KE2 21994 Condensing Unit Control
Product Information
The KE2 Condensing Unit Control is a control unit designed for condensing units. It provides various features such as compressor and condenser fan control, alarm outputs, and network connectivity.
Parts List
- 21232 Basic Display with 18 Cable
- 21324 Snaptrack 11
- 21994 KE2 Condensing Unit Control
- 20202 Additional Literature (Refer to the provided link or QR code for more information)
General Layout
The control unit has multiple inputs and outputs, including:
- Pilot relay for compressor contactor
- Suction pressure input
- Discharge pressure input
- 0-10VDC output
- Alarm output*
- 2-speed condenser fan output*
- Variable speed condenser fan output* (Requires PN 21304 Solid
State Relay) - Suction temperature input
- Discharge temperature input
- Ambient temperature input
- Auxiliary input 1
- Auxiliary input 2
- Display connection for KE2 Basic Display
- Network connection via Ethernet
- Auxiliary board connection
Wiring Schematic
The control unit requires incoming power of 24 VAC. It should be wired according to the equipment manufacturer’s wiring diagram. The condenser fan motor may require an external contactor if its amp draw exceeds the rating of the onboard relay. The controller must be powered by a 24 VAC transformer (not provided) with a minimum rating of 40VA. The wiring should follow local wiring codes to ensure safety.
Sensor Installation
Sensors should be labeled according to their function. It is important to avoid running sensor cables and other low-voltage wiring next to high-voltage wiring to prevent electrical noise and interference with sensor readings. If necessary, use 18 AWG shielded twisted pair cables to extend sensor wires, with a maximum recommended total length of 100 ft.
Alarm output and condenser fan outputs may require additional components such as the PN 21304 Solid State Relay.
Product Usage Instructions
- Ensure that all recommended parts are available for installation, including the Basic Display, Snaptrack, and KE2 Condensing Unit Control.
- Refer to the provided link or QR code to access additional literature for detailed information on the product.
- Follow the general layout diagram to understand the various inputs and outputs of the control unit.
- Refer to the wiring schematic to correctly wire the control unit. Note that factory-installed units may have specific wiring diagrams provided by the equipment manufacturer.
- Make sure to provide 24 VAC power to the controller using a transformer with a minimum rating of 40VA.
- If necessary, use an external contactor for the compressor and/or condenser fan if their amp draw exceeds the rating of the onboard relay. Wire the onboard relay to switch power to the contactor coil.
- Install the control unit according to local wiring codes for safety.
- If using sensors, ensure they are labeled correctly and avoid running sensor cables next to high-voltage wiring to prevent interference. Use shielded twisted pair cables if extending sensor wires.
- Standardize the installation process for all units.
Parts List
The following parts are recommended for each install.
- 21994 KE2 Condensing Unit Control
- 21232 Basic Display with 18” Cable
- 21324 Snaptrack 11”
- 20201 Pressure Transducer – 0 to 150 psia, 10 ft. (Suction Pressure)
- 20202 Pressure Transducer – 0 to 500 psig, 10 ft. (Discharge Pressure)
- 20199 Temp Sensor 10 ft. – Black (Suction Temp)
- 21794 Temp Sensor 10 ft. – Blue (Ambient Temp)
- 21230 Temp Sensor 15 ft. – White (Discharge Temp)
- 20199
Temp Sensor 10 ft. – Black (Suction Temp) - 21794
Temp Sensor 10 ft. – Blue (Ambient Temp) - 21230
Temp Sensor 15 ft. – White (Discharge Temp)
Additional Literature
Please visit: https://ke2therm.com/product/ke2-condensing-unit-control and click the Link to Literature button.
Use this QR code:
General Layout
Wiring Schematic
NOTE: If the factory is installed refer to the equipment manufacturer’s wiring diagram.
CONTROLLER INCOMING POWER MUST BE 24 VAC.
Ladder Diagram
- The Compressor Contactor Relay must be used to pilot an external contactor for the compressor. If the amp draw of the condenser fan motor exceeds the rating of the onboard relay, an external contactor must also be used. The onboard relay should be wired to switch power to the contactor coil.
- 24 VAC must be provided to power the controller; a 24 VAC transformer is not included. The transformer must be 20 VA or greater, class B, and only provide power to a single KE2 Condensing Unit Control.
- Install in accordance with local wiring codes. KE2 Therm does not accept responsibility for incorrect or unsafe wiring.
Sensor Installation
Sensors should be labeled with their function. DO NOT run sensor cables and other low-voltage wiring next to high-voltage wiring, as it will create electrical noise and interfere with sensor readings. If necessary to extend the sensor wire, use 18 AWG shielded twisted pair cables. The maximum recommends total length is 100 ft.
We recommend standardizing all installations
- Black (SUC TMP) – Suction Temperature
- White (DIS TMP) – Discharge Temperature
- Blue (AMB TMP) – Ambient Temperature
NOTE:
The suction and ambient temperature sensors can be used interchangeably. The discharge sensor must use PN 21230 – High-Temperature Sensor.
Controller Setup
Intro Mode
When powered up for the first time or after a factory reset the controller enters Intro Mode. Intro Mode consists of three initial startup setpoints that must be configured before refrigeration can begin.
for KE2 Condensing Unit Control, then
for refrigerant will be displayed. Press
several times until the correct refrigerant for the system is displayed, then press and hold
.
By default, the setpoint will be displayed next. This sets the initial cut-out pressure. Press
to the appropriate default then press and hold ENTER
.
404 R-404A 55A R-455A 45C R-454C 54A R-454A 449 R-449A 448 R-448A 744 R-744 410 R-410A 438 R-438A 290 R-290 717 R-717 r22 R-22 134 R-134A 40C R-407C 40A R-407A 507 R-507 The above default cut-out pressure is a starting point only. ALWAYS refer to the condensing unit manufacturer’s recommended low-pressure cut-out setting for the lowest space and ambient temperature the unit will experience. Adjust controller low-pressure cut-out setpoint as necessary.
for KE2 SmartAccess will be displayed next. KE2 SmartAccess allows you to easily view and modify your controllers online. Press
to
for enabled or
disabled, then press and hold ENTER
.
NOTE:
Enabling KE2 SmartAccess in Intro Mode will also enable DHCP client mode and allow the IP address of the controller to change from the factory default. Enable only if connecting directly to the local network without going through a KE2-Edge Manager.
Once Intro Mode is complete, the controller will begin to control the condensing unit. Review any necessary or desired additional setpoints and confirm the proper operation of the system.
INDICATOR LIGHTS
- RED LIGHT Critical alarm – a system not running, running may damage the system.
- YELLOW LIGHT Non-critical alarm – system running with potential issues.
- GREEN LIGHT Calling for refrigeration, compressor contactor relay energized.
- GREEN FLASHING Waiting on min. off timer to energize the compressor contactor relay.
- Access the setpoint menu by pressing and holding ENTER until rFG (refrigerant) displays on the screen.
- Press
or
to scroll through available setpoints.
- Press
to view the current setting.
- Press
or
to change the setpoint.
- Press
momentarily to move between digits to accelerate the changes.
- Press and hold
to save setpoint changes.
- Press BACK to escape.
Specifications
Input Voltage: | 24 VAC |
Ambient Temp: | -40°F to 140°F (-40°C to 60°C) |
Operating Temp: | -40°F to 140°F (-40°C to 60°C) |
Inputs: | (3) Temperature: Suction, Discharge, Ambient |
(2) Temp/Digital Input: Aux 1, Aux2 | |
(2) Pressure: Suction, Discharge | |
Outputs: | (1) Relay 2.5A, 240VAC Pilot Duty: Compressor Contactor |
(1) Relay 12A, 240VAC Inductive: Condenser Fan | |
(1) 0-10 VDC: Variable Speed Condenser Fan, 2 Speed Condenser Fan*, Alarm* | |
Communication: | RS-485 (to auxiliary boards only) |
TCP/IP, RESTful API | |
BACnet/IP** |
- Requires PN 21304 Solid State Relay
- Requires a KE2-EM w/ BACnet license (does not support BBMD)
Additional Part Numbers
Part # | Description |
22060 | Replacement Condenser Fan Relay |
21902 | KE2-Edge Manager Plus (Wi-Fi, Datalogging & more) |
20200 | Temp Sensor, 40 ft. – Black |
21066 | Temp Sensors – Set of 3– Blue, Yellow, Green, 40 ft. |
20204 | Pressure Transducer – 0 to 150 psia, 40 ft. (suction pressure) |
20712 | Pressure Transducer – 0 to 500 psig, 40 ft. (discharge pressure) |
21872 | Pressure Transducer – 0 to 750 psig, 10 ft. (R-744 suction pressure, R-410A discharge pressure) |
21873 | Pressure Transducer – 0 to 750 psig, 40 ft. (R-744 suction pressure, R-410A discharge pressure) |
21671 | Pressure Transducer – 0 to 1,000 psig, 10 ft. (R-744 discharge pressure) |
21672 | Pressure Transducer – 0 to 1,000 psig, 40 ft. (R-744 discharge pressure) |
20208 | Pressure Transducer – 0 to 300 psig, 10 ft. (R-410A suction pressure) |
20711 | Pressure Transducer – 0 to 300 psig, 40 ft. (R-410A suction pressure) |
Dimensions
Inches (millimeters)
© Copyright 2023 KE2 Therm Solutions, Inc., Washington, Missouri 63090.
KE2 Therm Solutions
- 12 Chamber Drive Washington, MO 63090
- 1.888.337.3358
- www.ke2therm.com.
Documents / Resources
![]() |
KE2 21994 Condensing Unit Control [pdf] User Guide 21994, 21232, 21324, 21994 Condensing Unit Control, Condensing Unit Control, Unit Control |