Operation

3.1 Protocol
CAN: CAN-Bus-protocol-PYLON-low-voltage-V1.2-20180408 or above.
RS485: RS485-protocol-pylon-low-voltage-V3.1-20180408 or above.
3.2 Cables Connection for US2000/US3000 under RS485 or CANBUS.
3.2.1 Cables Connection for RS485PYLONTECH LV-HUB Communication Hub - fig 4

  • Each battery group can configure maximum 8pcs US2000B Plus or 8pcs US3000.
  • LV-Hub-A configures maximum 5 group batteries.
  • RS485 communication needn’t additional cable and power just a simple hub is enough.PYLONTECH LV-HUB Communication Hub - fig 5
  • When each battery group’s current is >120A, this battery group must configure 2 pair external power cables like the diagram.
  • The details of ADD Switch setting also can see the menu of battery.

3.2.2 Cables Connection for CAN (single HUB) PYLONTECH LV-HUB Communication Hub - fig 6

  • Each battery group can configure maximum 8pcs US2000B Plus or 8pcs US3000.
  • LV-Hub-A configures maximum 5 group batteries.
  • When each battery group’s current is >120A, this battery group must configure 2 pair external power cables like the diagram.
  • The details of ADD Switch setting also can see the menu of battery.
  •  When using with SMA SUNNY ISLAND, the ADD on HUB(or master HUB if there are multiple HUBs) must be 000011(for B14V0105 presenting on product label) or 000101 (for B14V0106 presenting on product label).

3.3 Cables Connection for US2000C/US3000C/UP5000 under CANBUS
Note:
The cable connection for RS485 do not require a LV-HUB. The specific cable connection way please refer to the related battery operation manual.
Connect power cable first:

  1. each pair of cable hold max 100A constant current. Connect enough pairs of cable based on calculation of system current.
  2. Suitable protection breaker between battery system and inverter is required.
  3. connect power cable of LV-HUBPYLONTECH LV-HUB Communication Hub - fig 7
  4. Make sure all dipswitch is X0XX, then turn ON batteries.
  5. After all batteries running and buzzer of master battery in group1 rings 3 times. Means all groups are online.
  6. Change the dip switch of master battery in group1 to X1XX. Then connect communication cable between LV-HUB and master battery in group 1.
  7. Then turn ON LV-HUB.

*Below communication cable shall be 8 pin direct-pin cable:
a. Between battery modules
b. Between LV-HUB Port 0 to LV-HUB CAN IN
*Below communication cable shall has first 3 pin NULL or use WI0SCAN30RJ1 cable inside external cable kits:
a. Between Group 1 Master Battery A/CAN to LV-HUB Port 1. PYLONTECH LV-HUB Communication Hub - fig 83.4 Cables Connection for Multiple HUBs under CANBUS. PYLONTECH LV-HUB Communication Hub - fig 9

In above picture, all communication cable connect in between shall be 8 pin direct-pin cable.
Annex 1: Cables Connection for US2000/US3000 under RS485 PYLONTECH LV-HUB Communication Hub - fig 10Annex 2: Cables Connection for US2000/US3000 under CAN PYLONTECH LV-HUB Communication Hub - fig 11Annex 3: Cables Connection for CAN (multi HUB) PYLONTECH LV-HUB Communication Hub - fig 12Annex 4: Cables Connection for US2000C/US3000C/UP5000 under CANBUS
PYLONTECH LV-HUB Communication Hub - fig 13

PYLONTECH - logo

Pylon Technologies Co., Ltd.
No. 73, Lane 887, ZuChongzhi Road, Zhangjiang Hi-Tech Park
Pudong, Shanghai 201203, China
T +86-21-51317699 | F +86-21-51317698
E service@pylontech.com.cn
W www.pylontech.com.cn
Pylon Technologies Co., Ltd.
No. 73, Lane 887, ZuChongzhi Road, Zhangjiang Hi-Tech Park
Pudong, Shanghai 201203, China Zip Code: 201203
Tel: 021-51317699
Fax: 021-51317698
Email: service@pylontech.com.cn
Website: http://www.pylontech.com.cn

Documents / Resources

PYLONTECH LV-HUB Communication Hub [pdf] User Manual
LV-HUB Communication Hub, Communication Hub, LV-HUB Hub, Hub, LV-HUB
PYLONTECH LV-Hub Communication Hub [pdf] User Manual
LV-Hub-A, LV-Hub Communication Hub, LV-Hub, Communication Hub, Hub

References

Leave a comment

Your email address will not be published. Required fields are marked *