neptronic CMMB102 Dual Mini I-O Communication Module

neptronic-CMMB102-Dual-Mini-I-O-Communication-Module-PRO

Description

The CMMB extends your BACnet or Modbus network when your application requires additional inputs and outputs on a physical controller. Combining the 8 inputs and outputs of the CMMB with your Building Automation System provides simple expansion of a new or existing controller and reduces unnecessary costs of additional components.

Features

Power & Communication

  • 24Vac or 24Vdc supply
  • BACnet® MS/TP or Modbus communication port (selectable)

Inputs & Outputs

  • 4 universal inputs
  • 2 universal outputs (supervised)
  • 2 binary outputs (supervised)

Installation

  • 4 override switches to manually control each output
  • LED status indication of each input and output
  • DIN rail mounting
  • Removable, non-strip, raising clamp terminals
  • Removable see-through panel for easy access to DIP switches

Network Communication

  • BACnet® MS/TP or Modbus communication port (selectable via DIP switch)
  • Select MAC address via DIP switch or via network

BACnet®

  • MS/TP @ 9600, 19200, 38400 or 76800 bps
  • Automatic baud rate detection
  • Automatic device instance configuration
  • Copy & broadcast configuration to other CMMB modules

Modbus

  • • Modbus @ 9600, 19200, 38400 or 57600 bps
    • RTU Slave, 8 bits (configurable parity and stop bits)
    • Connects to any Modbus master

Technical Specifications

Specifications CMMB102
Input Voltage 24 Vac or 24 Vdc
Consumption 3VA (175mA @ 24 Vac)
Universal Inputs (12-bit) 4 [0-10Vdc, Thermistor, on/off (dry contact), 4-20mA] / 12-bit resolution
Universal Outputs 2 [0-10Vdc, pulsed signal (20mA drive), on/off] / 12-bit resolution OptoFET (250mA max)
Binary Relay Outputs 2 [normally open/closed, independent common per relay, 5A resistive]
BACnet BACnet® MS/TP @ 9600, 19200, 38400 or 76800 bps (BAS-C)
 Modbus Modbus RTU slave @ 9600, 19200, 38400 or 57600. Selectable parity and stop bit configuration:

· No parity, 2 stop bit

·Even parity, 1 stop bit

· Odd parity, 1 stop bit

Communication Connections 24 AWG twisted-shield cable (Belden 9841 or equivalent)
Electrical Connections 0.8 mm2 [18 AWG] minimum
Operational Temperature 0ºC to 50ºC [32ºF to 122ºF]
Storage Temperature -30ºC to 50ºC [-22ºF to 122ºF]
Relative Humidity 5 a 95% non condensed
Weight 0.2 kg [0.4 lb]
Dimensions

 A = 3.18” / 81 mm

B = 4.93” / 125 mm

C = 2.27” / 58 mm

 

neptronic-CMMB102-Dual-Mini-I-O-Communication-Module-1

 

 

Connections and Configurations

Please note that all jumper settings must also be set to the same value through BACnet. Some additional configurations are only available through BACnet (see Network Conditions on page 4).

neptronic-CMMB102-Dual-Mini-I-O-Communication-Module-2

MAC Address DIP Switch (DS1)

MAC address for BACnet and Modbus communication, are selectable by DIP switch DS1 using binary logic.

BACnet

  • Highest MAC address is 254.
  • Default is all switches OFF = MAC address 0
  • If you do not change device instance in program mode, it will be automatically modified according to the MAC address.
MAC Address DS.1 = 1 DS.2 = 2 DS.3 = 4 DS.4 = 8 DS.5 = 16 DS.6 = 32 DS.7 = 64 DS.8 = 128 Default Device Instance
0 OFF OFF OFF OFF OFF OFF OFF OFF 153000
1 ON OFF OFF OFF OFF OFF OFF OFF 153001
2 OFF ON OFF OFF OFF OFF OFF OFF 153002
3 ON ON OFF OFF OFF OFF OFF OFF 153003
4 OFF OFF ON OFF OFF OFF OFF OFF 153004
126 OFF ON ON ON ON ON ON OFF 153126
254 OFF ON ON ON ON ON ON ON 153254

Modbus

  • Highest MAC address is 247.
  • Default is all switches OFF = MAC address 1
  • MAC address is binary value +1
  • There is no device instance for Modbus.
MAC Address DS.1 = 1 DS.2 = 2 DS.3 = 4 DS.4 = 8 DS.5 = 16 DS.6 = 32 DS.7 = 64 DS.8 = 128
0+1 = 1 OFF OFF OFF OFF OFF OFF OFF OFF
1+1 = 2 ON OFF OFF OFF OFF OFF OFF OFF
2+1 = 3 OFF ON OFF OFF OFF OFF OFF OFF
3+1 = 4 ON ON OFF OFF OFF OFF OFF OFF
4+1 = 5 OFF OFF ON OFF OFF OFF OFF OFF
126+1 = 127 OFF ON ON ON ON ON ON OFF
246+1 = 247 OFF ON ON OFF ON ON ON ON

LEDs

Power

  • On = Input voltage normal
  • Off = No power

Status

  • Flashing = Normal operation (watchdog)

RX/TX (BACnet)

  • Flashing = Receiving (RX) and/or transmitting (TX) data.

RX/TX (Modbus)

  • Flashing = Receiving (RX) and/or transmitting (TX) data.

Input Status

  • On = Input on
  • Off = Input off
  • Flashing = Input not connected (thermistor setting only)
  • Analog = When Universal Inputs are set to analog values (Vdc, mA, or Thermistor); the LED intensity corresponds to the input value. For example: At 10Vdc, the LED will be fully on. At 5Vdc, the LED will be at 50% intensity. At 0 Vdc, the LED will be off.

Output Status

  • On = Activated
  • Off = Deactivated
  • Flashing = Output pulsed
  • Analog = When Universal and Analog outputs are set to analog values (Vdc); the LED intensity corresponds to the output value.
    For example: At 10Vdc, the LED will be fully on. At 5Vdc, the LED will be at 50% intensity. At 0 Vdc, the LED will be off.

Network Conditions

Please note that all jumper settings must also be set to the same value through BACnet or Modbus. The following is a list of conditions and additional BACnet or Modbus objects.

Universal Inputs (AI1-AI4)

  • For temperature thermistor reading: with the jumper set to Thermistor, set the AI input type to 10K_TypeG, 10K_Type3A1, 10K_Type4A1, 10K_NTC, 20K_Type6A1 or 30K_Type6A1.
  • For on/off contact input reading: with the hardware jumper set to Thermistor, set the AI input type to Digital_Input. The polarity can also be set to direct or reverse. For example, in Reverse an “on” signal would be recognized as an “off” signal.
  • For analog 0-10 Vdc input reading: with the hardware jumper set to 0-10 Vdc, set the AI input type to 0_10V

Universal/Analog Outputs (AO1-AO2)

  • You can set the polarity to direct or reverse. For example, in reverse the output range would be 10-0 Vdc instead of 0-10 Vdc. The polarity applies to all settings 0-10Vdc, on/off and pulsed.
  • You can also set the outputs to pulsed or digital on/off.
  • A fixed output value can only be modified via BACnet when the override switch is in the “Automatic” position.

Binary Outputs (BO1-BO4)

  • A fixed output (open/closed) can only be modified via BACnet when the override switch is in the “Automatic” position.
  • The displayed text can be set to either Open/Closed, On/Off, or Alarm/Normal (BACnet only).

Supervised Outputs

  • All outputs are fully supervised via BACnet. This provides the actual state of the output including any manual overrides done using the on-board switches.

BACnet Objects Table

 

ID1

 

Name

 

Description

 

Writable?

Notes (* = default)

( = only when UniversalInputxFunction is set to 10K_Type3/G)

 

AI.1

 

UniversalInput1

 

Universal input 1

mode selected by MSV.1

 

Out of service

0 to 10Volt or -40 to 100ºC (150ºC) or

-40 to 212ºF (302ºF) or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1

 

AI.2

 

UniversalInput2

 

Universal input 2

mode selected by MSV.12

 

Out of service

0 to 10Volt or -40 to 100ºC (150ºC) or

-40 to 212ºF (302ºF) or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1

 

AI.3

 

UniversalInput3

 

Universal input 3

mode selected by MSV.15

 

Out of service

0 to 10Volt or -40 to 100ºC (150ºC) or

-40 to 212ºF (302ºF) or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1

 

AI.4

 

UniversalInput4

 

Universal input 4

mode selected by MSV.48

 

Out of service

0 to 10Volt or -40 to 100ºC (150ºC) or

-40 to 212ºF (302ºF) or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1

AV.52 AnalogOutput1Min Min. voltage of analog output 1 Present Value 0* Volt to AV.54 | Resolution 0.1 Volt
AV.53 AnalogOutput2Min Min. voltage of analog output 2 Present Value 0* Volt to AV.55 | Resolution 0.1 Volt
AV.54 AnalogOutput1Max Max. voltage of analog output 1 Present Value AV.52 to 10.0* Volt | Resolution 0.1 Volt
AV.55 AnalogOutput2Max Max. voltage of analog output 2 Present Value AV.53 to 10.0* Volt | Resolution 0.1 Volt
AV.72 AnalogOutput1 Analog output 1 value Present Value 0-100% | Resolution 0.1%
AV.73 AnalogOutput2 Analog output 2 value Present Value 0-100% | Resolution 0.1%
AV.226 UniversalInput1Offset Universal input 1 offset Present Value -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)

Resolution: 0.1 ºC/ºF/Volt/mA

AV.227 UniversalInput2Offset Universal input 2 offset Present Value -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)

Resolution: 0.1 ºC/ºF/Volt/mA

AV.228 UniversalInput3Offset Universal input 3 offset Present Value -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)

Resolution: 0.1 ºC/ºF/Volt/mA

AV.229 UniversalInput4Offset Universal input 4 offset Present Value -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)

Resolution: 0.1 ºC/ºF/Volt/mA

AV.468 CopyCfgStartAdd Copy configuration start address Present Value 0-254 Address of first CMMB to copy Available only if BV.101 is set to No
 

AV.469

 

CopyCfgEndAdd

 

Copy configuration end address

 

Present Value

AV.468 – (AV.468 + 64)

Address of last CMMB to copy Available only if BV.101 is set to No

 

 

 

AV.470

 

 

 

CopyCfgResult2

 

 

 

Copy configuration result

 

 

 

Present Value

AV.468 – AV.469

Result of copy is available on Description property and is available only if BV.101 is set to Yes. Results: Succeed, Prog_Error, Type_Error, Model_Error, FW_Error, Mem_Error, Size_Error, Comm_Error, SlaveDevice, InProgress, AllSucceed

AV.500 TPMOutput1 TPM Output 1 value Present Value 0-100% | Resolution 0.1%
AV.501 TPMOutput2 TPM Output 2 value Present Value 0-100% | Resolution 0.1%
 

BV.22

 

ContactOutput1

 

Binary output 1 status

 

Present Value

0= Open / Ouvert / Off / Arret / Normal * 1= Close / Fermé / On / Marche / Alarm Text depends of selection in MSV.66
 

BV.23

 

ContactOutput2

 

Binary output 2 status

 

Present Value

0= Open / Ouvert / Off / Arret / Normal * 1= Close / Fermé / On / Marche / Alarm Text depends of selection in MSV.67
 

BV.24

 

ContactOutput3

 

Binary output 3 status

 

Present Value

0= Open / Ouvert / Off / Arret / Normal * 1= Close / Fermé / On / Marche / Alarm Text depends of selection in MSV.68
 

BV.25

 

ContactOutput4

 

Binary output 4 status

 

Present Value

0= Open / Ouvert / Off / Arret / Normal * 1= Close / Fermé / On / Marche / Alarm Text depends of selection in MSV.69
BV.66 AnalogOutput1Direction Polarity of analog output 1 Present Value 0= Direct * 1= Reverse
BV.67 AnalogOutput2Direction Polarity of analog output 2 Present Value 0= Direct * 1= Reverse
BV.93 UI1_DI_Polarity Polarity of universal input 1 when used in digital input mode Present Value 0= Direct *

1= Reverse

 

ID1

 

Name

 

Description

 

Writable?

Notes (* = default)

( = only when UniversalInputxFunction is set to 10K_Type3/G)

BV.94 UI2_DI_Polarity Polarity of universal input 2 when used in digital input mode Present Value 0= Direct *

1= Reverse

BV.95 UI3_DI_Polarity Polarity of universal input 3 when used in digital input mode Present Value 0= Direct *

1= Reverse

BV.96 UI4_DI_Polarity Polarity of universal input 4 when used in digital input mode Present Value 0= Direct *

1= Reverse

 

BV.101

 

CopyCfgExecute

 

Start or stop copy configuration

 

Present Value

0= No *

1= Yes

Start copy and give results, must be reset by user.

BV.102 SystemUnit Select the unit system to use on the device Present Value 0= Celsius *

1= Fahrenheit

BV.103 Inhibit Output Override Inhibit the override of the outputs Present Value 0= Off *

1= On

 

 

MSV.1

 

 

UniversalInput1Function

 

 

Selected analog input 1 mode

 

 

Present Value

1= 0_10V

2= 4_20mA

3= 10K_Type3/G *

4= 10K_Type3A1

5= 10K_Type4A1

6= 10K_Type2

7= 20K_Type6A1

8= 30K_Type6A1

9= Digital_Input

 

 

MSV.12

 

 

UniversalInput2Function

 

 

Selected analog input 2 mode

 

 

Present Value

1= 0_10V

2= 4_20mA

3= 10K_Type3/G *

4= 10K_Type3A1

5= 10K_Type4A1

6= 10K_Type2

7= 20K_Type6A1

8= 30K_Type6A1

9= Digital_Input

 

 

MSV.15

 

 

UniversalInput3Function

 

 

Selected analog input 3 mode

 

 

Present Value

1= 0_10V

2= 4_20mA

3= 10K_Type3/G *

4= 10K_Type3A1

5= 10K_Type4A1

6= 10K_Type2

7= 20K_Type6A1

8= 30K_Type6A1

9= Digital_Input

 

 

MSV.48

 

 

UniversalInput4Function

 

 

Selected analog input 4 mode

 

 

Present Value

1= 0_10V

2= 4_20mA

3= 10K_Type3/G *

4= 10K_Type3A1

5= 10K_Type4A1

6= 10K_Type2

7= 20K_Type6A1

8= 30K_Type6A1

9= Digital_Input

MSV.54 AnalogOutput1Mode Select analog output 1 mode Present Value 1= Analog *

2= On_Off

3= Pulsing
MSV.55 AnalogOutput2Mode Select analog output 2 mode Present Value 1= Analog *

2= On_Off

3= Pulsing
 

MSV.66

 

ContactOutput1Text

Contact output 1 inactive & active text  

Present Value

1= Open_Close *

2= Ouvert_Fermé

3= On_Off

4= Marche_Arret

5= Alarm_Normal

 

MSV.67

 

ContactOutput2Text

Contact output 2 inactive & active text  

Present Value

1= Open_Close *

2= Ouvert_Fermé

3= On_Off

4= Marche_Arret

5= Alarm_Normal

 

MSV.68

 

ContactOutput3Text

Contact output 3 inactive & active text  

Present Value

1= Open_Close *

2= Ouvert_Fermé

3= On_Off

4= Marche_Arret

5= Alarm_Normal

 

MSV.69

 

ContactOutput4Text

Contact output 4 inactive & active text  

Present Value

1= Open_Close *

2= Ouvert_Fermé

3= On_Off

4= Marche_Arret

5= Alarm_Normal

MSV.100 OptofetOutput1Mode Select Optofet output 1 mode Present Value 1= On_Off * 2= TimePulseModulation
MSV.101 OptofetOutput2Mode Select Optofet output 2 mode Present Value 1= On_Off * 2= TimePulseModulation

Modbus Registers

  • Register address:
    • As per protocol base (base 0); for PLC add 1 to protocol base.
    • As per holding register (base 40001)
  • Functions:
    • 03 Read Holding Register
    • 06 Write Single Register
    • 16 Write Multiple Registers
  • Error Codes:
    • 02 Illegal Data Address
    • 03 Illegal Value
    • 06 Slave Device Busy
  • W = Writable register, [blank] = read only.
  • No Real number in modbus register, use scale to calculate real number. Register = Real number * Scale => Real number = Register / Scale. Scale could be 1, 10 or 100
  • Attention when writing a register that contains a bit string. If bit is writable (conditional or not), the write will always be accepted. If bit is reserved or not writable, the write will be ignored and will keep its actual state.
  • Use READ-MODIFY-WRITE sequence.
 

Protocol Base

 

Holding Register

 

Description

 

Data Type

 

MSB/LSB

 

Units/Values

 

Writable

Default Value
MB LB
0 40001 MSB = Neptronic Device ID LSB = MAC Address Unsigned 105 (69h) [1..247]

(1h- F7h)

* MAC address is writable if all DIP switches of DS2 are OFF. W* 69h 1h
 

 

1

 

 

40002

 

 

Device Baud Rate

 

Unsigned Scale 0.01

[96] [192] [384] [576] 9,600

19,200

38,400

57,600

 

 

W

 

 

96

 

 

2

 

 

40003

COM Port Configuration

IMPORTANT: The default value is “no parity, 2 stop bits”. To change the value, you must set DIP switch DS1-3 to OFF. If set to ON, it will always remain at the default value. Refer to

Connections and Configurations on page 2.

 

 

Unsigned

 

 

[0..2]
 

0 = no parity, 2 stop bits 1 = even parity, 1 stop bit 2 = odd parity, 1 stop bit

 

 

W

 

 

0

3 40004 Product Name (characters 8 & 7) 2 x ASCII char 8 char 7 Valid ASCII character: 32 (20h) – 122 (7ah), Empty = 0 W 43h [C] 40h [M]
4 40005 Product Name (characters 6 & 5) 2 x ASCII char 6 char 5 Valid ASCII character: 32 (20h) – 122 (7ah), Empty = 0 W 40h [M] 42h [B]
5 40006 Product Name (characters 4 & 3) 2 x ASCII char 4 char 3 Valid ASCII character: 32 (20h) – 122 (7ah), Empty = 0 W 31h [1] 30h [0]
6 40007 Product Name (characters 2 & 1) 2 x ASCII char 2 char 1 Valid ASCII character: 32 (20h) – 122 (7ah), Empty = 0 W 36h [6] 20h [ ]
7 40008 Firmware Version Unsigned Scale 100 102 1.02 102
8 40009 Application Version Unsigned Scale 100 100 1.00 100
 

Protocol Base

 

Holding Register

 

Description

 

Data Type

 

MSB/LSB

 

Units/Values

 

Writable

Default Value
MB LB
 

 

9

 

 

40010

 

 

System Status 1

 

 

Bit String

 

 

[B0..B15]
0 = Normal

1 = Fault

– – – – – – – – – – – – – – – – – – –

B0 = System operation

 

 

0000, 0001, 1111, 1110b

10 40011 System Status 2 Bit String [B0..B15] Always 0 0000, 0000, 0000, 0000b
 

11

 

40012

 

Analog Input 1

0-10V: Type: Unsigned, Scale:100, Unit: Volt, Range: 0.00-10.00V,                                                                                                                               Resolution: 0.01 4-20mA: Type: Unsigned, Scale:100,  Unit: mA, Range: 4.00-20.00 mA,  Resolution: 0.01 10K Type 3A1, 10K Type 4AI, 10K Type 2, 20K Type 6AI, 30K Type 6AI:

Type: Signed,    Scale:100,     Unit: ºC,     Range: -40.00 – 100.00 ºC, Resolution: 0.01 Type: Signed,                 Scale:100,        Unit: ºF,  Range: -40.00 – 212.00 ºF, Resolution: 0.02

10K Type 3/G:

Type: Signed,    Scale:100,     Unit: ºC,     Range: -40.00 – 150.00 ºC, Resolution: 0.01 Type: Signed,                 Scale:100,        Unit: ºF,  Range: -40.00 – 302.00 ºF, Resolution: 0.02

DI:           Type: Unsigned, Scale:1,      No Unit,     Range: 0-1,                         Resolution: 1

 

0

 

12

 

40013

 

Analog Input 2

 

0

 

13

 

40014

 

Analog Input 3

 

0

 

14

 

40015

 

Analog Input 4

 

0

15 to 19 40016 to

40020

Reserved
20 40021 Analog Output 1 Unsigned Scale 10   [0..1000]  

Unit: %,      Range: 0-100.0%,           Resolution: 0.1

 

W

0
21 40022 Analog Output 2 0
22 to 23 40023 to

40024

Reserved 0
 

24

 

40025

 

Relay Output

 

Bit String

  [B0..B5] B0 = Relay 1

B1 = Relay 2 B2 = Relay 3

B3 = Relay 4

B4 to B5 = Reserved

 

W

 

0000, 0000, 0000, 0000b

 

25

 

40026

Output Overwrite Status

Indicates that the output is overridden by the hardware switch (SW1-SW4).

 

Bit String

  [B0..B9] B0 = Relay 1 B1 = Relay 2 B2 = Relay 3

B3 = Relay 4

B4 = AO1 B5 = AO2

B6 to B9 = Reserved

 

0000, 0000, 0000, 0000b

26 40027 Universal Input 1 Function  

 

Unsigned

 

 

[1..9]
1= 0_10V

2= 4_20mA

3 = 10K_Type 3/G

4= 10K_Type3A1

5= 10K_Type4A1

 

6= 10K_Type2

7= 20K_Type6A1

8= 30K_Type6A1

9= Digital_Input

 

 

W

3
27 40028 Universal Input 2 Function 3
28 40029 Universal Input 3 Function 3
29 40030 Universal Input 4 Function 3
30 to 33 40031 to

40034

Reserved
 

Protocol Base

 

Holding Register

 

Description

 

Data Type

 

MSB/LSB

 

Units/Values

 

Writable

Default Value
MB LB
34 40035 Universal Input 1 Offset  

 

Signed Scale 100

 

 

[0..100]
 

 

Range: +/- 5.00, Resolution: 0.1

 

 

W

0
35 40036 Universal Input 2 Offset 0
36 40037 Universal Input 3 Offset 0
37 40038 Universal Input 4 Offset 0
38 to 41 40039 to

40042

Reserved
 

42

 

40043

 

Analog Output 1 Mode

 

Unsigned

  [1..3] 1 = Analog

2 = On/Off

3 = Pulse

 

W

 

1

43 40044 Analog Output 1 Minimum Voltage Signed Scale 10   [0..100] Unit: Volt, Range: 0 V – Register 44,     Resolution: 0.1  

W

0
44 40045 Analog Output 1 Maximum Voltage Unit: Volt,  Range: Register 43 – 10.0V, Resolution: 0.1 100
 

45

 

40046

 

Analog Output 2 Mode

 

Unsigned

  [1..3] 1 = Analog

2 = On/Off

3 = Pulse

 

W

 

1

46 40047 Analog Output 2 Minimum Voltage Signed Scale 10   [0..100] Unit: Volt, Range: 0 V – Register 47,        Resolution: 0.1  

W

0
47 40048 Analog Output 2 Maximum Voltage Unit: Volt, Range: Register 46 – 10.0V,    Resolution: 0.1 100
48 to 53 40049 to

40054

Reserved
0 = Direct 0 = Off
1 = Reverse 1 = On
– – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – –
B0 =      AO1 polarity B14 = Inhibit Output Override
System Options B1 =      AO2 polarity – – – – – – – – – – – – – – – – – – –
54 40055 Bit String [B0..B15] B2 to B3 = Reserved 0 = Celsius W 0000, 0000, 0000, 0000b
* = digital input mode only B4 =      AI1 polarity * 1 = Fahrenheit
B5 =      AI2 polarity * – – – – – – – – – – – – – – – – – – –
B6 =      AI3 polarity * B15 = System Unit
B7 =      AI4 polarity *
B8 to B13 = Reserved
55 40056 TPM Output 1 Unsigned Scale 10   [0..1000]  

Unit: %,

 

Range: 0-100.0%,           Resolution: 0.1

 

W

0
56 40057 TPM Output 2 0
57 to 60 40058 to

40061

Reserved
61 40062 Optofet Output 1 Mode  

Bit String

  [1, 2] 1 = On_Off

2 = TimePulseModulation

 

W

1
62 40063 Optofet Output 2 Mode 1

400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada
www.neptronic.com
Toll free in North America: 1-800-361-2308
Tel.: 514-333-1433
Fax: 514-333-3163
Customer service fax: 514-333-1091
Monday to Friday: 8:00am to 5:00pm (Eastern time)

Documents / Resources

neptronic CMMB102 Dual Mini I-O Communication Module [pdf] Instruction Manual
CMMB102 Dual Mini I-O Communication Module, CMMB102, Dual Mini I-O Communication Module, I-O Communication Module, Communication Module, Module