EC-TX803 PROFIBUS-DP Communication Expansion Module

Specifications

  • Working temperature: [specification]
  • Storage temperature: [specification]
  • Relative humidity: [specification]
  • Running environment: [specification]
  • Installation method: [specification]
  • Ingress protection (IP) rating: [specification]
  • Heat dissipation method: [specification]
  • Communication rate: [specification]
  • Network topology: [specification]

Product Overview

Model Description

Product model: EC-TX803

Distinguishing code: 803 (PROFIBUS-DP communication), TX
(communication module), EC (expansion module)

Component Description

No. Name Description
1 STATUS indicator (green) On: The expansion card is connected with the master device.
Off: The expansion card is disconnected from the master
device.
2 FAULT indicator (red) Blinking (On: 250ms; Off: 250ms): User parameter data is
incorrect. Off: No fault.
3 Installation fixing hole To fix the expansion module
4 PROFIBUS-DP communication port For communication with the control box

Installation and Wiring

Installation Precautions

  • Ensure the device is powered off before installation.
  • Use any of the 3 expansion module interfaces on the control
    box.
  • Recommended to install the PROFIBUS-DP expansion module at
    expansion slot 3.

Installation Instructions

  1. Place the expansion module in the corresponding position of the
    control box expansion slot 3.
  2. Align the positioning hole with the stud.
  3. Fix with an M3 screw to complete the installation.

FAQ

Q: What is the maximum number of nodes that can be
connected?

A: When used, a maximum of 127 nodes (including repeaters and
master nodes) can be connected.

Q: What standard does the product comply with?

A: The product complies with the fieldbus standard EN50170.

“`

EC-TX803 PROFIBUS-DP Communication Expansion Module
EC-TX803 PROFIBUS-DP Communication Expansion Modules User Manual

1.2 Specifications

EC-TX803 PROFIBUS-DP Communication Expansion Module Table 1-1 Specifications

Parameters Working temperature Storage temperature
Relative humidity Running environment Installation method Ingress protection (IP) rating Heat dissipation method Communication rate
Network topology

Specification -10­50 -20­60.0 5%­95% (No condensation) No corrosive gas Fixed with snap-fits and screws IP20 Natural air cooling 9.6k bit/s­12M bit/s Linear bus with one active fieldbus terminal resistor on each end

1.3 Structure

Figure 1-2 Structural diagram

1 2

3

5

EC-TX803 PROFIBUS-DP Communication Expansion Module
2.2 Dimensions
The dimensions of the PROFIBUS-DP expansion module is 73.5 ×74×23.3 (W*H*D) mm, as shown in Figure 2-1.
Figure 2-1 Product outline and mounting dimensions diagram (unit: mm)
72

73.5
STATUS FAULT

23.3 22.5

74 53

Preface
Thank you for choosing INVT EC-TX803 PROFIBUS-DP communication expansion modules. EC-TX803 is a PROFIBUS-DP fieldbus communication module that needs to be used with the GD880 series VFD control box. The expansion module communicates with the bus master through PROFIBUS-DP communication protocol. This manual describes the product overview, installation, wiring, and commissioning instructions. Before installing the VFD, read through this manual carefully to ensure the proper installation and running with the excellent performance and powerful functions into full play. Product features: Communication rate: 9.6kbit/s­12Mbit/s A maximum of 31 nodes can be connected when no repeater is used. If repeaters are
used, a maximum of 127 nodes (including the repeaters and master nodes) can be connected. Complies with the fieldbus standard EN50170
1 Product overview
1.1 Model description
Figure 1-1 Product nameplate and model designation

Nameplate

Manufacture No. Product model

XXXXXXXXXXXXXXX EC-TX803

Product model EC – TX 803
Distinguishing code 803: PROFIBUS-DP communication Module category TX: communication module Product category EC: expansion module

PLC1.ir

6

4

7

Table 1-2 Component description

No.

Name

Description

STATUS

On: The expansion card is connected with the master device and

1

bus status data exchange can be performed.

indicator Off: The expansion card is disconnected from the master device.

(green)

On: The expansion module is offline and data exchange cannot

be performed.

Blinking (On: 500ms; Off: 500ms): Configuration error occurs. The

length of the user parameter data set during the module

initialization is different from that during the network

FAULT

configuration.

2 Fault indicator Blinking (On: 250ms; Off: 250ms): User parameter data is

(red)

incorrect, The length or content of the user parameter data set

during the module initialization is different from that during the

network configuration.

Blinking (On: 125ms; Off: 125ms): An error occurs in the ASIC

initialization of PROFIBUS communication.

Off: No fault

3

Installation To fix the expansion module

fixing hole

X1 –

4 communication PROFIBUS-DP communication port

port

5

Nameplate Including the model and sequence number of the expansion

module

6

Connection For connection between the PROFIBUS-DP module and control

port

box.

Positioning To align the expansion module and control box for easy

7

hole

installation

2 Installation and wiring
2.1 Installation precautions

Make sure the device have been powered off before installation.

Note

There are 3 expansion module interfaces on the control box (expansion slot 1, expansion slot 2, expansion slot 3). You can use any of these slots according to the actual wiring.
It is recommended to install the PROFIBUS-DP expansion module at expansion slot 3.

Required tools: Phillips screwdriver PH1, straight screwdriver SL3

Table 2-1 Screw torque requirements

Screw size M3

Fastening torque 0.55 N·m

M3

2.3 Installation instructions
It is recommended to install the PROFIBUS-DP expansion module at expansion slot 3 of the control box. The following is an example of the installation at slot 3. Step 1 Place the expansion module in the corresponding position of the control box expansion slot 3, align it with the slot, and then buckle it together. Step 2 Align the expansion module positioning hole with the positioning stud. Step 3 Fix with a M3 screw. The installation is complete.

Expansion slot 1
Expansion slot 2

Expansion slot 3

Step 1

Step 2

Step 3

Note: The expansion module and control box are electrically connected through slots. Please
install them in place. To ensure the reliable operation of the expansion module and meet EMC requirements,
please tighten the screws according to the recommended torque for reliable grounding.
2.4 Disassembly instructions
You can disassembly the module by reversing the order of steps described in section 2.3 Installation instructions.
Step 1 Disconnect all power supplies and disassemble all cables connected to the expansion module.
Step 2 Use a Phillips screwdriver PH1 to remove the grounding screws of the expansion module.
Step 3 Lift the expansion module out of the control box positioning stud and pull it out to a suitable position. Disassembly is complete.

EC-TX803 PROFIBUS-DP Communication Expansion Module
2.5 User’s wiring terminal
Figure 2-2 Terminal diagram

EC-TX803 PROFIBUS-DP Communication Expansion Module
3 Commissioning instruction
Figure 3-1 PROFIBUS-DP communication expansion module configuration flowchart Start

Table 2-2 D-type connector function definition

D-type connector

5

4

3

2

1

6

7

8

9

Pin

Name

1

2

3

B-Line

4

RTS

5 GND_BUS

6

+5V BUS

7

8

A-Line

9

Housing SHLD

Description Not connected
Unused Receive Date+ Request sending
GND +5V Not connected Receive DataNot connected Shielded cable

2.6 Wiring precautions
The PROFIBUS-DP communication expansion module supports the standard 9-pin D-type connector. The electrical wiring diagram is shown in Figure 2-3.
Figure 2-3 PROFIBUS-DP bus connection diagram

Up to 31

Control box

Control box

PROFIBUS-DP

master

STATUS

FAULT

STATUS FAULT

Table 2-3 Transmission rates and corresponding transmission distances

Baud rate (kbps)
Transmission distance (m)

9.6 1200

19.2 1200

93.75 187.5 500 1500 12000

1200

1000

400

200

100

Note:
Transmission distance in Table 2-3 refers to the distance without repeaters.
A maximum of 31 nodes can be connected when no repeater is used. If repeaters are used, a maximum of 127 nodes (including the repeaters and master nodes) can be connected.

Check the electrical connection between the PLC and the module
is proper.
Wait for the PLC and the control box to be powered on.
Set the node number of expansion module (P40.01) based on the system (The control box is repowered on after the node number is changed.)

Check P40.00 to

N

confirm whether the

module status is 1:

online.

Y

Configure other function codes.

Check whether the

N

STATUS indicator is

green (flashing).

Y End

Table 3-1 Function code parameters related to PROFIBUS-DP communication expansion module

Function code

Name

Description

Bit0: Online status of SLOT1 module

Bit1: Online status of SLOT2 module

Bit2: Online status of SLOT3 module

Bit3: Online status of SLOT2-1 module

Bit4: Online status of SLOT2-2 module

P40.00

Module Bit5: Online status of SLOT2-3 module online status Bit6: Online status of SLOT3-1 module

Bit7: Online status of SLOT3-2 module

Bit8: Online status of SLOT3-3 module

Online status

0: Offline

1: Online

Node

P40.01

number of expansion

1­127

module

0: None

1: PROFIBUS-DP module

Bus adapter 2: PROFINET I/O module

P37.00 supporting 3: CANopen module

bus type 4: EtherNET module

5: EtherCAT module

6: DeviceNet module

Remote control channel selection

Remote 0: Bus adapter A

P02.00

control 1: Bus adapter B channel 2: MODBUS (address 0x4200, 0x4201)

selection 3: Terminal start/stop module (IN1,

IN2, IN3)

Setting range 0x00­0x1FF
1­127 0­6 0­3

Default 0x00 1 1 0

Note:
When two identical communication expansion modules are mounted at the same time, only the expansion module in the slot with a small label number is functional, while the other expansion module is used for redundancy. For example, when two DP expansion modules are inserted in slot 1 and slot 2 respectively, the DP module in slot 1 is valid.
For other parameter settings of the EC-TX803 PROFIBUS-DP expansion module, see software manuals of the GD880 series products.

PLC1.ir

EC-TX803 PROFIBUS-DP Communication Expansion Module

Documents / Resources

iNVT EC-TX803 PROFIBUS-DP Communication Expansion Module [pdf] User Manual
EC-TX803, EC-TX803 PROFIBUS-DP Communication Expansion Module, PROFIBUS-DP Communication Expansion Module, Communication Expansion Module, Expansion Module, Module