NLII-RH+T-IQRF | Combined RH/temperature sensor with IQRF

PROTRONIX NLII-RH+T-IQRF Combined RH Temperature Sensor with IQRF

Room sensor NLII-RH is used to continuously monitor the air quality inside buildings and then control ventilation (HVAC) systems according to current levels of air pollution. The sensor measures relative humidity (RH) and temperature (T). It is suitable for living rooms, bathrooms, warehouses, ateliers, etc.
PROTRONIX NLII-CO2+RH+T-5-RS485 Room Sensor with RS485 - symbol 1 measures RH and temperature
PROTRONIX NLII-CO2+RH+T-5-RS485 Room Sensor with RS485 - symbol 1 2x analog voltage/current output
PROTRONIX NLII-CO2+RH+T-5-RS485 Room Sensor with RS485 - symbol 1 IQRF wireless communication
PROTRONIX NLII-CO2+RH+T-5-RS485 Room Sensor with RS485 - symbol 1 maintenance during operation is not required
PROTRONIX NLII-CO2+RH+T-5-RS485 Room Sensor with RS485 - symbol 1 long life and stability

Sensor type / order code RH output T output SIM slot IQRF module
NLII-RH+T-IQRF 0-10 V/0-20 mA/4-20 mA1) 0-10 V/0-20 mA/4-20 mA1) *
NLII-RH+T-IQRF+ 0-10 V/0-20 mA/4-20 mA1) 0-10 V/0-20 mA/4-20 mA1) * *

1) It is possible to select the desired type of analog output by a jumper on the electronics board.

Description

Measurement of the relative humidity is based on the principle of capacitive polymer sensor.
The sensor has built-in two separate analog outputs -one for the actual temperature and the other for the actual relative humidity.
So the sensor efficiently manages ventilation and heat recovery units, based on current room air quality.
The current air quality can easily be determined by looking at the three LED indicators. The eco level means good indoor air quality necessary to achieve a sense of well-being and at the same time optimal energy costs for heating, ventilation, or air conditioning.
For detailed information about IQRF, use the document NLII-IQRF-Communication. For information on the communication protocol, use the document NLII-Modbus-Communication.
Explanation of abbreviations and technical terms can be found on our website in the Glossary section.

Technical data

Parameter Value Unit
Supply voltage range 12 – 35
12 – 24
V DC
V AC
Average consumption 0,2 W
RH measuring range 0 – 100 % RH
RH accuracy 20 – 80 % ± 3 % RH
RH accuracy 0 – 100 % ± 6 % RH
T measuring range 0 – 50 °C
T accuracy ± 0,4 °C
Working temperature 0 to +50 °C
Working humidity non-condensing 0 – 90 % RH
Storage temperature -20 to +60 °C
Expected lifetime min. 10 years
Ingress protection IP20
Dimensions 90x80x31 mm

Analog output values versus actual RH

PROTRONIX NLII-RH+T-IQRF Combined RH Temperature Sensor with IQRF - Analog output values versus actual RH

Typical RH measurement accuracy at 25 °C

PROTRONIX NLII-RH+T-IQRF Combined RH Temperature Sensor with IQRF - Typical RH measurement accuracy at 25 °C

Analog output values versus actual T

PROTRONIX NLII-RH+T-IQRF Combined RH Temperature Sensor with IQRF - Analog output values versus actual T

Typical T measurement accuracy

PROTRONIX NLII-RH+T-IQRF Combined RH Temperature Sensor with IQRF - Typical T measurement accuracy

LED indication description
White LED lights:

Less than 40 % RH or less than 18 °C. (according to the quantity selected for indication)
– low concentrations of RH. Too dry air feels cooler as compared to equally hot but more humid air – the risk of drying of the mucous membranes – respiratory problems
– low temperature and its higher fluctuation is not economically profitable

Green LED lights:
PROTRONIX NLII-CO2+RH+T-5-RS485 Room Sensor with RS485 - Green LED lights More than or equal to 40 % RH or 18 °C, less than or equal to 60 % RH or 22 °C. (according to the quantity selected for indication)
– optimal relative humidity for humans
– the optimal balance of air quality and energy efficiency of ventilation and air conditioning

Yellow LED lights:
PROTRONIX NLII-CO2+RH+T-5-RS485 Room Sensor with RS485 - Yellow LED lights More than 60 % RH or more than 22 °C. (according to the quantity selected for indication)
– too high humidity, the risk of mold growth, and associated health complications
– higher temperature T – the high temperature can cause fatigue, restlessness, headache, and feel hot

Sensor start after power on
All three LEDs flash simultaneously until the first readings are available, but no longer than 10 seconds.

Sensor failure indication
All three LEDs are shining permanently.

CAUTION:
Warm-up: operational after 1 minute since power on.
The declared accuracy is reached after 4 days of continuous power supply.
It is necessary to avoid the severe mechanical shock of the sensor.

Electronic board controls and terminals

PROTRONIX NLII-RH+T-IQRF Combined RH Temperature Sensor with IQRF - Electronic board controls and terminals

Terminals
1. ~ + supply AC or DC (+) plus pole
2. ~ GND supply AC or DC (-) minus pole, GND
3. OUT1 T sensor analog output, 0-10 V or 0-20 mA or 4-20 mA
4. GND T sensor output GND
5. OUT2 RH sensor analog output, 0-10 V or 0-20 mA or 4-20 mA
6. GND RH sensor output GND
Jumpers
JP1 – Current output offset RH
JP2 – Current output offset T
JP3 – Voltage/current output T
JP4 – Voltage/current output RH
JP6 – LED indication settings

Jumpers on the electronics board

Mark Description Settings

Meaning

JP1 Current output offset RH
– shift quiescent current from 0 mA to 4 mA
 PROTRONIX NLII-RH+T-IQRF Combined RH Temperature Sensor with IQRF - Settings 1 current output RH 0-20 mA
PROTRONIX NLII-RH+T-IQRF Combined RH Temperature Sensor with IQRF - Settings 2
current output RH 4-20 mA
JP2 Current output offset T
– shift quiescent current from 0 mA to 4 mA
PROTRONIX NLII-RH+T-IQRF Combined RH Temperature Sensor with IQRF - Settings 1 current output T 0-20 mA
PROTRONIX NLII-RH+T-IQRF Combined RH Temperature Sensor with IQRF - Settings 2 current output T 4-20 mA
JP3 Voltage/current output T
– select the type of analog output
– if voltage output T is selected, JP2 must not be shorted
PROTRONIX NLII-RH+T-IQRF Combined RH Temperature Sensor with IQRF - voltage output T voltage output T
PROTRONIX NLII-RH+T-IQRF Combined RH Temperature Sensor with IQRF - current output T current output T
JP4 Voltage/current output RH
– select the type of analog output
– if voltage output RH is selected, JP1 must not be shorted
PROTRONIX NLII-RH+T-IQRF Combined RH Temperature Sensor with IQRF - voltage output T voltage output RH
PROTRONIX NLII-RH+T-IQRF Combined RH Temperature Sensor with IQRF - current output T current output RH
JP6 – 1
JP6 – 3
LED indication
LED signalization by VOC or RH
– LED indication according to ambient light – when ambient light is dimmed (at night), LED indicators to turn off automatically.
– factory setting is an indication by VOC
PROTRONIX NLII-RH+T-IQRF Combined RH Temperature Sensor with IQRF - LED indication by VOC LED indication by VOC
LED indication according to ambient light
PROTRONIX NLII-RH+T-IQRF Combined RH Temperature Sensor with IQRF - LED indication by RH   LED indication by RH
permanent LED indication enabled
JP6 – 2
JP6 – 4
JP6 – 5
These positions are not intended for user settings. PROTRONIX NLII-RH+T-IQRF Combined RH Temperature Sensor with IQRF - Settings 3

Factory settings

LED indication: by RH, indication turns off when ambient light dims
T analog output: voltage output
RH analog output: voltage output

Example of RH sensor connection for direct EC motor control using 0-10 V signal

PROTRONIX NLII-RH+T-IQRF Combined RH Temperature Sensor with IQRF - signal

If you connect other devices to the same AC power source as the NL sensor, it is necessary to meet the GND wiring of all analog inputs and outputs, as well as power wires.

PROTRONIX NLII-RH+T-IQRF Combined RH Temperature Sensor with IQRF - power wires

Sensor assembly

PROTRONIX NLII-RH+T-IQRF Combined RH Temperature Sensor with IQRF - Sensor assembly

Box color
Front: White – RAL9016
Base: gray – RAL7035

Way to use
The product is intended for indoor use only. You can read the recommendations for sensor placement on our web pages.

End of product life
Discard the product according to the electronic waste law and the EU directives.

Dimensions

PROTRONIX NLII-RH+T-IQRF Combined RH Temperature Sensor with IQRF - DimensionsThe producer reserves the right of technical changes in order to produce improvements its properties and functions without previous notice.

Protronix s.r.o., Pardubická 177, Chrudim 537 01, Czech Republic
www.protronix.cz/en/
www.careforair.eu/en/
PROTRONIX NLII-CO2+RH+T-5-RS485 Room Sensor with RS485 - symbol

Documents / Resources

PROTRONIX NLII-RH+T-IQRF Combined RH/Temperature Sensor with IQRF [pdf] User Manual
NLII-RH T-IQRF, Combined RH Sensor with IQRF, Combined Temperature Sensor with IQRF

References

Leave a comment

Your email address will not be published. Required fields are marked *