LS logoLS ELECTRIC XBO-AD02A Programmable Logic Controller XGB AnalogC/N: 10310001187
XBO-AD02A
XGB Analog

Programmable Logic Controller Installation Guide
This installation guide provides simple function information of PLC control. Please read carefully this data sheet and manuals before using products. Especially read safety precautions and handle the products properly.

Safety Precautions

Meaning of warning and caution inscription

AVTech BATR3CWWW Battery Light - Icon WARNING WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury
AVTech BATR3CWWW Battery Light - Icon CAUTION CAUTION indicates a potentially hazardous situation which,  if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices

 AVTech BATR3CWWW Battery Light - IconWARNING

  1. Do not contact the terminals while the power is applied.
  2. Protect the product from being gone into by foreign metallic matter.
  3. Do not manipulate the battery(charge, disassemble, hitting, short, soldering).

AVTech BATR3CWWW Battery Light - Icon CAUTION

  1. Be sure to check the rated voltage and terminal arrangement before wiring.
  2. When wiring, tighten the screw of terminal block with the specified torque range.
  3. Do not install the flammable things on surroundings.
  4. Do not use the PLC in the environment of direct vibration.
  5. Except expert service staff, do not disassemble or fix or modify the product.
  6. Use the PLC in an environment that meets the general specifications contained in this datasheet.
  7. Be sure that external load does not exceed the rating of output module.
  8. When disposing of PLC and battery, treat it as industrial waste.

Operating Environment

To install, observe the below conditions.

No Item Specification Standard
1 Ambient temp. 0 – 55t
2 Storage temp. -25 – 70 t
3 Ambient humidity 5 – 95%RH, non-condensing
4 Storage humidity 5 – 95%RH, non-condensing
5 Vibration Resistance Occasional vibration
Frequency Acceleration Amplitude Number IEC 61131-2
55f<8.4 Hz 3.5mm 10 times in
each
direction
for
X, Y, Z
8.45f5150Hz 9.8mis'(1 g)
Continuous vibration
Frequency Acceleration Amplitude
55K8.4 Hz 1.75mm
8.45f5150Hz 4.9rnis'(0.5g)

Applicable Support Software

For system configuration, the following version is necessary.

  1. XBC Type : E(V1.1 or above), SU(V1.0 or above), H(V1.1 or above)
  2. XEC Type : E(V1.1 or above), SU(V1.1 or above), H(V1.2 or above)
  3. XG5000 Software : V4.0 or above

Parts Name and Dimension (mm)

This is front part of the Module. Refer to each name when driving the system. For more information, refer to user manual.LS ELECTRIC XBO-AD02A Programmable Logic Controller XGB Analog - Parts Name and Dimension

Installing / Removing Modules

Option Board can be installed in 9 or 10 slot of the Main Unit(Standard/Economic Type) as shown below.LS ELECTRIC XBO-AD02A Programmable Logic Controller XGB Analog - Option Board

  1. When installing Option Board, push the lower part( ①) of the Option Board to contact with connector.LS ELECTRIC
  2. After pushing the lower part( ①) completely, push the upper( ②) part of the Option Board entirely.

Performance Specifications

Performance specifications are as follows

Item XBO-ADO2A
Analog
input
Type Voltage Current
Range DC 0-10V DC 4-20mA
DC 0-20mA
Digital
output
Type 12bit binary data
Range Unsigned
value
0-4,000
Sig
Signed
value
-2,000-2,000
Precise
value
0-1,000
(DC 0 – 10V)
400-2,000(DC 4-20mA)
0-2,000(DC 0-20mA)
Percentile
value
0-1,000
Max. resolution 114,000
Accuracy ±1.0% or less

Wiring

Precaution for wiring

  1. Don’t let AC power line near to analog input module’s external output signal line.
    With an enough distance kept away between, it will be free from surge or inductive noise.
  2. Cable shall be selected in due consideration of ambient temperature and allowable current. More than AWG22 (0.3 ㎟) is recommended.
  3. Don’t let the cable too close to hot device and material or in direct contact with oil for long, which will cause damage or abnormal operation due to short-circuit.
  4. Check the polarity when wiring the terminal.
  5. Wiring with high-voltage line or power line may produce inductive hindrance causing abnormal operation or defect.
  6. Enable the channel that you want to use.

Wiring example

  1. In case of current input, connect V+ terminal and I+ terminal.
  2. Input resistance of current input circuit is 250Ω. (typ.)
  3. Input resistance of voltage input circuit is 1 MΩ. (min.)

Warranty

  • The warranty period is 36 months from the date of manufacture.
  • The initial diagnosis of faults should be conducted by the user. However, upon request, LS ELECTRIC or its representative(s) can undertake this task for a fee. If the cause of the fault is found to be the responsibility of LS ELECTRIC, this service will be free of charge.
  • Exclusions from warranty
  1. Replacement of consumable and life-limited parts (e.g. relays, fuses, capacitors, batteries, LCDs, etc.)
  2. Failures or damages caused by improper conditions or handling outside those specified in the user manual
  3. Failures caused by external factors unrelated to the product
  4. Failures caused by modifications without LS ELECTRIC’s consent
  5. Use of the product in unintended ways
  6. Failures that cannot be predicted/solved by current scientific technology at the time of manufacture
  7. Failures due to external factors such as fire, abnormal voltage, or natural disasters
  8. Other cases for which LS ELECTRIC is not responsible
  • For detailed warranty information, please refer to the user’s manual.
  • The content of the installation guide is subject to change without notice for product performance improvement.

LS ELECTRIC Co., Ltd. www.ls-electric.com 10310001187 V4.5 (2024.6)

• Headquarter/Seoul Office Tel: 82-2-2034-4033,4888,4703
• LS ELECTRIC Shanghai Office (China) Tel: 86-21-5237-9977
• LS ELECTRIC (Wuxi) Co., Ltd. (Wuxi, China) Tel: 86-510-6851-6666
• LS-ELECTRIC Vietnam Co., Ltd. (Hanoi, Vietnam) Tel: 84-93-631-4099
• LS ELECTRIC Middle East FZE (Dubai, U.A.E.) Tel: 971-4-886-5360
• LS ELECTRIC Europe B.V. (Hoofddorf, Netherlands) Tel: 31-20-654-1424
• LS ELECTRIC Japan Co., Ltd. (Tokyo, Japan) Tel: 81-3-6268-8241
• LS ELECTRIC America Inc. (Chicago, USA) Tel: 1-800-891-2941

Factory: 56, Samseong 4-gil, Mokcheon-eup, Dongnam-gu, Cheonan-si, Chungcheongnamdo, 31226, Korea

LS logoE-mail: automation@ls-electric.comLS ELECTRIC XBO-AD02A Programmable Logic Controller XGB Analog - symbol

Documents / Resources

LS ELECTRIC XBO-AD02A Programmable Logic Controller XGB Analog [pdf] User Guide
XBO-AD02A, XBO-AD02A Programmable Logic Controller XGB Analog, XBO-AD02A, Programmable Logic Controller XGB Analog, Logic Controller XGB Analog, XGB Analog, Analog

References

Leave a comment

Your email address will not be published. Required fields are marked *