HT Instruments - logoPV-ISOTEST Insulation Tester PV
Instruction Manual

PV-ISOTEST Insulation Tester PV

HT Instruments PV-ISOTEST Insulation Tester PVHT Instruments PV-ISOTEST Insulation Tester PV 2

Instrument for the verification, maintenance and safety of photovoltaic systems up to 1500VDC
15OO and no more 1OOO.

Photovoltaic technology is changing.
The design and production of installations increasingly takes into consideration the increase in rated voltage, which allows for the realization of strings up to 30% longer, for a higher generated power and, at the same time, uses a smaller number of components, which allows for the reduction of energy loss (BoS) up to 30%, while improving profitability.
In this way, an increasing number of photovoltaic installations are realized with a rated voltage close to 1500VDC, with a view to obtaining the maximization of all the relevant benefits, while falling, at the regulatory level, in the classification of Low Voltage systems.
Consequently, the probability of a stress on each part of the photovoltaic system generates the need of having suitable and highly performing tools for an accurate and appropriate verification of these new parameters.
This is why HT Italia has created and developed PV ISOTEST, the first and only instrument suitable to carry out, on a photovoltaic system up to 1500VDC, the most important safety checks required by standard IEC/EN62446-1, and to guarantee the quality performance a professional nowadays considers as highly indispensable.
PV-ISOTEST, the future is coming, and HT brings it.HT Instruments PV-ISOTEST Insulation Tester PV - fig

INSULATION IN DUAL MODE

VERIFIES 

Verification with an immediate result (OK | NO) of the insulation resistance of the active conductors of a module, string or entire photovoltaic field, according to the requirements of standard IEC/EN62446, with no need for an external switch to short-circuit the positive and negative terminals.HT Instruments PV-ISOTEST Insulation Tester PV - VERIFIES

IDENTIFIES

Automatic identification, with one single test, of the conformity of the total insulation of a whole photovoltaic field, with respect to expectations. PV-ISOTEST is the only verification instrument capable of simultaneously indicating the insulation resistance values of both the positive and negative poles, thus giving the operator the possibility to direct his search to the real location of the fault.HT Instruments PV-ISOTEST Insulation Tester PV - IDENTIFIESINSULATION IN TIMER MODE
VERIFIES
Verification with immediate result (OK | NO) of the insulation resistance of a cable with calculation of the Dielectric Absorption Ratio (DAR = R1min / R30s) and of the Polarization Index (PI = R10min/R1min), which indicate the state of deterioration of the insulation.
IDENTIFIES
Evaluation of the values of parameters DAR and PI, specifically useful in case the insulation of particularly long or old cables is to be tested. HT Instruments PV-ISOTEST Insulation Tester PV - Insulation

GFL (Ground Fault Locator) function
LOCALIZES
PV-ISOTEST provides the precise position of a possible single fault of low insulation found on a string of the PV system due, for example, to water or humidity infiltrations.
HT Instruments PV-ISOTEST Insulation Tester PV - LOCALIZES

RPE FUNCTION

VERIFIES
Verification with an immediate result (OK | NO) of the continuity of the protective conductors and of the relevant connections with test current >200mA
DMM FUNCTION
DISPLAYS
Immediate display of the DC and RMS voltages (also including possible AC components) between the poles and the earth.HT Instruments PV-ISOTEST Insulation Tester PV - Insulation mode TIMER

HT Instruments PV-ISOTEST Insulation Tester PV - icon Provided accessories

  • KITGSC4 Set of 4 banana cables 4mm + 4 alligator clips
  • KITPCMC4 Set of 2 MC4 banana adapters
  • VA507 Hard carrying case
  • SP-5100 Carrying straps
  • TOPVIEW2006 PC Windows software+ optical/USB connection cable (order code: C2006)
  • YAMUM0077HT0 User manual on CD-ROM
  • AMUM0076HT0 Quick reference guide
  • ISO calibration report

Optional accessories

  • 606-IECN
    Connector with magnetic terminal, black
  • 1066-IECN
    Connector for extension cables with 4mm banana connector, black
  • 1066-IECR
    Connector for extension cables with 4mm banana connector, red

HT Instruments PV-ISOTEST Insulation Tester PV - icon 2 Technical sheet

› DC VOLTAGE

Range (V) Resolution (V)  Accuracy
3 ÷ 1500 1 ± (1.0%reading + 2digits)

› AC TRMS VOLTAGE

Range (V) Resolution (V) Accuracy
3 ÷ 1000 1 ± (1.0%reading + 3digits)

› INSULATION RESISTANCE (MΩ) – DUAL MODE

Test voltage DC [V] Range [MΩ] Resolution [MΩ] Accuracy
250, 500,
1000, 1500
0.1 ÷ 0.99 0.01 ±(5%reading +
5digits)
1.0 ÷ 19.9 0.1
20 ÷ 100 1

› INSULATION RESISTANCE (MΩ) – TIMER MODE

Test voltage DC [V] Range [MΩ] Resolution [MΩ] Accuracy
250, 500, 1000, 1500 0.1 ÷ 9.99 0.01 ±(5.0%reading+ 5digits)
10.0 ÷ 99.9 0.1

› CONTINUITY OF PROTECTIVE CONDUCTORS (RPE)

Range (Ω) Resolution (Ω) Accuracy
0.00 ÷ 9.99 0.01 ±(2%reading
+ 2digits)
10.0 ÷ 99.9 0.1
100 ÷ 1999 1
Test current:  >200mA DC up to 5Ω (cables included)
Resolution: 1mA
Accuracy: ±(5.0%reading + 5digits)
Open-circuit voltage: 4 < Vo < 10V

› GFL (GROUND FAULT LOCATOR) FUNCTION

Test voltage DC [V] Range [MΩ] Resolution
[MΩ]
Accuracy Accuracy ofposition
250, 500, 1000, 1500 0.1 ÷ 0.99 0.01 ±(5.0%rdg + 5dgt) ± 1module
1.0 ÷ 19.9 0.1
20 ÷ 100 1

The GFL function provides correct results with the following conditions:

  • Test carried out with Vtest ≥Vnom on a single string disconnected from the inverter, from possible overvoltage protections and earth connections
  • Test carried out upstream of possible blocking diodes
  • Single fault of low insulation located at any position in the string
  • Insulation resistance of the single fault <0.1MΩ

Environmental conditions similar to those in which the fault occurred
POWER SUPPLY

Battery type: 6×1.5V alkaline batteries type AA LR06 or  6×1.2V rechargeable batteries type AA LR06
Battery duration: approx. 500 tests (for each function)
Auto Power OFF: after 5 minutes’ idling

OUTPUT INTERFACE
PC interface: optical/USB
REFERENCE STANDARDS:

Instrument safety: IEC/EN61010-1, IEC/EN61010-2-030 IEC/EN6 1 0 1 0-2 -0 3 3EC/EN6 1 0 1 0-2 -0 3 4
EMC: IEC/EN61326-1
Accessory safety:  IEC/EN61010-031
IEGeneral: IEC/EN62446
MΩ measurement: IEC/EN61557-2
RPE measurement: IEC/EN61557-4
Insulation: double insulation
Pollution level: 2
Measurement category CAT III 1500VDC, CAT III 1000VAC MAX 1500VDC / 1000VAC between inputs

WATCH TUTORIAL VIDEOS

HT Instruments PV-ISOTEST Insulation Tester PV - qr codehttps://l.ead.me/bbpoRV

PRODUCT DETAILS CONSULT THE

HT Instruments PV-ISOTEST Insulation Tester PV - qr code 1https://l.ead.me/bbsBHG

HT Instruments - logoHT ITALIA S.R.L.
Via della Boaria, 40 48018 Faenza (RA) Italia
T +39 0546 621002 | F +39 0546 621144 | M export@htitalia.it | ht-instruments.itHT Instruments PV-ISOTEST Insulation Tester PV - icon 3