Lindab CVA Perforated Diffuser Installation Guide
Lindab CVA Perforated Diffuser

Description

Comdif CVA is a rectangular perforated displacement diffuser for installation in walls or similar structures. CVA has a rectangular connection. Behind the perforated front plate, CVA is equipped with individually adjustable nozzles, making it possible to alter the geometry of the near zone. The diffuser can be turned and has a rectangular duct connection, so the diffuser can be connected at the top or bottom. A wall duct with circular connection is supplied as an accessory. The diffuser is suitable for the supply of large volumes
of moderately cooled air.

  • The diffuser is suitable for installation in walls.
  • The geometry of the near zone can be adjusted using adjustable nozzles.
  • A wall duct can be supplied as an accessory

Maintenance

The front plate can be removed from the diffuser, making it possible to clean the nozzles. The visible parts of the diffuser can be wiped with a damp cloth.

Ordering example
Ordering example

Order – accessories 

Wall duct: CVAZ – 1 – size

Dimension

Dimension

Size A [mm] B [mm] D [mm] H [mm] Weight [kg]
3005 540 50 75 320 4.40
5005 540 50 75 450 5.80
6005 540 50 75 580 8.70
6008 540 80 105 580 9.00
8008 540 80 105 840 12.0

Cutting dimension: A – 30 x H – 30

Accessories

Can be supplied with wall duct.

Materials and finish

Diffuser: Galvanised steel
Nozzles: Black plastic
Front plate: 1.5 mm galvanised steel
Standard finish: Powder-coated
Standard colour: RAL 9003 or RAL 9010 – white, gloss 30

The diffuser is available in other colours. Please contact Lindab’s sales department for further information.

Technical data

Technical data

Icon Recommended maximum volume flow.

The near zone is given at an under-temperature of -3 K to a maximum terminal velocity of 0.20 m/s.
Conversion to other terminal velocities – see table 1, correction of the near zone for -3 K and -6 K respectively.

Sound effect level

Sound effect level LW [dB] = LWA + Kok

Size  

63

 

125

Centre frequency Hz

250     500      1K       2K

 

4K

 

8K

3005 7 -2 -2 1 -8 -17 -27 -38
5005 7 -3 -1 1 -7 -17 -29 -36
6005 11 -4 -1 1 -7 -17 -29 -37
6008 12 -4 2 1 -9 -20 -31 -31
8008 10 -4 2 1 -9 -19 -30 -43
Sound attenuation

Sound attenuation ΔL [dB] including end reflection.

Size 63 125 Centre frequency Hz
250     500      1K       2K
4K 8K
3005 18 13 9 4 1 1 0 1
5005 15 11 8 2 2 1 0 0
6005 15 10 4 2 0 0 0 1
6008 12 8 3 2 0 0 0 0
8008 12 8 3 1 0 0 0 0
Nearzone

Nearzone

Large diffusion Small diffusion
(factory setting)
Large diffusion and small difusion

Table 1
Correction of the near zone (a0.2, b0.2)

Under- temperature Ti – Tr Maximum velocity m/s Mean velocity m/s Correction factor
  0.20 0.10 1.00
  0.25 0.12 0.80
-K3 0.30 0.15 0.70
  0.35 0.17 0.60
  0.40 0.20 0.50
  0.20 0.10 1.20
  0.25 0.12 1.00
-6K 0.30 0.15 0.80
  0.35 0.17 0.70
  0.40 0.20 0.60

Accessories

Wall duct CVAZ-1

Wall duct CVAZ-1

Size A
[mm]
B
[mm]
ØD1
[mm]
Weight
[kg]
3005 502 52 125 6.0
5005 502 52 160 6.0
6005 502 52 200 6.0
6008 502 82 250 6.5
8008 502 82 315 6.5

Ordering example
Ordering example

Lindab reserves the right to make changes without prior notice
2021-05-18

 

Documents / Resources

Lindab CVA Perforated Diffuser [pdf] Installation Guide
CVA Perforated Diffuser, CVA, Perforated Diffuser

References

Leave a comment

Your email address will not be published. Required fields are marked *