Chapter1. Introduction

1.1. Features
The AS400 relay card converts the RS232 signal of the “MegaTec” protocol into a true potential-free dry contact signal, and reflects the operating status of the UPS in real time through changes in the contact signal.

Features:

  1. CPU is PIC 8Bit, system clock is 20MHz, flash memory is 4096 word, and SDRAM is 256 word.
  2. AS400 normal operating temperature and humidity range is 0℃ to 60℃ and 5% to 95%。
  3. FCC, Class B, CE.

1.2. Power Specifications 

Item Minimum Maximum
DC Input Voltage +5.3V +40V
DC Input Current 3W Maximum

1.3. Pin Assignment 

Pin PIN Definition Input / Output Description
P1 UPS Failure O/P P1 short to P5
P2 Summary Alarm: UPS Failure, Battery Low, Utility Failure. O/P P2 short to P5
P3 GND I/P
P4 Remote Shutdown I/P P4 short to P3
P5 Common for Relays I/P
P6 Bypass Active O/P P6 short to P5
P7 Battery Low O/P P7 short to P5
P8 UPS ON O/P P8 short to P5
P9 Utility Failure O/P P9 short to P5

1.4. Signal Specification
Receiver Inputs

PARAMETER CONDITIONS MIN TYP MAX
Input Voltage Range -25V +25V
Input Threshold Low TA=±25℃ +0.6V +1.2V
Input Threshold High TA=±25℃ +1.5V +2.4V
Input Hysteresis 0.3V
Input Resistance TA=±25℃ 3 k ohm 5 k ohm 7 k ohm

Transmitter Outputs 

PARAMETER CONDITIONS MIN TYP MAX
Output Voltage Swing All transmitter outputs loaded with 3k ohm to ground ±5.0V ±5.4V
Output Resistance TA=±25℃ 300 10M
Output Short-Circuit Current ±35mA ±60mA

1.5. Size Specification
AS400 Internal Card

Dimension 137.7mm(L) × 60mm(W) × 43.0mm(H)
Weight 88g±2g
Connector 26PIN gold finger

MegaTec AS400 Relay Card Converts - Internal Card

AS400 Mini Internal Card

Dimension 81.06 mm(L) × 51.76 mm(W) × 25.8 mm(H)
Weight 45 g±2 g
Connector 26PIN gold finger

MegaTec AS400 Relay Card Converts - Mini Internal Card

AS400 External Card 

Dimension 156 mm(L) × 82 mm(W) × 32 mm(H)
Weight 206g±5g

MegaTec AS400 Relay Card Converts - External Card

AS400 Adapter

Dimension 42.5 mm(L) × 36.2 mm(W) × 17.1 mm(H)
Weight 15g±2g

MegaTec AS400 Relay Card Converts - Adapter

Chapter2. Verification Test

There is no need to set up the AS400 relay card. After receiving the product, users can directly refer to the above “PIN Assignment” for verification testing.
Users can directly connect the AS400 to a UPS or simulation software, or directly short-circuit the PIN on the AS400 relay card for verification testing (The outer casing of the external card needs to disassemble, please confirm with our technical support before operation).

Test PIN: 