Solid State Module SSR
Three-phase 40 and 80 A Model with 1 and 3 SSR

USER GUIDE V1.0x D
Product marketed by NOVUS Automation.

Presentation
The SSR Static Switch is an electronic device used to drive resistive and inductive loads with numerous advantages over conventional electromechanical (contactor) relays. A control signal determines the activation of the load connected to the power terminals of the device.

Identification
Attached to the device is the identification tag. Check if the features described on this tag are in accordance with what was requested.

Operation

After receiving a command signal at its input terminals, the static switch conducts (turns on) and feeds the load. The conduction happens effectively at the next zero crossing of the mains voltage. The same happens in the shutdown. The command signal is removed, but the key only effectively blocks (turns off) the next zero crossing of the electric current on the load.
This implies delays never exceeding 8.3 milliseconds between the tripping time of the ON/OFF command and the effective charging/discharging of the load. Turning the load on and off at zero crossing always brings important advantages to the installation. Practically no electrical interference is generated at the installation and the switch is not subjected to severe switching conditions. It is impossible to switch DC voltage, only alternating voltage (AC).

Installation
Follow the installation guidelines to ensure proper functioning of the SSR module.

Electrical Connections
When installing the SSR module, Command Signal, Fan and Load connections are required.

Dissipation of Heat
With the current of load circulating, there is generation of intense heat on the switch. This heat should be quickly transferred (dissipated) into the environment to prevent the switch overheating. The nominal load current (IL) values defined for each switch model consider the use of a suitably calculated heatsink. The SSR static switch already incorporates the heatsink in the dimension suitable for the rated current specified and the fan required. As a safety measure for installations, the nominal load current shall not exceed 80% of the rated current of the switch.

Overheating Protection
Ensure proper protection mechanisms are in place to prevent overheating.

Dimension
Dimensions of SSR static switch for models with 1 SSR and 3 SSR are provided for installation reference.

Problems Solutions

Static Switch Does Not Turn On
Identify the cause of the defect and arrange the correction, always with the key turned off.

Static Switch Turns Off Improperly
Identify the cause of the defect and arrange the correction, always with the key turned off.

Technical Specifications

Operation Conditions Unit Static Switch 4840 Static Switch 4880
Load Current (IL) A rms 40 80
Load Voltage V rms 40 to 480
Voltage Drop (Vssr) V rms < 1.5
Leakage Current mA rms < 1.0
Frequency Hz 47 to 63
dv/dt V/μs 300
Control Voltage V 4 to 32
Control Current mA 15 to 20
Switch Time ms < 10
Trigger Zero cross
Isolation V 2000
Ambient Temperature* °C -20 to 40

Warranty

Warranty conditions are available on our website www.novusautomation.com/warranty.

FAQ

  1. What is the SSR Static Switch used for?
    The SSR Static Switch is used to drive resistive and inductive loads with advantages over conventional electromechanical relays.
  2. How does the SSR Static Switch operate?
    It operates by receiving a command signal and conducting at the next zero crossing of the mains voltage.
  3. What should I do if the static switch does not turn on?
    Identify the cause of the defect and arrange the correction with the key turned off.
  4. Where can I find the warranty conditions?
    Warranty conditions are available on the NOVUS Automation website.

Solid State Module SSR Three-phase 40 and 80 A Model with 1 and 3 SSR
USER GUIDE V1.0x D

PRESENTATION

The SSR Static Switch is an electronic device used to drive resistive and inductive loads with numerous advantages over conventional electromechanical (contactor) relays. A control signal determines the activation of the load connected to the power terminals of the device.

Differentials of this product:

  • No electrical noise, sparking or mechanical wear.
  • Status indicator light (LED) on or off.
  • Internal protection circuit (Snubber) for the output.
  • Zero Crossing: Turns on at 0 Volt and turns off at 0 Ampère.
  • Optical isolation between command and power.

IDENTIFICATION

Attached to the device is the identification tag. Check if the features described on this tag are in accordance with what was requested.

OPERATION

After receiving a command signal at its input terminals, the static switch conducts (turns on) and feeds the load. The conduction happens effectively at the next zero crossing of the mains voltage. The same happens in the shutdown. The command signal is removed, but the key only effectively blocks (turns off) the next zero crossing of the electric current on the load.

novus-40A-Solid-State-Module-SSR-Three-Phase- (2)This implies delays never exceeding 8.3 milliseconds between the tripping time of the ON/OFF command and the effective charging/discharging of the load.
Turning the load on and off at zero crossing always brings important advantages to the installation. Practically no electrical interference is generated at the installation and the switch is not subjected to severe switching conditions.
It is impossible to switch DC voltage, only alternating voltage (AC).

INSTALLATION

To install the device, the following recommendations must be observed:

  • Fix it upright, with the fan blowing up.
  • There should be a free area below and above the device, with 15 cm from other devices or wall, to allow good air circulation.
  • Protection and disconnection devices must be provided.
  • As a safety measure for installations, the maximum load current must not exceed 80% of the rated current of the SSR module.
  • At these nominal current values, well-secured terminals, suitable conductors, and environments with adequate ventilation help in the installation efficiency.
  • The recommended cables are 10, 16, 25 and 35 mm² for the 40, 60, 80 and 100 A chains, respectively.
  • To the connections, use compatible compression terminals.
  • Power cords are connected directly to the SSRs, and, to avoid damage, do not over-strain the device.
  • Proper grounding is essential to avoid electrical shock and interference.

Under rated current, the ambient temperature must not exceed 40 °C.

ELECTRICAL CONNECTIONS

When installing the SSR module, Command Signal, Fan and Load connections are required.

  • The control signal must be connected to terminals 1 and 2 of the side connector. A thermal protection relay is already inserted in this circuit. It interrupts the control circuit when the temperature of the heatsink exceeds 80 °C.
  • In the connection with the load, the power buses (or cables) are connected directly to the key buses of the switch. You must use an ultrafast fuse to protect the installation.
  • The fan is available on terminals 3, 4, 5, and 6 of the side connector. The installer must observe the fan’s supply voltage and connect it in accordance with the respective figures.

novus-40A-Solid-State-Module-SSR-Three-Phase- (3) novus-40A-Solid-State-Module-SSR-Three-Phase- (4) novus-40A-Solid-State-Module-SSR-Three-Phase- (5)

DISSIPATION OF HEAT

With the current of load circulating, there is generation of intense heat on the switch. This heat should be quickly transferred (dissipated) into the  environment to prevent the switch overheating. The nominal load current (IL) values defined for each switch model consider the use of a suitably calculated heatsink.
The SSR static switch already incorporates the heatsink in the dimension suitable for the rated current specified and the fan required.
As a safety measure for installations, the nominal load current shall not exceed 80% of the rated current of the switch.

novus-40A-Solid-State-Module-SSR-Three-Phase- (6)

OVERHEATING PROTECTION

The SSR static switch has a NC (normally closed) thermal relay that is in series with the control terminals. This thermal relay interrupts the command signal by turning off the switch when the heatsink temperature exceeds 80 °C. This prevents damage to the electronic relays of the switch.

DIMENSION

novus-40A-Solid-State-Module-SSR-Three-Phase- (7)
novus-40A-Solid-State-Module-SSR-Three-Phase- (1)

* The 3-phase static switch with 80 A uses the NDP3-180MM heatsink.

PROBLEMS SOLUTIONS

  1. STATIC SWITCH DOES NOT TURN ON
    The following possibilities must be observed:
    • Inverted control signal.
    • Control signal without sufficient voltage (minimum).
    • Minimum load current not reached.
    • Minimum load voltage not reached.
    • Overheated device.
    • Protection relay is defective, causing overheating.
  2. STATIC SWITCH TURNS OFF IMPROPERLY
    The following possibilities must be observed:
    • Overheating caused by overload current.
    • Overheating caused by a defective fan.
    • Overheating caused by excessively hot environment.
    • Overheating caused by poorly made load connections or badly tightened screws.
    • The user must identify the cause of the defect and arrange the correction, always with the key turned off

TECHNICAL SPECIFICATIONS

 OPERATION CONDITIONS  UNIT MODEL
STATIC SWITCH 4840 STATIC SWITCH 4880
Load Current (IL) A rms 40 80
Load Voltage V rms 40 to 480
Voltage Drop (Vssr) V rms < 1.5
Leakage Current mA rms < 1.0
Frequency Hz 47 to 63
dv/dt V/µs 300
Control Voltage Vcc 4 to 32
Control Current mAcc 15 to 20 (*)
Switch Time ms < 10
Trigger Zero cross
Isolation V rms 2000
Ambient Temperature* °C -20 to 40
Protection Actuation Temperature °C 80

(*) For the Static Switch model with individual SSRs, the required control current is > 30 mA.
Table 1 – Technical specifications

WARRANTY

Warranty conditions are available on our website www.novusautomation.com/warranty