INSTRUCTIONS MANUAL – V1.2x

INTRODUCTION

The N1020 is a small yet powerful temperature controller. It accepts most of the temperature sensors used in industry and its 2 outputs can be configured independently as control or alarm output. It also embeds an auto-adaptative PID control algorithm for best system performance.
Configuration can be performed either directly on the controller or via the USB interface once QuickTune software has been installed on the computer to be used. Once connected to USB, the device will be recognized as a serial communication (COM) port operating with Modbus RTU protocol.
Through the USB interface, even if disconnected from the power supply, the configuration performed in a piece of equipment can be saved in a file and repeated in other pieces of equipment that require the same configuration.
It is important that the users read carefully this manual before using the controller. Verify if the release of this manual matches the instrument version (the firmware version is shown when the controller is energized). The N1020 main characteristics are:

  • LED Display, red, high brightness;
  • Multi-sensor universal input: : thermocouples, Pt100, and 50 mV;
  • Self-tuning PID parameters;
  • 2 outputs: 1 relay and 1 logical pulse for SSR;
  • Output functions: Control, Alarm1 and Alarm 2;
  • 8 distinct alarm functions;
  • Programmable timer;
  • Function key for enabling/disabling outputs, resetting the timer or turning the timer ON/OFF;
  • Programmable soft-start;
  • Rate function;
  • Password for parameters protection;
  • The capability of restoring factory calibration.

USB INTERFACE

The USB interface is used to CONFIGURE, MONITOR or UPDATE the controller FIRMWARE. The user should use QuickTune software, which offers features to create, view, save and open settings from the device or files on the computer. The tool for saving and opening configurations in files allows the user to transfer settings between devices and perform backup copies. For specific models, QuickTune allows updating the firmware (internal software) of the controller via the USB interface. For MONITORING  purposes, the user can use any supervisory software (SCADA) or laboratory software that supports the MODBUS RTU communication over a serial communication port. When connected to a computer’s USB, the controller is recognized as a conventional serial port (COM x).
The user must use QuickTune software or consult the DEVICE MANAGER on the Windows Control Panel to identify the COM port assigned to the controller.
The user should consult the mapping of the MODBUS memory in the controller’s communication manual and the documentation of the supervision software to start the MONITORING process.

Follow the procedure below to use the USB communication of the device:

  1. Download QuickTime software from our website and install it on the computer. The USB drivers necessary for operating the communication will be installed with the software.
  2. Connect the USB cable between the device and the computer. The controller does not have to be connected to a power supply. The USB will provide enough power to operate the communication (other device functions may not operate).
  3. Run the QuickTune software, configure the communication and start the device recognition.
warning 2Electric Warning Icon The USB interface IS NOT SEPARATE from the signal input (PV) or the controller’s digital inputs and outputs. It is intended for temporary use during CONFIGURATION and MONITORING periods. For the safety of people and equipment, it must only be used when the piece of equipment is completely disconnected from the input/output signals. Using the USB in any other type of connection is possible but requires a careful analysis by the person responsible for installing it. When MONITORING for long periods of time and with connected inputs and outputs, we recommend using the RS485 interface, which is available or optional in most of our products.

INSTALLATION / CONNECTIONS

The controller must be fastened on a panel, following the sequence of steps described below:

  • Prepare a panel cut-out according to Specifications;
  • Remove the mounting clamps from the controller;
  • Insert the controller into the panel cut-out;
  • Slide the mounting clamp from the rear to a firm grip at the panel.

RECOMMENDATIONS FOR THE INSTALLATION

  • All electrical connections are made to the screw terminals at the rear of the controller. They accept wire sizes from 0.5 to 1.5 mm² (16 to 22 AWG). The terminals should be tightened to a torque of 0.4 Nm (3.5 lb in).
  • To minimize the pick-up of electrical noise, the low voltage DC connections and the sensor input wiring should be routed away from high-current power conductors. If this is impractical, use shielded cables. In general, keep cable lengths to a minimum.
  • All electronic instruments must be powered by a clean mains supply, proper for instrumentation.
  • It is strongly recommended to apply RC’S FILTERS (noise suppressor) to contactor coils, solenoids, etc.
  • In any application, it is essential to consider what can happen when any part of the system fails. The controller features by themselves can’t assure total protection.

ELECTRICAL CONNECTIONS

The controller’s complete set of features is drawn in Fig. 01. The features loaded in a particular unit are shown on its label:

itsensor N1020 Yet Powerful Temperature Controller - fig 1

Removal of the Controller Back Connector 

itsensor N1020 Yet Powerful Temperature Controller - fig 2

FEATURES

INPUT TYPE SELECTION
Select the input type (in parameter “) from Table 01 below.

TYPE CODE RANGE OF MEASUREMENT
J itsensor N1020 Yet Powerful Temperature Controller - fig 3 Range: -110 to 950 ºC (-166 to 1742 ºF)
K Range: -150 to 1370 ºC (-238 to 2498 ºF)
T Range: -160 to 400 ºC (-256 to 752 ºF)
N Range: -270 to 1300 ºC (-454 to 2372 ºF)
R Range: -50 to 1760 ºC (-58 to 3200 ºF)
S Range: -50 to 1760 ºC (-58 to 3200 ºF)
B Range: 400 to 1800 ºC (752 to 3272 ºF)
E Range: -90 to 730 ºC (-130 to 1346 ºF)
Pt100 Range: -200 to 850 ºC (-328 to 1562 ºF)
0 to 50 mV Linear. Programmable indication -1999 to 9999

Table 01 – Input Types

OUTPUTS
The N1020 offers two output channels, user configurable as Control output, Alarm 1 output or Alarm 2 output.
OUT1 – Logical pulse, 5 Vdc / 25 mA, available at terminals 4 and 5.
OUT2 – Relay SPST-NA, 1.5 A / 240 Vac, available at terminals 6 and 7.
Note: The outputs can be configured independently from each other, for example, both can be control outputs at the same time.
CONTROL OUTPUT
The control strategy can be configured as ON / OFF or PID.

ALARM OUTPUT
These two alarms are available in the N1020. The alarms can be assigned to either output, logical or relay. The alarm functions are described below.

ALARM FUNCTIONS
The alarms can be configured to operate with nine different functions, as shown in Table 02.

itsensor N1020 Yet Powerful Temperature Controller - fig 4 Alarms turned itsensor N1020 Yet Powerful Temperature Controller - fig 4.
itsensor N1020 Yet Powerful Temperature Controller - fig 5 The alarm of Absolute Minimum Value. Triggers when the value of measured PV is below the value defined for alarm Setpoint (SPA1 or SPA2).
itsensor N1020 Yet Powerful Temperature Controller - fig 6
itsensor N1020 Yet Powerful Temperature Controller - fig 7 The alarm of Valor Absolute Maximum Value. Triggers when the value of measured PV is above the value defined for alarm Setpoint.
itsensor N1020 Yet Powerful Temperature Controller - fig 8
itsensor N1020 Yet Powerful Temperature Controller - fig 9 The alarm of Differential Value. In this function, the parameters  represent the deviation of PV in relation to the SP of CONTROL.
itsensor N1020 Yet Powerful Temperature Controller - fig 10
SPA1 positive SPA1 negative
itsensor N1020 Yet Powerful Temperature Controller - fig 11 The alarm of Minimum Differential Value. It triggers when the value of PV is below the defined point by (using Alarm 1 as an example):
itsensor N1020 Yet Powerful Temperature Controller - fig 12
SPA1 positive SPA1 negative
itsensor N1020 Yet Powerful Temperature Controller - fig 13 Alarm of Valor Maximum Differential Value. Triggers when the value of PV is above the defined point by (using Alarm 1 as example):
itsensor N1020 Yet Powerful Temperature Controller - fig 14
SPA1 positive SPA1 negative
itsensor N1020 Yet Powerful Temperature Controller - fig 15 Timer ON alarm. Sets alarm output ON when the timer is running.
itsensor N1020 Yet Powerful Temperature Controller - fig 16 Timer end. Configures the alarm to actuate when the timer expires.
itsensor N1020 Yet Powerful Temperature Controller - fig 17 Sensor Break Alarm. Activated when the input signal of PV is interrupted, out of the range or when Pt100 in short-circuit.

Table 02 – Alarm functions

The above examples also apply to Alarm 2.
Important note: Alarms configured with the itsensor N1020 Yet Powerful Temperature Controller - fig 18and itsensor N1020 Yet Powerful Temperature Controller - fig 19functions also trigger their associated output when a sensor fault is identified and signaled by the controller. A relay output, for example, configured to act as a High Alarm (itsensor N1020 Yet Powerful Temperature Controller - fig 20), will operate when the SPAL value is exceeded and also when the sensor connected to the controller input is broken.

Alarms Timer Modes (Temporization)
The controller alarms can be configured to perform 4 timer modes:

MODE itsensor N1020 Yet Powerful Temperature Controller - fig 21 itsensor N1020 Yet Powerful Temperature Controller - fig 22 ACTION
Normal Operation 0 0 itsensor N1020 Yet Powerful Temperature Controller - fig 23
Activation for a defined time 1 to 6500 s 0 itsensor N1020 Yet Powerful Temperature Controller - fig 24
Activation with delay 0 1 to 6500 s itsensor N1020 Yet Powerful Temperature Controller - fig 25
Intermittent Activation 1 to 6500 s 1 to 6500 s itsensor N1020 Yet Powerful Temperature Controller - fig 26

Table 03 – Temporization Functions for the Alarms

The signs associated to the alarms will light when the alarm condition is recognized, not following the actual state of the output, which may be temporarily OFF because of the temporization.

Initial Blocking of Alarm
The initial blocking option inhibits the alarm from being recognized if an alarm condition is present when the controller is first energized (or after a transition from run YES →NO). The alarm will be enabled only after the occurrence of a nonalarm condition followed by a new occurrence for the alarm.

The initial blocking is useful, for instance, when one of the alarms is configured as a minimum value alarm, causing the activation of the alarm soon upon the process start-up, an occurrence that may be undesirable.
The initial blocking is disabled for the sensor break alarm function.

RAMP AND SOAK FUNCTION
Allows reaching the SP value gradually. The value of SP is increased gradually from an initial value (PV value) until it reaches the set value. The itsensor N1020 Yet Powerful Temperature Controller - fig 27parameter sets this increase for SP in degrees per minute. The Ramp function will work when turning on the controller, enabling control (RUN = YES) or when the SP value is changed. A value equal to zero (0) in the rate parameter disables the Ramp function.

TIMER FUNCTION
The N1020 embeds a timer function (decreasing) for applications that require a particular process duration.
Once defined the time interval in the itsensor N1020 Yet Powerful Temperature Controller - fig 29  parameter, the timer will START when:

  • When PV reaches the temperature programmed in the SP parameter.
  • When enabling the control (RUN = YES).
  • By pressing the F key when configured to Timer reset mode (the timer is reloaded with the itsensor N1020 Yet Powerful Temperature Controller - fig 29 parameter and restarts counting).
  • Pressing the F key in ON/OFF mode stops the timer counting; pressing it again, resumes the counting.
    When the timer expires, the two possible actions can be:
  • Disables de control (RUN→ NO) or
  • Activate the alarm.

FUNCTIONS FOR THE F KEY
The F key on the frontal keypad is meant for special commands, as follows:

  • Enable outputs (identically to the RUN parameter).
  • Timer reset: – reloads the timer and initiates a new time counting.
  • Timer ON/OFF. The timer holds or resumes counting each time the F key is pressed.
    Keeping the F key pressed for 3 seconds resets the timer (reloads the timer to the value set in itsensor N1020 Yet Powerful Temperature Controller - fig 29), initiating a new time counting.

Note: when the F key is configured as RUN = YES/NO (RUN =  the controller outputs are born disabled after powers up.

SOFT-START
The Soft-start function is generally used in processes that require slow start-up, where the instantaneous application of 100% of the available power to the load may cause damage to parts of the system.
In order to disable this function, the soft-start parameter must be configured with 0 (zero).

OFFSET
Allows fine trimming the PV indication to compensate for sensor errors. Default value: zero.
SERIAL COMMUNICATION
For full documentation download the Registers Table N1020 for Serial Communication on our website – www.novusautomation.com.

itsensor N1020 Yet Powerful Temperature Controller - fig 31

Fig. 03 – Serial Communications Connections
The table below helps you connect the RS485 communication interface connectors:

D1 D D + B Bidirectional data line
D0 D D – A Inverted bidirectional data line
C The optional connection improves the performance of the communication.
GND

OPERATION

The controller’s front panel, with its parts, can be seen in Fig. 04:

itsensor N1020 Yet Powerful Temperature Controller - fig 32

Display: Displays the current value of PV. When configuring a parameter, the display alternates between the parameter prompt and its value (the parameter value is shown with a light blinking to differentiate it from the parameter prompt).

The display contains also the signs AT, OUT, RUN ALM, and COM:
AT Indicator: Stays ON while the controller is in the tuning process.
OUT Indicator: For relay or pulse control output; it reflects the actual state of the output.
RUN Indicator: Indicates that the controller is active, with the control output and alarms enabled. (RUN=YES).
ALM Indicator: Signalize the occurrence of an alarm condition. It lights when either alarm is active.
COM Indicator: Flashes when there is RS485 activity.

P Key: Used to walk through the menu parameters.
itsensor N1020 Yet Powerful Temperature Controller - fig 33 Increment key anditsensor N1020 Yet Powerful Temperature Controller - fig 34 Decrement key: allow altering the values of the parameters.
F Key: accesses special functions: RUN (toggles YES/NO) and the two modes of timer control.

STARTUP
When the controller is powered up, it displays its firmware version for 3 seconds, after which the controller starts normal operation. The value of PV is then displayed and the outputs are enabled. In order for the controller to operate properly in a process, its parameters need to be configured first, such that it can perform accordingly to the system requirements. The user must be aware of the importance of each parameter and for each one determine a valid condition.
The parameters are grouped in levels according to their functionality and operation easiness. The 5 levels of parameters are:

  1. – Operation Level
  2. – Tuning Level
  3. – Alarms Level
  4. – Configuration Level
  5. – Calibration Level

The P key is used for accessing the parameters within a level. Keeping the P key pressed, at every 2 seconds the controller jumps to the next level of parameters, showing the first parameter of each level:

itsensor N1020 Yet Powerful Temperature Controller - fig 35

To enter a particular level, simply release the P key when the first parameter in that level is displayed. To walk through the parameters in a level, press the P key with short strokes. The display alternates the presentation of the parameter prompt and its value. The parameter value is displayed with a light blinking to differentiate it from the  arameter prompt.
Depending on the level of parameter protection adopted, the parameter PASS precedes the first parameter in the level where the protection becomes active. See section CONFIGURATION PROTECTION.
At the end of this manual, a table with the complete sequence of levels and parameters is presented.
Note: It is recommended to disable/suspend the control () whenever it is necessary to change the device settings.

DESCRIPTION OF THE PARAMETERS

OPERATION LEVEL

PV PV indication
Timer Timer remaining time. Only shown when the Timer
function is in use. (itsensor N1020 Yet Powerful Temperature Controller - fig 36) (HH:MM).
itsensor N1020 Yet Powerful Temperature Controller - fig 37 Control SP adjustment.
itsensor N1020 Yet Powerful Temperature Controller - fig 38 Sets the Timer, 00:00 to 99:59 (HH:MM).
itsensor N1020 Yet Powerful Temperature Controller - fig 39 RATE OF PV RISE: from the current PV to the SP value.
In degrees/minute.
itsensor N1020 Yet Powerful Temperature Controller - fig 41 Enables control outputs and alarms.
itsensor N1020 Yet Powerful Temperature Controller - fig 88– Outputs enabled.
– Outputs disabled.
-“F” key assumes control over the RUN command.

TUNING LEVEL

itsensor N1020 Yet Powerful Temperature Controller - fig43Auto-tune Defines the control strategy to be taken:
itsensor N1020 Yet Powerful Temperature Controller - fig 44 – Turned off. (no PID tuning)
– Fast automatic tuning.
– More accurate automatic tuning.
–  Precise + auto-adaptative tuning
– Forces one new precise automatic
precise + auto-adaptative tuning.
– Forces one new precise automatic +
– adaptative tuning when Run = YES  or controller is turned on.
Refer to the “DETERMINING PID PARAMETERS” section for further details on tuning strategies.
itsensor N1020 Yet Powerful Temperature Controller - fig 45Proportional Band Proportional Band – Value of the term P of the control mode PID, in percentage of the maximum span of the
input type. Adjust of between 0 and 500.0 %. Select zero for ON/OFF control.
itsensor N1020 Yet Powerful Temperature Controller - fig 46Integral Rate Integral Rate – Value of the term I of the PID algorithm, in repetitions per minute (Reset). Adjustable between 0 and 99.99.
Displayed only if proportional band ≠ 0.
itsensor N1020 Yet Powerful Temperature Controller - fig 47Derivative Time Derivative Time – Value of the term D of the control mode PID, in seconds. Adjustable between 0 and 300.0 seconds.
Displayed only if proportional band ≠ 0.
itsensor N1020 Yet Powerful Temperature Controller - fig 48Level Time Pulse Width Modulation (PWM) period in seconds. Adjustable between 0.5 and 100.0 seconds.
Displayed only if proportional band ≠ 0.
itsensor N1020 Yet Powerful Temperature Controller - fig 49Hysteresis Control Hysteresis (in engineering. units): This parameter is only shown for ON / OFF control (Pb=0). Adjustable between 0 and the measurement input type span.
itsensor N1020 Yet Powerful Temperature Controller - fig 51Action Control Action: For Auto Mode only.
itsensor N1020 Yet Powerful Temperature Controller - fig 52 Control with Reverse Action. Appropriate heating. Turns control output on when PV is below SP.
itsensor N1020 Yet Powerful Temperature Controller - fig 53 Control with Direct Action. Appropriate for cooling. Turns control output on when PV is
above SP.
itsensor N1020 Yet Powerful Temperature Controller - fig 54Softstart SoftStart Function –: Time in seconds during which the controller limits the MV value progressively from 0 to 100 %. It is enabled at power up or when the control output is activated. If in doubt set zero (zero value disables the Soft start function).
itsensor N1020 Yet Powerful Temperature Controller - fig 55 Outputs 1 and 2 function:
itsensor N1020 Yet Powerful Temperature Controller - fig 56not used;
control output.
Alarm 1.
Alarm 2.
Alarm 1 AND Alarm 2 at the same time.

ALARMS LEVEL 

itsensor N1020 Yet Powerful Temperature Controller - fig 57Function Alarm Functions of Alarms. Defines the functions for the alarms among the options of the Table 02.
itsensor N1020 Yet Powerful Temperature Controller - fig 58 Alarm Setpoint: Tripping points for alarms 1 and 2. Value that defines the point of activation for the programmed alarms with the functions itsensor N1020 Yet Powerful Temperature Controller - fig 59
For the alarms configured with Differential type functions, this parameter defines deviation (band).  Not used for the other alarm functions.
itsensor N1020 Yet Powerful Temperature Controller - fig 60Blocking Alarm Block Alarm 1 and 2: This function blocks the alarms when the controller is energized.
itsensor N1020 Yet Powerful Temperature Controller - fig 61– enables initial blocking
– inhibits initial blocking
itsensor N1020 Yet Powerful Temperature Controller - fig 62Hysteresis of Alarm Alarm Hysteresis. Defines the difference between the value of PV at which the alarm is triggered and the value
at which it is turned off.
itsensor N1020 Yet Powerful Temperature Controller - fig44 Defines the temporization time , for the alarms.  In seconds.
itsensor N1020 Yet Powerful Temperature Controller - fig 66 Defines the temporization time , for the alarms. In seconds.
itsensor N1020 Yet Powerful Temperature Controller - fig 67 Allows you to identify the occurrence of alarm conditions
by flashing the PV indication on the display screen.
itsensor N1020 Yet Powerful Temperature Controller - fig 68– Enables alarm signaling flashing PV
– Disables alarm signaling flashing PV

CONFIGURATION LEVEL 

itsensor N1020 Yet Powerful Temperature Controller - fig 69 Input Type: Selects the input signal type to be connected to the process variable input. Refer to Table 1 for the available options.
itsensor N1020 Yet Powerful Temperature Controller - fig 70 Digital Input Filter – Used to improve the stability of the measured signal (PV). Adjustable between 0 and 20. In 0 (zero) it means filter turned off and 20 means maximum filter. The higher the filter value, the slower is the response of the measured value.
itsensor N1020 Yet Powerful Temperature Controller - fig 71 Selects the decimal point position to be viewed in both PV and SP.
itsensor N1020 Yet Powerful Temperature Controller - fig 72 Unit. Temperature indication in °C or °F. Not shown for linear inputs.
itsensor N1020 Yet Powerful Temperature Controller - fig 73 Sensor Offset: Offset value to be added to the PV reading to compensate sensor error.
Default value: zero.
itsensor N1020 Yet Powerful Temperature Controller - fig 74 Defines the SP lower limit.
To 0-50 mV input type sets the lower range for SP and PV indication.
itsensor N1020 Yet Powerful Temperature Controller - fig 75 Defines the SP upper limit.
To 0-50 mV input type sets the upper range for SP and PV indication.
itsensor N1020 Yet Powerful Temperature Controller - fig 76 Time. Adjustment. 00:00 to 99:59 (HH: MM). (same function as the one presented in the operation level)
itsensor N1020 Yet Powerful Temperature Controller - fig 77 Shows a copy of the Timer parameter in the operating level.
itsensor N1020 Yet Powerful Temperature Controller - fig 78 – enables itsensor N1020 Yet Powerful Temperature Controller - fig 79 parameters to the operating level
– doesn’t show the itsensor N1020 Yet Powerful Temperature Controller - fig 79 parameter in the operating level
itsensor N1020 Yet Powerful Temperature Controller - fig 80 Defines the mode for starting the Timer.
itsensor N1020 Yet Powerful Temperature Controller - fig 81– when PV reaches the temperature value in SP
– when RUN →YES
– “F” key (reset the timer)
– “F” key (start/stop the timer).
itsensor N1020 Yet Powerful Temperature Controller - fig 82Timer End Control Off Control behavior when the timer expires:
itsensor N1020 Yet Powerful Temperature Controller - fig 83– disables the outputs (RUN = NO).
– outputs continue to operate.
itsensor N1020 Yet Powerful Temperature Controller - fig 84 Ramp function. Establishes the rate of increase of PV, in degrees/minute.
Same itsensor N1020 Yet Powerful Temperature Controller - fig 84function as showed in the operating level.
itsensor N1020 Yet Powerful Temperature Controller - fig 84Rate Enable Shows a copy of the Rate parameter in the operating level.
itsensor N1020 Yet Powerful Temperature Controller - fig 86– enables the itsensor N1020 Yet Powerful Temperature Controller - fig 84 parameter to the operating level.
– doesn’t show the itsensor N1020 Yet Powerful Temperature Controller - fig 84 parameter in the operating level
itsensor N1020 Yet Powerful Temperature Controller - fig 87 Enables the control and alarm outputs.

itsensor N1020 Yet Powerful Temperature Controller - fig 88– outputs enabled.
– outputs disabled.
–  outputs enabled/disabled function assigned to the F key.
Same itsensor N1020 Yet Powerful Temperature Controller - fig 87 function as shown in the operating level.

itsensor N1020 Yet Powerful Temperature Controller - fig 85Run Enable Shows a copy of the itsensor N1020 Yet Powerful Temperature Controller - fig 90 parameter in the operating level.
itsensor N1020 Yet Powerful Temperature Controller - fig 91– enables the itsensor N1020 Yet Powerful Temperature Controller - fig 90 parameter in the operating level
– doesn’t show the itsensor N1020 Yet Powerful Temperature Controller - fig 90 parameter in the operating level
itsensor N1020 Yet Powerful Temperature Controller - fig 93Baud Rate Baud Rate serial communication. In kbps, with the following speeds available
1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6 and 115.2
itsensor N1020 Yet Powerful Temperature Controller - fig 94Parity Parity of the serial communication.
itsensor N1020 Yet Powerful Temperature Controller - fig 95Without parity
Eve parity
 Odd parity
itsensor N1020 Yet Powerful Temperature Controller - fig 96 Communication Address. Identifies the controller in the network. The possible address numbers are from 1 to 247.

CALIBRATION LEVEL
All of the input and output types are calibrated in the factory. If a recalibration is required, this should be carried out by a experienced personnel. If this level is accidentally accessed, pass through all the parameters without pressing the itsensor N1020 Yet Powerful Temperature Controller - icon 2or itsensor N1020 Yet Powerful Temperature Controller - icon 1 keys

itsensor N1020 Yet Powerful Temperature Controller - fig 97Password Input of the Access Password.
This parameter is presented before the protected levels. See item Protection of Configuration.
itsensor N1020 Yet Powerful Temperature Controller - fig 98Calibration? Enables or disables instrument calibration by the user,
YES: shows calibration parameters
No: Hides the calibration parameters
itsensor N1020 Yet Powerful Temperature Controller - fig 99Input Low Calibration See section MAINTENANCE / Input Calibration.
Enter the value corresponding to the low scale signal applied to the analog input.
Only showed if itsensor N1020 Yet Powerful Temperature Controller - fig 100= YES
itsensor N1020 Yet Powerful Temperature Controller - fig 101Input High Calibration See section MAINTENANCE / Input Calibration.
Enter the value corresponding to the full-scale signal applied to the analog input.
Only shown if  itsensor N1020 Yet Powerful Temperature Controller - fig 100= YES
itsensor N1020 Yet Powerful Temperature Controller - fig 103Restore Restores the factory calibration for all inputs and outputs, disregarding modifications carried out by the user.
itsensor N1020 Yet Powerful Temperature Controller - fig 104Output Low Limit Lower limit for the control output – Minimum percentage value assumed by the control output when in automatic mode and in PID. Typically configured with 0 %. Default value: 0 %
itsensor N1020 Yet Powerful Temperature Controller - fig 105Output High Limit Upper limit for the control output – Maximum percentage for the control output when in automatic mode and in PID. Typically configured with 100 %. Default value: 100 %.
itsensor N1020 Yet Powerful Temperature Controller - fig 106Cold Junction Cold junction temperature controller.
itsensor N1020 Yet Powerful Temperature Controller - fig 107Password Change Allows defining a new access password, always different from zero.
itsensor N1020 Yet Powerful Temperature Controller - fig 108Protection Sets up the Level of Protection. See Table 04.
itsensor N1020 Yet Powerful Temperature Controller - fig 109Frequency Mains frequency. This parameter is important for proper noise filtering.
itsensor N1020 Yet Powerful Temperature Controller - fig 110 Shows the four first digits of the controller serial number.
itsensor N1020 Yet Powerful Temperature Controller - fig 111 Shows the four last digits of the controller serial number.

CONFIGURATION PROTECTION

The controller provides means for protecting the parameters configurations, not allowing modifications to the values of the parameters, and avoiding tampering or improper manipulation. The parameter Protection (itsensor N1020 Yet Powerful Temperature Controller - fig 112), in the Calibration level, determines the protection strategy, limiting the access to particular levels, as shown by Table 04.

Protection Level Protection Levels
1 Only the Calibration level is protected.
2 Calibration and Tuning levels.
3 Calibration, Tuning and Alarms levels
4 Calibration, Tuning, Alarms and Configuration levels
5 Calibration, Tuning, Alarms, Configuration levels

Table 04 – Levels of Protection for the Configuration

ACCESS PASSWORD
The protected levels, when accessed, request the user to provide the Access Password for granting permission to change the configuration of the parameters on these levels.
The prompt itsensor N1020 Yet Powerful Temperature Controller - fig 113 precedes the parameters on the protected levels. If no password is entered, the parameters of the protected levels can only be visualized.
The Access Password is defined by the user in the parameter Password Change (itsensor N1020 Yet Powerful Temperature Controller - fig 114), present in the Calibration Level. The factory default for the password code is 1111.

PROTECTION ACCESS PASSWORD
The protection system built into the controller blocks for 10 minutes the access to protected parameters after 5 consecutive frustrated attempts of guessing the correct password.

MASTER PASSWORD
The Master Password is intended for allowing the user to define a new password in the event of it being forgotten. The Master Password doesn’t grant access to all parameters, only to the Password Change parameter (itsensor N1020 Yet Powerful Temperature Controller - fig 114). After defining the new password, the protected parameters may be accessed (and modified) using this new password.
The master password is made up by the last three digits of the serial number of the controller added to the number 9000.
As an example, for the equipment with serial number 07154321, the master password is 9 3 2 1.

DETERMINATION OF PID PARAMETERS

The determination (or tuning) of the PID control parameters in the controller can be carried out in an automatic way and in auto-adaptative mode. The automatic tuning is always initiated under the request of the operator, while the auto-adaptive tuning is initiated by the controller itself whenever the control performance becomes poor.
Automatic Tuning: In the beginning of the automatic tuning the controller has the same behavior of an ON/OFF controller, applying minimum and maximum performance to the process. Along the tuning process, the controller’s performance is refined until its conclusion, already under optimized PID control. It begins immediately after the selection of the options FAST, FULL, RSLF or TGHT, defined by the operator in the parameter ATUN.
Auto-adaptative Tuning: Is initiated by the controller whenever the control performance is worse than the one found after the previous tuning. In order to activate the performance supervision and auto adaptative tuning, the parameter ATUN must be adjusted for SELF, RSLF or TGHT. The controller’s behavior during the auto-adaptative tuning will depend on the worsening of the present performance. If the maladjustment is small, the tuning is practically imperceptible for the user. If the maladjustment is big, the auto-adaptive tuning is similar to the method of automatic tuning, applying minimum and maximum performance to the process in ON/OFF control.

itsensor N1020 Yet Powerful Temperature Controller - fig 115

itsensor N1020 Yet Powerful Temperature Controller - fig 116

The operator main selects through the ATUN parameter, the desired tuning type among the following options:

  • : The controller does not carry through automatic tuning or auto-adaptative tuning. The PID parameters will not be automatically determined nor optimized by the controller.
  • itsensor N1020 Yet Powerful Temperature Controller - fig 117 The controller will process automatic tuning one single time, returning to the OFF mode after finishing. The tuning in this mode is completed in less time, but not as precise as in the FULL mode.
  • itsensor N1020 Yet Powerful Temperature Controller - fig 118 The same as the FAST mode, but the tuning is more precise and slower, resulting in better performance of the P.I.D.
  • itsensor N1020 Yet Powerful Temperature Controller - fig 119 The performance of the process is monitored and the auto-adaptative tuning is automatically initiated by the controller whenever the performance is poorer.
    After a tuning level, the controller starts collecting data from the process for determining the performance benchmark that will allow evaluation the need for future tunings.  This phase is proportional to the process response time and is signaled by the flashing TUNE indication on the display. It is recommended not to turn the controller off or change the SP during this learning period. It is recommended not to turn the controller off or change the SP during this learning period.
  • itsensor N1020 Yet Powerful Temperature Controller - fig 120 SF: Accomplishes the automatic tuning and returns into the SELF mode. Typically used to force an immediate automatic tuning of a controller that was operating in the SELF mode, returning to this mode at the end.
  • itsensor N1020 Yet Powerful Temperature Controller - fig 121 TGHT: Similar to the SELF mode, but in addition to auto-adaptative tuning, it also executes the automatic tuning whenever the controller is set in RUN=YES or when the controller is turned on.

Whenever the parameter ATUN is altered by the operator into a value different from OFF, an automatic tuning is immediately initiated by the controller (if the controller is not in RUN=YES, the tuning will begin when it passes into this condition). The accomplishment of this automatic tuning is essential for the correct operation of the auto-adaptative tuning. The methods of automatic tuning and auto-adaptative tuning are appropriate for most of the industrial processes. However, there may be processes or even specific situations where the methods are not capable to determine the controller’s parameters in a satisfactory way, resulting in undesired oscillations or even taking the process to extreme conditions. The oscillations themselves imposed by the tuning methods may be intolerable for certain processes. These possible undesirable effects must be considered before beginning the controller’s use, and preventive measures must be adopted in order to assure the integrity of the process and users. The AT signaling device will stay on during the tuning process. In the case of PWM or pulse output, the quality of tuning will also depend on the level time adjusted previously by the user. If the tuning does not result in a satisfactory control, refer to Table 05 for guidelines on how to correct the behavior of the process.

PARAMETER VERIFIED PROBLEM SOLUTION
Proportional Band Slow answer Decrease
Great oscillation Increase
Rate of Integration Slow answer Increase
Great oscillation Decrease
Derivative Time Slow answer or instability Decrease
Great oscillation Increase

Table 05 – Guidance for manual adjustment of the PID parameters

MAINTENANCE

PROBLEMS WITH THE CONTROLLER
Connection errors and inadequate programming are the most common errors found during the controller operation. A final revision may avoid loss of time and damages.
The controller displays some messages to help the user identify problems.

MESSAGE

DESCRIPTION OF THE PROBLEM

……….

Open input. No sensor o signal.
itsensor N1020 Yet Powerful Temperature Controller - fig 123 Connection and/or configuration errors. Check the wiring and the configuration.
OPERATING LEVEL TUNING LEVEL ALARMS LEVEL CONFIGURATION LEVEL CALIBRATION LEVEL
PV indication itsensor N1020 Yet Powerful Temperature Controller - fig 125 itsensor N1020 Yet Powerful Temperature Controller - fig 126 itsensor N1020 Yet Powerful Temperature Controller - fig 127 itsensor N1020 Yet Powerful Temperature Controller - fig 128
Timer indication
itsensor N1020 Yet Powerful Temperature Controller - fig 124

( * ) The PR55 prompt precedes the parameters on the protected levels.

Other error messages may indicate hardware problems requiring maintenance service.
CALIBRATION OF THE INPUT
All inputs are factory calibrated and recalibration should only be done by qualified personnel. If you are not familiar with these procedures do not attempt to calibrate this instrument.
The calibration steps are:
a) Configure the input type to be calibrated.
b) Enter in Calibration Level.
c) At the input terminals, apply a signal corresponding to a value slightly above the lower input limit.
d) Access the parameter in. Using the itsensor N1020 Yet Powerful Temperature Controller - icon 1and  itsensor N1020 Yet Powerful Temperature Controller - icon 2keys, adjust  the display reading such as to match the applied signal, then press the key
e) At the input terminals, apply a signal corresponding to a value slightly below the upper input limit.
f) Access the parameter ink. Using the and keys, adjust the display reading such as to match the applied signal, then press the key.
g) Return to the Operation level and check the calibration result.
Note: When checking the controller calibration with a Pt100 simulator, pay attention to the simulator minimum excitation current requirement, which may not be compatible with the 0.170 mA excitation current provided by the controller.

SPECIFICATIONS

DIMENSIONS: …………………………………. 25 x 48 x 105 mm (1/32 DIN)
Panel Cutout: ……………………………….. 23 x 46 mm (+0.5 -0.0 mm)
Approximate Weight: …………………………………………………….. 75 g
POWER SUPPLY: ………………… 100 to 240 Vac/dc (±10 %), 50/60 Hz
Maximum consumption: ………………………………………………… 5 VA
CONDITIONS ENVIRONMENTAL:
Operation Temperature: ……………………………………….. 0 to 50 °C
Relative Humidity: ………………………………………………… 80 % max.
INPUT ………………………… T/C, Pt100 and voltage (according to Table 01)
Input Resolution: ………………………………… 32767 levels (15 bits)
Resolution of Display: …… 12000 levels (from -1999 up to 9999)
Rate of input reading: ……………………………..up to 55 per second
Accuracy: . Thermocouples J, K, T, E: 0.25 % of the span ±1 ºC
………………. Thermocouples N, R, S, B: 0.25 % of the span ±3 ºC
……………………………………………………… Pt100: 0.2 % of the span
…………………………………………………………………………… mV: 0.1 %
Input Impedance: ……………. Pt100 and thermocouples: > 10 MΩ
Measurement of Pt100: ………………….. 3-wire type, (α=0.00385)
With compensation for cable length, an excitation current of 0.170 mA
OUTPUT
OUT1: ………………………………………….. Voltage pulse; 5 V / 25 mA
OUT2: ………………………….. Relay SPST, 1.5 A / 240 Vac / 30 Vdc
FRONT PANEL: …………………………… IP65, Polycarbonate (PC) UL94 V-2
ENCLOSURE: …………………………………………….. IP30, ABS+PC UL94 V-0
ELECTROMAGNETIC COMPATIBILITY: …………… EN 61326-1:1997 and EN 61326-1/A1:1998
EMISSION: …………………………………………………… CISPR11/EN55011
IMMUNITY: …………………. EN61000-4-2, EN61000-4-3, EN61000-4-4,
EN61000-4-5, EN61000-4-6, EN61000-4-8 and EN61000-4-11
SAFETY: …………………….. EN61010-1:1993 and EN61010-1/A2:1995 (UL file E300526)
USB INTERFACE 2.0, CDC CLASS (VIRTUAL COMMUNICATIONS PORT), MODBUS RTU PROTOCOL.
SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS; PROGRAMMABLE LEVEL OF PWM DE 0.5 UP 100 SECONDS;
STARTS UP OPERATION AFTER 3 SECONDS CONNECTED TO THE POWER SUPPLY; CERTIFICATIONS: CE, UKCA and UL.

IDENTIFICATION

N1020 – A – B – C

A: Output:
PR: OUT1= Pulse / OUT2= Relay
B: Digital Communication:
485: Interface communication RS485
C: Power Supply: 100~240 Vac/dc; 50~60 Hz

WARRANTY
Warranty conditions are available on our website
www.novusautomation.com/warranty.
CONTACTS
For further information, contact us: assistenza@itsensor.it +39 0425 1810834
ITSENSOR Srl- Viale Porta Adige 45 – Torre Uffici Censer
45100 Rovigo (RO) – ITALY www.itsensor.it +39 0425 1810834 info@itsensorN
www.itsensor.it