Features

MEAN-WELL-DBUF20-24-24V-Din-Rail-Type-Buffer-Module-FIG (2)

MEAN-WELL-DBUF20-24-24V-Din-Rail-Type-Buffer-Module-FIG (1)

  • Buffering with electrolytic capacitors instead of lead-acid batteries
  • A type buffering time of 350ms @22Vdc/20A
  • Buffer mode selectable by switch:
    • Fixed mode at 22Vdc
    • Dynamic mode for Vin-1 Vdc
  • LED indicator for signal status
  • Supports parallel connection to extend the buffering time
  • Cooling by free air convection
  • -25~+75°C wide operating temperature
  • 3 years warranty

Applications

  • Industrial control system
  • Semiconductor fabrication equipment
  • Factory automation
  • Electro-mechanical apparatus

GTIN CODE

Model Encoding

MEAN-WELL-DBUF20-24-24V-Din-Rail-Type-Buffer-Module-FIG (3)

SPECIFICATION

MODEL   DBUF20-24
 

 

 

 

 

CHARGING MODE

DC NORMAL OPERATING VOLTAGE 24Vdc
CHARGING VOLTAGE 23~30Vdc
CHARGING CURRENT 900mA Max.
CURRENT CONSUMPTION AT

STANDBY

100mA Max.
 

CHARGING TIME

15s Typ.
25s Max.
 

 

 

 

 

 

BUFFER

MODE

DC NORMAL OPERATING VOLTAGE 22Vdc/Vin-1Vdc
DC OPERATING VOLTAGE RANGE 22-29Vdc
OUTPUT CURRENT(max.) 20A
 

BUFFER TIME

(Refer to Buffering Curve at 22Vdc)

Output current 20A 10A 0.1A
Typ. 350ms 700ms 45s
Min. 250ms 500ms 30s
RIPPLE & NOISE (max.)                                                        Note.2 200mVp-p
 

 

 

 

 

PROTECTION

OVER VOLTAGE 31~37.5V only,shut down o/p voltage
 

OVER LOAD

105%~125% rated output power at buffer mode
Protection type:Shut down o/p voltage , re-power on to recover
SHORT CIRCUIT Protection type:Shut down o/p voltage , re-power on to recover
TVS FOR SIGNALS (max.) 35V
REVERSE POLARITY PROTECTION By internal MOSFET, no damage , recovers automatically after fault condition removed
 

 

 

 

 

 

 

 

 

FUNCTION

 

SELECTABLE BY SWITCH

Fix 22Vdc(Default) Buffering starts if terminal voltage falls below 22Vdc
Vin-1Vdc Buffering starts if terminal voltage is decreased by > 1Vdc
 

CONTROL

 

Inhibit (I)

+Vs – V(I) < 6Vdc: Buffer module ON;  +Vs – V(I) >10Vdc: Buffer module OFF
35Vdc /4mA Max.
 

 

 

 

 

SIGNALS

 

Ready(R)

Charged ready: V(R)>+Vs – 2Vdc;  Unready: V(R)<1Vdc
35Vdc /10mA Max.
 

Buffering (B)

Buffering: V(B)>+Vs – 2Vdc;  Other mode: V(B)<1Vdc
35Vdc /10mA Max.
Supply Voltage(+Vs) 10~35Vdc /10mA(Connected to +V or external voltage)
 

 

 

 

LED STATUS DISPLAY

ON Ready
OFF Discharged
 

Flashing

1Hz Charging
10Hz Buffering
PARALLEL CONNECTION Refer to Typical Application Notes(Page 6)
 

 

 

 

 

 

ENVIRONMENT

WORKING TEMP. -25~+75℃(Refer to”Derating Curve”)
WORKING HUMIDITY 5 ~ 95% RH non-condensing
STORAGE TEMP. -25~+80℃
SHOCK TEST IEC60068-2-27,30G (300m/S²) for a duration of 18ms,1 time per direction,2 times in total
TEMP. COEFFICIENT ±0.03%/℃ (0 ~ 75℃)
 

VIBRATION

Component: 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting clip: Compliance to IEC60068-2-6
OPERATING ALTITUDE                                                   Note.3 5000 meters /OVCⅡ
 

 

 

 

 

 

 

 

 

 

 

 

SAFETY & EMC

(Note.4)

SAFETY STANDARDS IEC62368-1,UL62368-1  approved
WITHSTAND VOLTAGE IP/OP-FG:2.2KVdc; Signals-FG:2.2KVdc
ISOLATION RESISTANCE IP/OP-FG, Signals-FG: >100M Ohms / 500Vdc / 25℃/ 70% RH
 

 

 

 

EMC EMISSION

Parameter Standard Test Level / Note
Conducted BS EN/EN55032 Class B
Radiated BS EN/EN55032 Class B
Voltage Flicker —– —–
Harmonic Current —– —–
 

 

 

 

 

 

 

EMC IMMUNITY

BS EN/EN55035, BS EN/EN61000-6-2
Parameter Standard Test Level / Note
ESD BS EN/EN61000-4-2 Level 4, 15KV air ; Level 3, 8KV contact; criteria A
Radiated BS EN/EN61000-4-3 Level 3, 10V/m ; criteria A
EFT / Burst BS EN/EN61000-4-4 Level 3, 2KV ; criteria A
Surge BS EN/EN61000-4-5 Level 3, 1KV/Line-Line ;Level 3, 2KV/Line-Line-FG ;criteria A
Conducted BS EN/EN61000-4-6 Level 3, 10V ; criteria A
Magnetic Field BS EN/EN61000-4-8 Level 4, 30A/m ; criteria A
 

 

 

 

OTHERS

 

MTBF

164.8K hrs min.  MIL-HDBK-217F (25℃) ; 1510.0K hrs min.         Telcordia TR/SR-332 (Bellcore) (25℃)
108.6K hrs min.  MIL-HDBK-217F (40℃) ; 765.8K hrs min.          Telcordia TR/SR-332 (Bellcore) (40℃)
DIMENSION 63*125.2*114.9mm (W*H*D)
PACKING 1.062Kg; 12pcs/12.8Kg/0.74CUFT
 

 

 

 

 

 

NOTE

 

1.  All parameters NOT specially mentioned are measured at normal input, rated load and 25℃ of ambient temperature.

2.  Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.

3.  The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).

4.  The power supply is considered as an independent unit, but the final equipment still need to confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf)

※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram

MEAN-WELL-DBUF20-24-24V-Din-Rail-Type-Buffer-Module-FIG (4)

Derating Curve

MEAN-WELL-DBUF20-24-24V-Din-Rail-Type-Buffer-Module-FIG (5)

Buffering Curve

MEAN-WELL-DBUF20-24-24V-Din-Rail-Type-Buffer-Module-FIG (6)

Function Manual

User Elements

MEAN-WELL-DBUF20-24-24V-Din-Rail-Type-Buffer-Module-FIG (7)

Back-up Threshold Voltage Selectable by Switch:

  • Option 1: Fixed mode (Switch in Fix 22Vdc) The unit switches to buffer mode as soon as the voltage falls below 22Vdc.
  • Option 2: Dynamic mode (Switch in Vin-1Vdc) Unit switches to buffer mode when input voltage decreases by 1Vdc.

Note: Factory setting is fixed mode.

  • LED Indicator Status:
  • LED OFF: Capacitors are discharged
  • LED ON: Capacitors are fully charged.
  • LED Flashing slowly (1Hz): Capacitors are getting charged.
  • LED Flashing quickly (10Hz): Capacitors are getting discharged.

Signal Connector:

  • Inhibit, +Vs – VI)<6Vdc: Buffer module ON; +Vs – VI) >10Vdc: Buffer module OFF.
  • Ready, Charged ready: V(R)>+Vs – 2Vdc; Unready: V(R)<1 Vac.
  • Buffering, Buffering: V(B)>+Vs – 2Vdc; Other mode: V(B)<1Vdc.

Operating Diagram

MEAN-WELL-DBUF20-24-24V-Din-Rail-Type-Buffer-Module-FIG (8)

Signal Schematics

MEAN-WELL-DBUF20-24-24V-Din-Rail-Type-Buffer-Module-FIG (9)

Typical Application Notes

  1. General wiring diagram
  2. MEAN-WELL-DBUF20-24-24V-Din-Rail-Type-Buffer-Module-FIG (10)Signals supplied from an external voltageMEAN-WELL-DBUF20-24-24V-Din-Rail-Type-Buffer-Module-FIG (11)
  3. Paralleling of buffer unitsMEAN-WELL-DBUF20-24-24V-Din-Rail-Type-Buffer-Module-FIG (12)

Mechanical Specification

(Unit: mm, tolerance ÷ 1mm)

MEAN-WELL-DBUF20-24-24V-Din-Rail-Type-Buffer-Module-FIG (13)

Installation Instruction

MEAN-WELL-DBUF20-24-24V-Din-Rail-Type-Buffer-Module-FIG (14)

Installation Manual

Documents / Resources

MEAN WELL DBUF20-24 24V Din Rail Type Buffer Module [pdf] Owner's Manual
DBUF20-24, DBUF20-24 24V Din Rail Type Buffer Module, 24V Din Rail Type Buffer Module, Rail Type Buffer Module, Type Buffer Module, Buffer Module, Module

References

Leave a comment

Your email address will not be published. Required fields are marked *