MEAN-WELL-logo

MEAN WELL RSD-100 Series 100W Railway Single Output DC Converter

MEAN-WELL-RSD-100-Series-100W-Railway-Single-Output-DC-Converter-product

Features

  • Compliance to BS EN/EN50155 and BS EN/EN45545-2 railway standard
  • 2:1 wide input range
  • Protections: Short circuit / Overload / Over voltage / Input reverse polarity
  • 4000VDC 1/O isolation
  • Cooling by free air convection
  • Half encapsulated
  • Built-in constant current limiting circuit
  • 1U low profile 36mm
  • All using 105°C long life electrolytic capacitors
  • LED indicator for power on
  • 100% full load burn-in test
  • 3 vears warranty

SPECIFICATION

MODEL RSD-100B-5 RSD-100B-12 RSD-100B-24 RSD-100C-5 RSD-100C-12 RSD-100C-24 RSD-100D-5 RSD-100D-12 RSD-100D-24
 

 

 

 

 

 

OUTPUT

DC VOLTAGE 5V 12V 24V 5V 12V 24V 5V 12V 24V
RATED CURRENT 20A 8.4A 4.2A 20A 8.4A 4.2A 20A 8.4A 4.2A
CURRENT RANGE 0 ~ 20A 0 ~ 8.4A 0 ~ 4.2A 0 ~ 20A 0 ~ 8.4A 0 ~ 4.2A 0 ~ 20A 0 ~ 8.4A 0 ~ 4.2A
RATED POWER 100W 100.8W 100.8W 100W 100.8W 100.8W 100W 100.8W 100.8W
RIPPLE & NOISE (max.) Note.2 100mVp-p 120mVp-p 150mVp-p 100mVp-p 120mVp-p 150mVp-p 100mVp-p 120mVp-p 150mVp-p
VOLTAGE TOLERANCE Note.3 ±2.0% ±2.0% ±2.0% ±2.0% ±2.0% ±2.0% ±2.0% ±2.0% ±2.0%
LINE REGULATION ±0.5% ±0.3% ±0.2% ±0.5% ±0.3% ±0.2% ±0.5% ±0.2% ±0.2%
LOAD REGULATION ±1.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0%
SETUP, RISE TIME 800ms, 50ms at full load
HOLD UP TIME (Typ.) Please refer to page 3 Hold up Time( Load de-rating curve )
 

 

 

 

INPUT

VOLTAGE RANGE CONTINUOUS 16.8 ~ 31.2VDC 33.6 ~ 62.4VDC 67.2 ~ 143VDC
1 SEC. 14.4 ~ 33.6VDC 28.8 ~ 67.2VDC 57.6 ~ 154VDC
EFFICIENCY (Typ.) 88% 89% 89% 89% 91% 91% 89.5%                91% 90%
DC CURRENT (Typ.) 4.8A/24V 4.8A/24V 4.8A/24V 2.4A/48V 2.4A/48V 2.4A/48V 1.2A/110V 1.2A/110V 1.2A/110V
INRUSH CURRENT (Typ.) 30A/24VDC 30A/48VDC 30A/110VDC
 

INTERRUPTION OF VOLTAGE SUPPLY

EN50155:2007-B/C- type comply with S1 level @ full load, comply with S2 level @ 70% load ; D-type comply with S2 level @ full load
EN50155:2017-Comply with S1 level
 

 

PROTECTION

 

OVERLOAD

105 ~ 135% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
 

OVER VOLTAGE

5.75 ~ 7V 13.8 ~ 16.2V 27.6 ~ 32.4V 5.75 ~ 7V 13.8 ~ 16.2V 27.6 ~ 32.4V 5.75 ~ 7V 13.8 ~ 16.2V 27.6 ~ 32.4V
Protection type : Shut down o/p voltage, re-power on to recover
 

 

 

ENVIRONMENT

WORKING TEMP. -40 ~ +55℃ (no derating) ; +70℃ @ 60% load by free air convection ; +70℃ no derating with external base plate, TX class compliance
WORKING HUMIDITY 5 ~ 95% RH non-condensing
STORAGE TEMP. -40 ~ +85℃
TEMP. COEFFICIENT ±0.03%/℃ (0 ~ 50℃)
VIBRATION 10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes ; Mounting : compliance to IEC61373
OPERATING ALTITUDE 5000 meters
 

 

SAFETY & EMC

(Note 5)

SAFETY STANDARDS IEC 62368-1, UL 62368-1, AS/NZS 62368-1, EAC TP TC 004 approved, Design refer to BS EN/EN62368-1
WITHSTAND VOLTAGE I/P-O/P:4KVDC  I/P-FG:2.5KVDC  O/P-FG:2.5KVDC
ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION Compliance to BS EN/EN55032 (CISPR32) Conduction Emission: Class A, Radiation Emission: Class B, EAC TP TC 020
EMC IMMUNITY Compliance to BS EN/EN61000-4-2,3,4,5,6,8, BS EN/EN55035, light industry level, EAC TP TC 020
RAILWAY STANDARD BS EN/EN50155 / IEC60571 including IEC61373 for shock & vibration, BS EN/EN50121-3-2 for EMC ; BS EN/EN45545-2 for fire protection
 

OTHERS

MTBF 2446.2K hrs min.       Telcordia SR-332 (Bellcore) ; 254.2K hrs min.        MIL-HDBK-217F (25℃)
DIMENSION 161*68*36mm (L*W*H)
PACKING 0.563Kg; 24pcs/14.5Kg/0.91CUFT
 

NOTE

1.  All parameters NOT specially mentioned are measured at 24,48,110VDC input, rated load and 25℃ of ambient temperature.

2.  Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.

3.  Tolerance: includes set up tolerance, line regulation, and load regulation.

4.  Strongly recommended that external output capacitance should not exceed 5000uF. (Only for: RSD-100-5 / -12)

5.  The power supply is considered a component that will be installed into the final equipment. All the EMC tests are been executed by mounting the unit on a 360mm*360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)

6.  The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).

※ Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Mechanical Specification

MEAN-WELL-RSD-100-Series-100W-Railway-Single-Output-DC-Converter-fig-1

Block Diagram

MEAN-WELL-RSD-100-Series-100W-Railway-Single-Output-DC-Converter-fig-2

Input Fuse

There is one fuse connected in series to the positive input line, which is used to protect against abnormal surge. Fuse specifications of each model are shown as below.

Type Fuse Type Reference and Rating
B Time-Lag Conquer UDA-A, 10A, 250V
C Time-Lag Conquer UDA-A, 5A, 250V
D Time-Lag Conquer UDA-A, 3.15A, 250V

Input Reverse Polarity Protection
There is a MOSFET connected in series to the negative input line. If the input polarity is connected reversely, the MOSFET opens and there will be no output to protect the unit.

Input Range and Transient Ability
The series has a wide range input capability. Within ±30% of rated input voltage, it can be executed at full-load operation and operate properly; with±40% of rated input voltage, it can withstand that for 1 second.

Input Under-Voltage Protection
If input voltage drops below Vimin, the internal control IC shuts down and there is no output voltage. It recovers automatically when input voltage reaches above Vimin, please refer to the cruve below.MEAN-WELL-RSD-100-Series-100W-Railway-Single-Output-DC-Converter-fig-3

Inrush Current
Inrush current is suppressed by a resistor during the initial start-up, and then the resistor is bypassed by a MOSFET to reduce power consumption after accomplishing the start-up.

Hold-up Time

  • EN50155: 2007 version -D type complies with S2 level, while B and C types comply with S1 level at full load output condition. To fulfil the This function is optional, which the standard product does not have it. If you do need the function, please contact MW for details. requirements of S2 level, B and C types require de-rating their output load to 70%, please refer to the curve diagrams below.MEAN-WELL-RSD-100-Series-100W-Railway-Single-Output-DC-Converter-fig-4

Output Voltage Adjustment
This function is optional, which the standard product does not have it. If you do need the function, please contact MW for details.

Efficiency vs Load & Vin Curve

The efficiency vs load & Vin curves of each model are shown as below.

MEAN-WELL-RSD-100-Series-100W-Railway-Single-Output-DC-Converter-fig-5

Parallel and Series Connection

Operation in Parallel

Since the RSD-100 series doesn’t have a built-in parallel circuit, it can only use external circuits to achieve redundant operation but not increase the current rating.

  1. Add a diode at the positive output of each power supply (as shown as below), the current rating of the diode should be larger than the maximum output current rating and attached to a suitable heat sink. This is only for redundant use (increase the reliability of the system) and users have to check the suitability of the circuit by themselves.MEAN-WELL-RSD-100-Series-100W-Railway-Single-Output-DC-Converter-fig-6
  2. When using S.P.S. in parallel connection, the leakage current will increase at the same time. This could pose as a shock hazard for the user. So please contact the supplier if you have this kind of application.

Operation in Series

RSD-100 can be operated in series. Here are the methods of doing it:

  1. Positive and negative terminals are connected as shown as below. According to the connection, you can get the positive and negative output voltages for your loads.MEAN-WELL-RSD-100-Series-100W-Railway-Single-Output-DC-Converter-fig-7
  2. Increase the output voltage (current does not change). Because the RSD-100 series have no reverse blocking diode in the unit, you should add an external blocking diode to prevent damage of every unit while starting up. The voltage rating of the external diode should be larger than V1+V2 (as shown as below).MEAN-WELL-RSD-100-Series-100W-Railway-Single-Output-DC-Converter-fig-8

Overload Protection

If the output draws up to 105~135% of its output power rating, the converter will go into overload protection which is constant current mode. After the faulty condition is removed, it will recover automatically. Please refer to the diagram below for the detail operation characteristics. Please note that it’s not suitable to operate within the overload region continuously, or it may cause to over temperature and reduce the life of the power supply unit or even damage it.MEAN-WELL-RSD-100-Series-100W-Railway-Single-Output-DC-Converter-fig-9

Over Voltage Protection

  • The converter shuts off to protect itself when the output voltage drawn exceeds 115~140% of its output rating. It must be repowered on to recover.

LED Indicator

  • Equipped with a built-in LED indicator, the converter provides an easy way for users to check its condition through the LED indicator. Green: normal operation; No signal: no power or failure.

Derating Curve

Single unit operation
If the unit has no iron plate mounted on its bottom, the maximum ambient temperature for the unit will be 55℃ as operating under full load conditions. It requires a de-rating output current when the ambient temperature is between 55-70℃, please refer to the de-rating curve below.MEAN-WELL-RSD-100-Series-100W-Railway-Single-Output-DC-Converter-fig-10

Suitable installation methods are shown as below. Since RSD-100 is a semi-potted model, its thermal performances for the following installation methods are similar and share the same derating curve.MEAN-WELL-RSD-100-Series-100W-Railway-Single-Output-DC-Converter-fig-11

Operate with additional iron plate
If it is necessary to fulfil the requirements of EN50155 TX level that operate the unit fully-loaded at 70℃, the RSD-100 series must be installed onto an iron plate on the bottom. The size of the suggested iron plate is shown as below. In order for optimal thermal performance, the iron plate must have an even & smooth surface and the RSD-100 series must be firmly mounted at the center of the iron plate.MEAN-WELL-RSD-100-Series-100W-Railway-Single-Output-DC-Converter-fig-12

The load vs ambient temperature curve is shown as below.

MEAN-WELL-RSD-100-Series-100W-Railway-Single-Output-DC-Converter-fig-13

Suitable installation methods are shown as below. Since RSD-100 is a semi-potted model, its thermal performances for the following installation methods are similar and share the same derating curve.MEAN-WELL-RSD-100-Series-100W-Railway-Single-Output-DC-Converter-fig-14

Immunity to Environmental Conditions

Test method Standard Test conditions Status
Cooling Test EN 50155 section 12.2.3 (Column 2, Class TX)

EN 60068-2-1

Temperature: -40℃

Dwell Time: 2 hrs/cycle

No damage
 

Dry Heat Test

EN 50155 section 12.2.4 (Column 2, Class TX)

EN 50155 section 12.2.4 (Column 3, Class TX & Column 4, Class TX) EN 60068-2-2

Temperature: 70℃ / 85℃ Duration: 6 hrs / 10min  

PASS

 

Damp Heat Test, Cyclic

EN 50155 section 12.2.5

EN 60068-2-30

Temperature: 25℃~55℃ Humidity: 90%~100% RH Duration: 48 hrs  

PASS

 

Vibration Test

EN 50155 section 12.2.11

EN 61373

Temperature: 19℃ Humidity: 65%

Duration: 10 mins

 

PASS

 

Increased Vibration Test

EN 50155 section 12.2.11

EN 61373

Temperature: 19℃ Humidity: 65%

Duration: 5 hrs

 

PASS

 

Shock Test

EN 50155 section 12.2.11

EN 61373

Temperature: 21± 3℃ Humidity: 65 ± 5%

Duration: 30ms*18

 

PASS

 

Low Temperature Storage Test

EN 50155 section 12.2.3 (Column 2, Class TX)

EN 60068-2-1

Temperature: -40℃ Dwell Time: 16 hrs  

PASS

 

Salt Mist Test

 

EN 50155 section 12.2.10 (Class ST4)

Temperature: 35℃±2℃ Duration: 96 hrs  

PASS

EN45545-2 Fire Test Conditions

Test Items Hazard Level
Items Standard HL1 HL2 HL3
 

 

 

R22

Oxygen index test EN 45545-2:2013

EN ISO 4589-2:1996

PASS PASS PASS
Smoke density test EN 45545-2:2013

EN ISO 5659-2:2006

PASS PASS PASS
Smoke toxicity test EN 45545-2:2013 NF X70-100:2006 PASS PASS PASS
R24 Oxygen index test EN 45545-2:2013

EN ISO 4589-2:1996

PASS PASS PASS
R25 Glow-wire test EN 45545-2:2013

EN 60695-2-11:2000

PASS PASS PASS
R26 Vertical flame test EN 45545-2:2013

EN 60695-11:2003

PASS PASS PASS

Documents / Resources

MEAN WELL RSD-100 Series 100W Railway Single Output DC Converter [pdf] Owner's Manual
RSD-100B-5, RSD-100B-12, RSD-100B-24, RSD-100C-5, RSD-100C-12, RSD-100C-24, RSD-100D-5, RSD-100D-12, RSD-100D-24, RSD-100 Series, RSD-100 Series 100W Railway Single Output DC Converter, 100W Railway Single Output DC Converter, Railway Single Output DC Converter, Single Output DC Converter, Output DC Converter, DC Converter, Converter

References

Leave a comment

Your email address will not be published. Required fields are marked *