LINDAB

Lindab CCA Circular Air Diffuser

Lindab-CCA-Circular-Air-Diffuser

Description

Comdif CCA is a circular perforated displacement diffuser for freestanding installation. Behind the perforated front plate, CCA is equipped with individually adjustable nozzles, making it possible to alter the geometry of the near zone. The diffuser can be turned and has a circular duct connec-tion (MF measure), so the diffuser can be connected at the top or bottom. The diffuser is suitable for the supply of large volumes of moderately cooled air.

  • The diffuser is suitable for the supply of large volumes of air.
  • The geometry of the near zone can be adjusted using adjustable nozzles.
  • Plinths can be supplied as accessories.

Maintenance

The front plate can be removed from the diffuser, making it possible to clean the nozzles. The visible parts of the dif-fuser can be wiped with a damp cloth.

Ordering exampleLindab-CCA-Circular-Air-Diffuser-2

Order – accessories

Plinth: CCAZ – 2 – size

DimensionLindab-CCA-Circular-Air-Diffuser-1

 

Size

ØA

[mm]

ØD

[mm]

H

[mm]

Weight [kg]
1207 250 125 710 5,00
1607 300 160 710 7,50
2010 360 200 970 13,0
2510 400 250 970 18,0
3115 520 315 1490 35,0
4020 630 400 2010 58,0
5020 730 500 2010 78,0
6320 830 630 2010 106

Accessories

Can be supplied with plinth.

Materials and finish
  • Diffuser: Galvanised steel
  • Nozzles: Black plastic
  • Front plate: 1 mm galvanised steel
  • Standard finish: Powder-coated
  • Standard colour:  RAL 9003 or RAL 9010 – white

The diffuser is available in other colours. Please contact Lindab’s sales department for further information.

Technical data

The near zone is given at an under-temperature of -3 K to a maximum terminal velocity of 0.20 m/s. Conversion to other terminal velocities – see table 1, correc-tion of the near zone for -3 K and -6 K respectively.Lindab-CCA-Circular-Air-Diffuser-3

Sound effect level

Sound effect level LW [dB] = LWA + Kok

Centre frequency Hz

Size         63      125     250     500     1K      2K       4K       8K

1207 8 -1 1 1 -9 -17 -28 -40
1607 10 -1 1 1 -8 -17 -29 -33
2010 10 -1 3 0 -9 -17 -27 -40
2510 7 -1 3 0 -7 -18 -28 -41
3115 13 2 3 -1 -8 -17 -29 -27
4020 13 2 3 -1 -7 -16 -28 -43
5020 7 3 2 0 -6 -16 -19 -17
6320 7 3 2 0 -8 -16 -20 -17

Sound attenuation
Sound attenuation ΔL [dB] including end reflection.

Centre frequency Hz

Size         63      125     250     500     1K      2K       4K       8K

1207 19 14 5 3 2 1 2 1
1607 16 12 4 1 2 1 2 2
2010 12 8 4 2 3 2 2 2
2510 12 8 5 2 1 1 1 1
3115 11 8 3 2 1 1 2 2
4020 9 6 1 1 1 1 1 1
5020 6 4 1 1 1 1 1 1
6320 5 3 1 1 0 0 0 1

NearzoneLindab-CCA-Circular-Air-Diffuser-5

Table 1
Correction of the near zone (a0.2, b0.2)

Under- temperature

Ti-Tr

Maximum velocity

m/s

 

Mean velocity m/s

Correction factor
  0.20 0.10 1.00
  0.25 0.12 0.80
-3K 0.30 0.15 0.70
  0.35 0.17 0.60
  0.40 0.20 0.50
  0.20 0.10 1.20
  0.25 0.12 1.00
-6K 0.30 0.15 0.80
  0.35 0.17 0.70
  0.40 0.20 0.60

Lindab reserves the right to make changes without prior notice 2020-10-07

Documents / Resources

Lindab CCA Circular Air Diffuser [pdf] Instructions
CCA, Circular Air Diffuser, CCA Circular Air Diffuser, Air Diffuser, Diffuser, Perforated Diffuser Circular CCA, Perforated Diffuser

References

Leave a comment

Your email address will not be published. Required fields are marked *