Pepperl Fuchs - logoHART Transmitter Power Supply, Input Isolator
LB3002A2Pepperl Fuchs LB3002A2 HART Transmitter Power Supply Input Isolator - cover

LB3002A2 HART Transmitter Power Supply Input Isolator

  • 1-channel
  • Power supply for 2- or 3-wire transmitters with 4 mA … 20 mA
  • Installation in Zone 2 or safe area
  • Supply circuit 15 V (20 mA)
  • Input from active signals of 4-wire transmitters
  • HART communication via field bus or service bus
  • HART communication also for separately powered devices
  • Simulation mode for service operations (forcing)
  • Line fault detection (LFD) and Live Zero monitoring
  • Permanently self-monitoring
  • Module can be exchanged under voltage

Function

The transmitter power supply feeds 2- and 3-wire transmitters.
Active signals from separately powered field devices and 4-wire transmitters can be connected.
Open circuit, short circuit, and Live Zero status are detected.
The input is galvanically isolated from the bus and the power supply.

Connection

Pepperl Fuchs LB3002A2 HART Transmitter Power Supply Input Isolator - Connection

Zone 2

Technical Data

Slots
Occupied slots 1
Supply
Connection backplane bus
Rated voltage Ur 12 V DC , only in connection with the power supplies LB9***
Power dissipation 0.75 W
Power consumption 1.1 W
Internal bus
Connection backplane bus
Interface manufacturer-specific bus to standard com unit
Analog input
Number of channels 1
Suitable field devices
Field device pressure converter
Field device [2] flow converter
Field device [3] level converter
Field device [4] Temperature Converter
Field device interface
Connection 2-wire transmitter
Connection [2] 3-wire transmitter
Connection [3] 4-wire transmitter
Connection 2-wire transmitter (HART): supply circuit: 2/3+, 4/53-wire transmitter (HART):
supply circuit: 2/3+, 6measuring circuit: 4/5+, 64-wire transmitter (separately powered): measuring circuit: 4/5+, 6HART measuring circuit: 1+, 6-
Transmitter supply voltage min. 15 V at 20 mA ;  21.5 V at 4 mA
Input resistance 15 Ω (terminals 5, 6) <P></P> 236 Ω (terminals 1, 6) HART
Line fault detection can be switched on/off for each channel via configuration tool , configurable via
configuration tool
Short-circuit factory setting: > 22 mA configurable between 0 … 26 mA
Open-circuit factory setting: < 1 mA configurable between 0 … 26 mA
HART communication yes
HART secondary variable yes
Transfer characteristics
Deviation
After calibration 0.1 % of the signal range at 20 °C (68 °F)
Influence of ambient temperature 0.1 %/10 K of the signal range
Resolution 12 Bit (0 … 26 mA)
Refresh time 100 ms
Indicators/settings
LED indication Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1) red: line fault (lead breakage or short circuit) Status LED (2) yellow: Live Zero monitoring
Coding optional mechanical coding via front socket
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013
Conformity
Electromagnetic compatibility NE 21:2007
Degree of protection IEC 60529:2000
Environmental test EN 60068-2-14:2009
Shock resistance EN 60068-2-27:2009
Vibration resistance EN 60068-2-6:2008
Damaging gas EN 60068-2-42:2003
Relative humidity EN 60068-2-78:2001
Ambient conditions
Ambient temperature -40 … 60 °C (-40 … 140 °F) , 70 °C (non-Ex)
Storage temperature -40 … 85 °C (-40 … 185 °F)
Relative humidity 95 % non-condensing
Shock resistance shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistance frequency range 10 … 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 … 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protection IP20 when mounted on backplane
Connection removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 … 1.5 mm 2 ) or screw terminals (0.08 … 1.5 mm 2 )
Mass approx. 90 g
Dimensions 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch)
Data for application in connection with hazardous areas
Certificate BVS 13 ATEX E 038 X
Marking 1 II 3 G Ex nA [ic] IIC T4 Gc
Galvanic isolation
Input/power supply, internal bus safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020
EN 60079-11:2012
EN 60079-15:2010
International approvals
ATEX approval BVS 13 ATEX E 038X
IECEx approval BVS 13.0043X
Approved for Ex nA [ic] IIC T4 Gc
General information
System information The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or
outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in
an appropriate enclosure.
Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Assembly

Front view

Pepperl Fuchs LB3002A2 HART Transmitter Power Supply Input Isolator - Assembly

Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.

Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com

Release date: 2021-12-01 Date of issue:
2021-12-01 Filename: 254699_eng.pdf