POTTER RCDS SERIES Releasing Circuit Disable Switch

POTTER-RCDS-SERIES-Releasing-Circuit-Disable-Switch-PRODUCT

Features

  • Meets requirements of NFPA 72 and 2001
  • Colored LEDs indicate system status
  • Stainless steel plate mounts to single gang box
  • RCDS-1: key removable in both positions
  • RCDS-2001: key only removable in enabled position to comply with NFPA 2001
  • Compatible with any 24VDC system

Description

The device consists of a stainless steel faceplate, green LED, amber LED, and a switch assembly. It is designed to mount on a standard single gang electrical enclosure.

Application

The RCDS-1 complies with the requirements of NFPA 72 (National Fire Alarm and Signaling Code):

The RCDS-2001 complies with the requirements of NFPA 2001 (Standard on Clean Agent Fire Extinguishing Systems):

  • Specifying a physical switch to disconnect the release circuit in place of a software-controlled disconnect.
  • Creating a supervisory condition on the associated release panel.

Technical Specifications

Dimensions 2 3/4” W x 4-1/2” H x 2” D (Approximate) Mounts on single gang or handy box
Contact Rating 1 AMP @ 40 VDC
Power Requirements 24 VDC, 10mA
Environmental

Specifications

Indoor use only

Temperature range -22°F to140°F (-30°C to 60°C)

InstallationPOTTER-RCDS-SERIES-Releasing-Circuit-Disable-Switch-FIG-1

  1. Connect the red and black leads to the 24 VDC auxiliary power terminals on the release panel. Be certain to observe polarity.
  2. Connect the yellow wires to the supervisory zone on the panel.

Operation

  • The green LED indicates the RCDS is in Normal condition and the release circuit is enabled.
  • The amber LED indicates that the release circuit is disabled.

Ordering Information

Model Description Stock No.
RCDS-1 Releasing Circuit Disable Switch 3001002
RCDS-2001 Releasing Circuit Disable Switch (Clean Agent) 3001005

NOTICE: The connection for the supervisory circuit has 4 wires: 2 yellow and 2 gray. The 2 yellow wires are for connection to the supervisory circuit. The 2 gray wires are for connection to additional supervisory devices or the EOLR for the supervisory zone.

Potter Electric Signal Company, LLC

firealarmresources.com

Documents / Resources

POTTER RCDS SERIES Releasing Circuit Disable Switch [pdf] Owner's Manual
RCDS SERIES Releasing Circuit Disable Switch, RCDS SERIES, Releasing Circuit Disable Switch, Circuit Disable Switch, Disable Switch

References

Leave a comment

Your email address will not be published. Required fields are marked *