iSMA CONTROLLI SFAR-1M-4DI-M Modbus I-O Module

iSMA CONTROLLI SFAR-1M-4DI-M Modbus I-O Module-PRODUCT

SPECIFICATION

Power supply Voltage 10-38 V DC; 10-28 V AC
Power consumption 1 W @ 24 V DC; 2 VA @ 24 V AC
Digital inputs 4x, logical “0”: 0-3 V, logical “1”: 6-38 V
Isolation 1500 Vrms
Counters 4x, Resolution 32 bits Frequency max 1 kHz
Non-volatile counters memory (FRAM)
Baudrate from 2400 to 115200 bps
Ingress protection IP40 – for indoor installation
Temperature Operating -10°C – +50°C; Storage – 40°C – +85°C
Relative humidity 5 to 95% RH (without condensation)
Connectors Max 2.5 mm2
Dimension 90 mm x 56,4 mm x 17,5 mm
Mounting DIN rail mounting (DIN EN 50022)
Housing material Plastic, self-extinguishing PC/ABS

TOP PANEL

iSMA CONTROLLI SFAR-1M-4DI-M Modbus I-O Module-FIG-1

CONNECTION OF INPUTS

Digital inputs

iSMA CONTROLLI SFAR-1M-4DI-M Modbus I-O Module-FIG-2

WARNING

  • Note, an incorrect wiring of this product can damage it and lead to other hazards. Make sure the product has been correctly wired before turning the power ON.
  • Before wiring, or removing/mounting the product, be sure to turn the power OFF. Failure to do so might cause electric shock.
  • Do not touch electrically charged parts such as the power terminals. Doing so might cause electric shock.
  • Do not disassemble the product. Doing so might cause electric shock or faulty operation.
  • Use the product within the operating ranges recommended in the specification (temperature, humidity, voltage, shock, mounting direction, atmosphere etc.). Failure to do so might cause fire or faulty operation.
  • Firmly tighten the wires to the terminal. Insufficient tightening of the wires to the terminal might cause fire.

TERMINALS OF THE DEVICE

iSMA CONTROLLI SFAR-1M-4DI-M Modbus I-O Module-FIG-3

Registered access

Modbus Dec Hex Register Name Access Description
30001 0 0x00 Version/Type Read Version and Type of the device
30002 1 0x01 Address Read Module Address
40003 2 0x02 Baud rate Read & Write RS485 baud rate
40004 3 0x03 Stop Bits & Data Bits Read & Write No of Stop bits & Data Bits
40005 4 0x04 Parity Read & Write Parity bit
40006 5 0x05 Response Delay Read & Write Response delay in ms
40007 6 0x06 Modbus Mode Read & Write Modbus Mode (ASCII or RTU)
40009 8 0x08 Watchdog Read & Write Watchdog
 

40033

 

32

 

0x20

Received packets LSR (Least Significant  

Read & Write

 

 

No of received packets

 

40034

 

33

 

0x21

Received packets MSR (Most Significant  

Read & Write

40035 34 0x22 Incorrect packets LSR Read & Write  

No of received packets with error

40036 35 0x23 Incorrect packets MSR Read & Write
40037 36 0x24 Sent packets LSR Read & Write  

No of sent packets

40038 37 0x25 Sent packets MSR Read & Write
30051 50 0x32 Inputs Read Inputs state
40053 52 0x34 Counter 1 LSR Read & Write  

32-bit counter 1

40054 53 0x35 Counter 1 MSR Read & Write
40055 54 0x36 Counter 2 LSR Read & Write  

32-bit counter 2

40056 55 0x37 Counter 2 MSR Read & Write
Modbus Dec Hex Register Name Access Description
40057 56 0x38 Counter 3 LSR Read & Write  

32-bit counter 3

40058 57 0x39 Counter 3 MSR Read & Write
40059 58 0x3A Counter 4 LSR Read & Write  

32-bit counter 4

40060 59 0x3B Counter 4 MSR Read & Write
40061 60 0x3C CCounter 1 LSR Read & Write  

32-bit value of captured counter 1

40062 61 0x3D CCounter 1 MSR Read & Write
40063 62 0x3E CCounter 2 LSR Read & Write  

32-bit value of captured counter 2

40064 63 0x3F CCounter 2 MSR Read & Write
40065 64 0x40 CCounter 3 LSR Read & Write  

32-bit value of captured counter 3

40066 65 0x41 CCounter 3 MSR Read & Write
40067 66 0x42 CCounter 4 LSR Read & Write  

32-bit value of captured counter 4

40068 67 0x43 CCounter 4 MSR Read & Write
40069 68 0x44 Counter Config 1 Read & Write Counter Configuration

+1 – time measurement (if 0 counting impulses)

+2 – autocatch counter every 1 sec

+4 – catch value when input low

+8 – reset counter after catch

+16 – reset counter if input low

40070 69 0x45 Counter Config 2 Read & Write
40071 70 0x46 Counter Config 3 Read & Write
40072 71 0x47 Counter Config 4 Read & Write
40073 72 0x48 Catch Read & Write Catch counter
40074 73 0x49 Status Read & Write Captured counter

INSTALLATION GUIDELINE

Please read the instruction before use or operating the device. In case of any questions after reading this document, please contact the iSMA CONTROLLI Support Team (support@ismacontrolli.com).

  • Before wiring or removing/mounting the product, make sure to turn the power off. Failure to do so might cause an electric shock.
  • Improper wiring of the product can damage it and lead to other hazards. Make sure that the product has been correctly wired before turning the power on.
  • Do not touch electrically charged parts such as power terminals. Doing so might cause an electric shock.
  • Do not disassemble the product. Doing so might cause an electric shock or faulty operation.
  • Use the product only within the operating ranges recommended in the specification (temperature, humidity, voltage, shock, mounting direction, atmosphere, etc.). Failure to do so might cause a fire or faulty operation.
  • Firmly tighten the wires to the terminal. Failure to do so might cause a fire.
  • Avoid installing the product in close proximity to high-power electrical devices and cables, inductive loads, and switching devices. Proximity of such objects may cause an uncontrolled interference, resulting in an instable operation of the product.
  • Proper arrangement of the power and signal cabling affects the operation of the entire control system. Avoid laying the power and signal wiring in parallel cable trays. It can cause interferences in monitored and control signals.
  • It is recommended to power controllers/modules with AC/DC power suppliers. They provide better and more stable insulation for devices compared to AC/AC transformer systems, which transmit disturbances and transient phenomena like surges and bursts to devices. They also isolate products from inductive phenomena from other transformers and loads.
  • Power supply systems for the product should be protected by external devices limiting overvoltage and effects of lightning discharges.
  • Avoid powering the product and its controlled/monitored devices, especially high power and inductive loads, from a single power source. Powering devices from a single power source causes a risk of introducing disturbances from the loads to the control devices.
  • If an AC/AC transformer is used to supply control devices, it is strongly recommended to use a maximum 100 VA Class 2 transformer to avoid unwanted inductive effects, which are dangerous for devices.
  • Long monitoring and control lines may cause loops in connection with the shared power supply, causing disturbances in the operation of devices, including external communication. It is recommended to use galvanic separators.
  • To protect signal and communication lines against external electromagnetic interferences, use properly grounded shielded cables and ferrite beads.
  • Switching the digital output relays of large (exceeding specification) inductive loads can cause interference pulses to the electronics installed inside the product. Therefore, it is recommended to use external relays/contactors, etc. to switch such loads. The use of controllers with triac outputs also limits similar overvoltage phenomena.
  • Many cases of disturbances and overvoltage in control systems are generated by switched, inductive loads supplied by alternating mains voltage (AC 120/230 V). If they do not have appropriate built-in noise reduction circuits, it is recommended to use external circuits such as snubbers, varistors, or protection diodes to limit these effects.

Electrical installation of this product must be done in accordance with national wiring codes and conform to local regulations.