RCD testing

6516 RCD Testing Clear Thinking with Kewtech

RCDs can be used as part of an installation design to enable the requirements of fault protection or additional protection to be met.

  • Earth fault loop impedance test should be done and verified as acceptable before RCDs are tested.
  • The test button on the RCD should pressed to ensure the RCD is working before testing.
  • BS 7671 is a minimum standard and only mandates that all RCDs are tested under an AC test current.
  • If the RCD tester being used has settings for additional types of RCDs it is advisable to carry the optional tests below.
  • RCDs should be tested on both the positive (0°) and negative (180°) half cycles of the AC supply with the highest tripping time recorded.

Required tests.

Max. tripping time
RCD type Instrument setting Applied current Non-delay S type or time-delay
All Type AC AC 1 x I ∇n 300 ms 500 ms

Optional tests.

RCD type Instrument setting Applied current Max. trippin6 time
Non-delay S type or time-delay
All Type AC IA x I An No trip No trip
All RCDs with
I An 5 30 mA
Type AC 5 x I An or 250 mA (if
declared by RCD manu.)
40 ms 150 ms
All RCDs with
I An > 30 mA
Type AC 5 x I An 40 ms 150 ms
Type A, F or B Type A
(after type
AC tests)
1/2 x I An
1 x I An
5 x I An
No trip
300 ms
40 ms
No trip
500 ms
150 ms
Type B Type B
(after type
AC & A tests )
2 x I An 300 ms 500 ms

NB: These values comply to RCDs designed to the Harmonised Standards: BS EN 61008, BS EN 61009, BS EN 60947-2 and using test equipment designed to BS EN 61557.

Scan to view video

6516 RCD Testing Clear Thinking with Kewtech - QR CODEhttps://www.youtube.com/watch?v=uIyZPEEttBQ6516 RCD Testing Clear Thinking with Kewtech

Kewtech ‘Clear Thinking’ diagrams are schematics to aid the understanding of electrical testing. Ensure proper safety procedures are taken before any testing.6516 RCD Testing Clear Thinking with Kewtech - TEST

Innovation and Support you can rely on
kewtechcorp.com

Documents / Resources

KEWTECH 6516 RCD Testing Clear Thinking with Kewtech [pdf] Instruction Manual
6516 RCD Testing Clear Thinking with Kewtech, 6516, RCD Testing Clear Thinking with Kewtech, Testing Clear Thinking with Kewtech, Thinking with Kewtech

References

Leave a comment

Your email address will not be published. Required fields are marked *