RMA803 Smart Line Remote Field Bus Indicator
“
Specifications:
- Number of Devices/Segment Entity IS model: 6
devices/segment - Schedule Entries: 30 maximum schedule entries
- Number of VCR’s: 50 max
- Compliance Testing: Tested according to ITK 6.1.1
- Software Download: Utilizes Class-3 of the Common Software
Download procedure as per FF-883 - Operating Conditions:
- Ambient Temperature:
- Reference Condition: 25°C (77°F)
- Operative Limits: -40 to 70°C (-4 to 158°F)
- Transportation and Storage: -30 to 80°C (-22 to 175°F)
- Humidity: 10% to 55% RH (0% to 100% RH)
- Ambient Temperature:
Product Usage Instructions:
Display Features:
The RMA803 SmartLine Fieldbus Remote Indicator features an
advanced graphics LCD display with the following capabilities:
- Up to 8 displays in Large PV, Bar Graph, and Trend Display
formats - User-configurable display rotation timing and contrast
settings
Integral Keypad:
The RMA803 comes with an integral three-button keypad for
limited display set-up and operation. Full setup capabilities are
available using DD/DTM based configuration tools.
Function Blocks:
The RMA803 supports function blocks for enhanced control and
monitoring capabilities.
FAQ:
Q: How many devices can be connected per segment?
A: The IS model allows for connection of up to 6 devices per
segment.
Q: What is the maximum number of schedule entries
supported?
A: The device supports a maximum of 30 schedule entries.
Q: How many displays can be shown on the graphics LCD?
A: The graphics display can show up to 8 displays in Large PV,
Bar Graph, and Trend Display formats.
“`
SmartLine
Technical Information
RMA803 SmartLine Remote Fieldbus Indicator Specification 34-ST-03-90, December 2023
Introduction The Honeywell RMA803 is a Foundation Fieldbus remote indicator suitable for use with any Foundation Fieldbus measuring device. The RMA803 allows users to display up to eight (8) values and associated status from devices connected on the same H1 link. The RMA803 can be located anywhere along the Foundation Fieldbus H1 segment providing easy to access data for inaccessible measuring devices or control devices not equipped with displays. The RMA can also provide advanced calculation and or control capability via the use of the optional PID, signal characterizer, arithmetic, input selector, and integrator function blocks.
Best in Class Features:
· Foundation Fieldbus Interoperability tested · Up to eight values can be displayed · Full graphic display provides bar graph and trending · Link master capability · Wide variety of function blocks · Remote Meter diagnostic displays · Polarity insensitive electrical connections · Modular design characteristics · Dual compartment housing
Link Active Scheduler Transmitters can perform as a backup Link Active Scheduler (LAS) and take over when the host is disconnected. Acting as a LAS, the device ensures scheduled data transfers typically used for the regular, cyclic transfer of control loop data between devices on the Fieldbus.
Number of Devices/Segment Entity IS model: 6 devices/segment
Schedule Entries 30 maximum schedule entries
Number of VCR’s: 50 max Compliance Testing: Tested according to ITK 6.1.1
Figure 1 RMA803 Remote Indicator
Software Download Utilizes Class-3 of the Common Software Download procedure as per FF-883.
Integral Keypad The RMA803 utilizes an integral three button keypad permitting limited display set-up and operation. Full set up capabilities are available using DD/DTM based configuration tools
Advanced Graphics LCD Display Features
· 0, 90, 180, & 270 degree viewing position adjustments · Standard and custom measurement units available. · Up to eight display screens with 3 formats are possible · (Large PV or PV with Bar Graph or PV with Trend
Graph)
· Configurable screen rotation timing (4 to 30 sec) · Multiple language capability. (EN, GE, FR, IT, SP, RU,
TU, CH & JP)
· Ability to enable/disable screen rotation
2
RMA803 SmartLine Fieldbus Remote Indicator
Display Screens & Diagnostics The RMA803 graphics display is capable of up to 8 displays in any one of 3 formats (Large PV, Bar Graph, and Trend Display). Certain diagnostics for the RMA803 are also accessible (see the accessible parameter listing for details).
Accessible Parameter Listing
Large PV
Trend Display
Bar Graph
Similar to all other SmartLine products, the display rotation timing and contrast settings are user configurable.
Function Blocks
x- Not available, – Available, R Read Only, R/W Read/Write, W Write Only
RMA803 SmartLIne Fieldbus Remote Indicator
3
Specifications Operating Conditions Parameter
Ambient Temperature1
Reference Condition
C
F
25±1 77±2
Operative Limits
C -40 to 70
F -4 to 158
Transportation and Storage
C -30 to 80
F -22 to 175
Humidity (%RH)
10 to 55
0 to 100
0 to 100
LCD display operating temperature is 20 to 70°C. At temperatures beyond this operating limit, display may not be readable but the loop will remain intact.
Physical/Functional Specifications
Parameter
Description
Supply Voltage
9 – 32Vdc Terminal Voltage
Current Consumption Vibration: Electromagnetic Compatibility Lightning Protection Option
Electronic Housing
Wiring Mounting Bracket Electrical Connections
Steady State: 17.5mAdc Code Download: 28mA
IEC 60770-1 field or pipeline, vibration (10-2000 Hz: 0.21mm displacement / 3g max acceleration)
IEC 61326-3-1
Leakage Current: 10uA max @ 42.4VDC 93C
Impulse rating:
8/20uS
5000A (>10 strikes) 10000A (1 strike min.)
10/1000uS 200A (> 300 strikes)
Pure Polyester Powder Coated Low Copper (<0.4%)-Aluminum. Meets NEMA 4X,
IP66, IP67 and NEMA 7 (explosion proof). All stainless steel housing is optional.
Cover O-Ring material : Silicone
Accepts up to 16 AWG (1.5 mm diameter).
Carbon Steel (Zinc-Chromate plated) or 316 Stainless Steel. Suitable for wall or 2″ (50mm) vertical or horizontal pipe mounting.
½”-14 NPT or M20
Dimensions
See Figure 2, Figure 3, Figure 4 and Figure 5
Net Weight
2.5 lbs (1,1 kg) with aluminum housing
Performance Parameter
Accuracy
Display Resolution
Display Capacity
Standard Function Blocks (Execution Times)
Optional Function Blocks (Execution Times)
Description Equivalent to connected devices
Digital Readout: 7 digits, Bar Graph: 128 divisions or 0.78%, Trend: 2.5% of scale
Up to eight (8) function block outputs Resource (n/a), Transducer (n/a), LCD (n/a), Diagnostic (n/a) & Multiple Analog Output (30ms)
PID (45ms), Signal Characterizer (30ms), Arithmetic (30ms), Input Selector (30ms), Integrator (30ms),
4
Mounting & Dimensional Drawings
Reference
Dimensions:
millimeters inches
RMA803 SmartLine Fieldbus Remote Indicator
Figure 2 RMA Dimensions
* Note 1: Housing adapter may not be present on all transmitter models. If the housing adapter is not present, subtract 24,5mm (0,96 inches) from the dimension specified.
RMA803 SmartLine Fieldbus Remote Indicator
5
Mounting & Dimensional Drawings TRANSMITTER ENCLOSURE CAN BE ROTATED A TOTAL OF 90O FROM THE STANDARD MOUNTING POSITION
Figure 3 Horizontal Wall Mounting
Figure 4 Pipe Mount, Horizontal & Vertical
* Note 1: Housing adapter may not be present on all transmitter models. If the housing adapter is not present, subtract 24,5mm (0,96 inches) from the dimension specified.
6
RMA803 SmartLine Fieldbus Remote Indicator
Figure 5 – Pipe Mount, Vertical
*Note 1: Figure 5. Housing adapter may not be present on all transmitter models. If the housing adapter is not present,
subtract 24,5mm (0,96 inches) from the dimension specified.
RMA803 SmartLine Fieldbus Remote Indicator
7
Approval Certifications:
MSG CODE
Agency
FM
A
Approvals TM
(USA)
Type of Protection
Electrical Parameters
Ambient Temperature
Explosion proof Class I, Division 1, Groups A, B, C, D; T6..T4 Dust Ignition Proof: Class II, III, Division 1, Groups E, F, G; T4 Class 1, Zone 1, AEx d IIC T4 Gb Class 2, Zone 21, AEx tb IIIC T 95oC IP 66 Db
Note 1
T6: -50ºC to +65ºC
T4, T5: -50 ºC to 85ºC
Intrinsically Safe: Class I, II, III, Division 1, Groups A, B, C, D, E, F, G; T4 Class I Zone 0 AEx ia IIC T4 Ga Non-Incendive Class I, Division 2, Groups A, B, C, D; T4 Class I Zone 2 AEx nA IIC T4 Gc
Note 2 Note 1
-50 ºC to 70ºC -50 ºC to 85ºC
Enclosure: Type 4X/ IP66/ IP67
ALL
ALL
Standards: FM 3600: 2018;FM 3611: 2018; ANSI/ UL 60079-0: 2013; ANSI/ UL 60079-1:
2015; FM 3610: 2018; ANSI/ UL 60079-11: 2014; FM 3810: 2018; ANSI/ UL 60079-15: 2013; ANSI/ UL 60079-31 : 2015; FM Class 3615: 2018; FM 3616: 2011
Explosion proof:
CSA 14.2689056
Class I, Division 1, Groups A, B, C, D;T6..T4
Dust Ignition Proof: Class II, III, Division 1, Groups E, F, G; T4
Class I Zone 1 Ex db IIC T4 Gb Ex db IIC T4 Gb
Note 1
T6: -50ºC to +65ºC T4, T5: -50 ºC to 85ºC
Zone 21 Ex tb IIIC T 95oC Db
Ex tb IIIC T 95o C Db
Intrinsically Safe:
B
CSA-Canada CSA 14.2689056
Class I, II, III, Division 1, Groups A, B, C, D, E, F, G;
Note 2
-50°C to 70°C
T4
Ex ia IIC T4 Ga
Non-Incendive
CSA 14.2689056
Class I, Division 2, Groups A, B, C, D; T4
Note 1
-50°C to 85°C
Class I Zone 2 Ex nA IIC T4 Gc
Ex nA IIC T4 Gc
Enclosure: Type 4X/ IP66/ IP67
ALL
ALL
Standards: CSA C22.2 No. 0: 2015; CSA C22.2 No. 30: 2016; CSA C22.2 No. 94-M91; CSA C22.2 No. 25: 2017; CSA C22.2 No. 61010-1: 2017; CSA-C22.2No.157: 2016; C22.2 No. 213: 2017; C22.2 No. CSA 60079-0:2015; C22.2 No. 60079-1: 2016; C22.2 No. 60079-11: 2014; C22.2 No. 60079-15: 2016; C22.2 No. 60079-31: 2015;
ANSI/ ISA12.12.01-2017; ANSI/ ISA 61010-1: 2016; ANSI/ UL 60079-0: 2013; ANSI/ UL 60079-1: 2015; ANSI/ UL 60079-11: 2014; ANSI/ UL 60079-15: 2013; ANSI/ UL 60079-31: 2015 ; FM 3600: 2011; FM 3615: 2006; FM Class 3616: 2011; ANSI/ UL 913: 2015; UL 916: 2015; ANSI/ UL 12.27.01: 2017; ANSI/UL 50E: 2015
Flame-proof:
C
ATEX
II 2 G Ex d IIC T6..T4 Gb II 2 D Ex tb IIIC T 95°C Db
Note 1
T6: -50ºC to +65ºC T4, T5: -50 ºC to 85ºC
8
RMA803 SmartLine Fieldbus Remote Indicator
Intrinsically Safe:
II 2 G Ex ia IIC T4 Ga
Note 2
-50°C to 70°C
Non-Incendive II 3 G Ex ec IIC T4 Gc
Note 1
-50°C to 85°C
Enclosure: Type 4X/ IP66/ IP67
ALL
ALL
STANDARDS: EN IEC 60079-0: 2018; EN 60079-1: 2014; EN 60079-11: 2012; EN 60079-
31: 2014; EN 60079-7: 2015+A1 : 2018;
Flame-proof: II 2 G Ex d IIC T6..T4 Gb
II 2 D Ex tb IIIC T 95°C Db
Note 1
T6: -50ºC to +65ºC T4, T5: -50 ºC to 85ºC
Intrinsically Safe:
II 2 G Ex ia IIC T4 Ga
Note 2
-50°C to 70°C
C
UKEX
Non-Incendive
Note 1
-50°C to 85°C
II 3 G Ex ec IIC T4 Gc
Enclosure: Type 4X/ IP66/ IP67
ALL
ALL
STANDARDS: EN IEC 60079-0: 2018; EN 60079-1: 2014; EN 60079-11: 2012; EN
60079-31: 2014; EN 60079-7: 2015+A1 : 2018;
Flame-proof:
T6: -50ºC to +65ºC
Ex db IIC T6..T4 Gb Ex tb IIIC T 95o C Db
Note 1
T4, T5: -50 ºC to 85ºC
D
IECEx
Intrinsically Safe:
Ex ia IIC T4 Ga
Note 2
-50°C to 70°C
Non-Incendive Ex nA IIC T4 Gc
Note 1
-50°C to 70°C
Enclosure: Type 4X/ IP66/ IP67
ALL
ALL
STANDARDS: IEC 60079-0: 2017; IEC 60079-1: 2014;
IEC 60079-11: 2011; IEC 60079-7: 2017; IEC 60079-31: 2014 Flame-proof:
T6: -20°C to 65°C
Ex db IIC T6..T5 Gb Ex tb IIIC T 95o C Db
Note 1
T95°C, T5: -20°C to 85°C
Intrinsically Safe:
Ex ia IIC T4 Ga
E
SAEx
Ex ic IIC T4 Gc
Non-Incendive
Ex ec IIC T4 Gc
Enclosure: IP66/ IP67
Note 2
Note 1 ALL
-20°C to 70°C
–20°C to 85°C ALL
STANDARDS: IEC 60079-0: 2011; IEC 60079-1: 2014; IEC 60079-11: 2011;
IEC 60079-7: 2006; IEC 60079-31: 2013
Flame-proof: Ex db IIC T6..T5 Gb
Note 1
T6: 50°C to 65°C T5: -50°C to 85°C
Intrinsically Safe:
P
CCoE/ PESO Ex ia IIC T4 Ga
Enclosure: IP66/ IP67
Note 2 ALL
-50°C to 70°C ALL
STANDARDS: IEC 60079-0: 2017; IEC 60079-1: 2014; IEC 60079-11: 2011; IEC 60079-7: 2017; IEC 60079-31: 2013
Notes:
Operating Parameters:
Voltage= 12 to 42 V
Current = 25 mA
Intrinsically Safe Entity Parameters
For details see Control Drawing, 50089981.
RMA803 SmartLine Fieldbus Remote Indicator
9
Model Selection Guide
The Model Selection Guide is subject to change and is inserted into the specification as guidance only.
Model RMA800 Remote Indicator
Section 13 Page: RMA8-1
Effective Date: December 01,2023
Model Selection Guide
34-ST-16-90 Issue 22
Instructions: Make selections from all Tables Key through VI using column below the proper arrow. Asterisk indicates availability. Letter (a) refer to restrictions highlighted in the restrictions table. Tables delimited with dashes. List Price: Price equals the sum of prices for all selections made.
Key
I
II
III
IV
V
VI
RMA80_ – _ – _ _ _ – _ _ – _ _ _ _ – _ _, _ _,_ _ – 00000
KEY NUMBER Remote DE Protocol or Analog (4-20mA DC) Indicator Foundation Fieldbus
BASE MODEL
TABLE I
AGENCY APPROVALS (see data sheet for Approval Code Details)
No Approvals Required
FM Explosion proof, Intrinsically Safe, Non-incendive, & Dustproof
CSA Explosion proof, Intrinsically Safe, Non-incendive, & Dustproof
ATEX Explosion proof, Intrinsically Safe & Non-incendive
Approvals
IECEx Explosion proof, Intrinsically Safe & Non-incendive cCSAus Explosion proof, Intrinsically Safe, Non-incendive, & Dustproof-Canada & US SAEx/CCoE Explosion proof, Intrinsically Safe & Non-incendive
INMETRO Explosion proof, Intrinsically Safe & Non-incendive NEPSI Explosion proof, Intrinsically Safe & Non-incendive KOSHA Explosion proof, Intrinsically Safe & Non-incendive
CCoE Explosion proof, Intrinsically Safe & Non-incendive
TABLE II
a. Electronic Housing Material &
Connection Type
b. Protocol Compatibility
c. Customer Interface Selections
TRANSMITTER ELECTRONICS SELECTIONS
Material
Connection
Polyester Powder Coated Aluminum
1/2 NPT
Polyester Powder Coated Aluminum
M20
Polyester Powder Coated Aluminum
1/2 NPT
Polyester Powder Coated Aluminum
M20
316 Stainless Steel (Grade CF8M)
1/2 NPT
316 Stainless Steel (Grade CF8M)
M20
316 Stainless Steel (Grade CF8M)
1/2 NPT
316 Stainless Steel (Grade CF8M)
M20
Communications Protocol
DE protocol or Analog (4-20mA DC)
Foundation Fieldbus Enabled
Lightning Protection None None Yes Yes None None Yes Yes
Display Standard
External Config Buttons None (Integrated on Display)
Languages English
Advanced Advanced Advanced Advanced
None External
None External
EN, GE, FR, IT, SP, RU, TU EN, GE, FR, IT,SP, RU, TU
EN, CH, JP EN, CH, JP
TABLE III
a. Application Software
CONFIGURATION SELECTIONS
Application Software Standard Software Additional Function Blocks (Fieldbus Only: Adds PID, Char, Arith, Selector & Integ blocks)
b. Configuration
Factory Configuration Factory Standard Factory Standard
Write Protection
Disabled
Enabled
List Price equals the sum of prices
for all selections.
Selection RMA801 RMA803
0
**
A
*
B
*
C
**
D
**
K
*
E
**
F
**
G
**
H
*
P
*
A _ _ B _ _ C _ _ D _ _ E _ _ F _ _ G _ _ H _ _
** **
* * ** ** * *
_ D _ _ F _
_ _ A
_ _ D _ _ E _ _ H _ _ J
* *
* * * * *
1 _
**
2 _
*
_S
**
_T
*
10
RMA803 SmartLine Fieldbus Remote Indicator
TABLE IV
ACCESSORY SELECTIONS
Bracket Type
Material
None
None
a. Mounting Bracket
Flat Pipe Mounting Bracket Flat Pipe Mounting Bracket Wall Mounting Bracket Wall Mounting Bracket
Carbon Steel 316 Stainless Steel Carbon Steel 316 Stainless Steel
Marine Approved Mounting Bracket
316 Stainless Steel
Angle Pipe Mounting Bracket Angle Pipe Mounting Bracket
Carbon Steel 316 Stainless Steel
b. Customer Tag
Customer Tag Type No customer tag One Wired Stainless Steel Tag (Up to 4 lines 26 char/line) Two Wired Stainless Steel Tag (Up to 4 lines 26 char/line)
Unassembled Conduit Plugs & Adapters
c. Unassembled No Conduit Plugs or Adapters Required
Conduit Plugs &
1/2 NPT Male to 3/4 NPT Female 316 SS Certified Conduit Adapter
Adapters 1/2 NPT 316 SS Certified Conduit Plug
M20 316 SS Certified Conduit Plug
RMA803 RMA801
0 _ _ _ 1 _ _ _ 2 _ _ _ 3 _ _ _ 4 _ _ _ 5 _ _ _ 6 _ _ _ 7 _ _ _
** ** ** ** ** ** ** **
_ 0 _ _ _ 1 _ _ _ 2 _ _
** ** **
_ _ A0 _ _ A2 _ _ A6 _ _ A7
** nn nn mm
TABLE V
a. Additional Options
OTHER Certifications & Options:(String in sequence comma delimited (XX, XX, XX,..) None – No additional options required Certificate of Conformance Certificate of Origin Extended Warranty Additional 1 year Extended Warranty Additional 2 years Extended Warranty Additional 3 years Extended Warranty Additional 4 years Extended Warranty Additional 15 years
00
**
F3
**
F5
**
01
**
02
**
03
** b
04
**
15
**
TABLE VI MANUFACTURING SPECIALS Factory Factory Identification
0000 * *
MODEL RESTRICTIONS
Restriction
Available Only with
Letter
Table
d
IIa
m
IIa
n
IIa
b
Not Available with
Selection(s)
Table
Selection(s)
C, D, G, H _ _
IVa
1,2,3,4,6,7 _ _ _
B, D, F, H_ _
A, C, E, G _ _
Select only one option from this group
PRODUCT MANUALS Description
RMA801 Remote Meter Assembly HART / DE manual – English RMA803 Remote Meter Assembly Foundation Fieldbus manual – English
All product documentation is available at www.process.honeywell.com
Part Number 34-ST-25-62 34-ST-25-51
RMA803 SmartLine Fieldbus Remote Indicator
11
Sales and Service
For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor, contact one of the offices below.
ASIA PACIFIC
Honeywell Process Solutions, (TAC) hfs-tacsupport@honeywell.com
Australia Honeywell Limited Phone: +(61) 7-3846 1255 FAX: +(61) 7-3840 6481 Toll Free 1300-36-39-36 Toll Free Fax: 1300-36-04-70
China PRC – Shanghai Honeywell China Inc. Phone: (86-21) 5257-4568 Fax: (86-21) 6237-2826
Singapore Honeywell Pte Ltd. Phone: +(65) 6580 3278 Fax: +(65) 6445-3033
South Korea Honeywell Korea Co Ltd Phone: +(822) 799 6114 Fax: +(822) 792 9015
EMEA
Honeywell Process Solutions, Phone: + 80012026455 or +44 (0)1344 656000
Email: (Sales) FP-Sales-Apps@Honeywell.com or (TAC) hfs-tac-support@honeywell.com
AMERICA’S
Honeywell Process Solutions, Phone: (TAC) 1-800-423-9883 or 215/641-3610 (Sales) 1-800-343-0228
Email: (Sales) FP-Sales-Apps@Honeywell.com or (TAC) hfs-tac-support@honeywell.com
Specifications are subject to change without notice.
For more information To learn more about SmartLine RMA Remote Meter, visit https://process.honeywell.com/ Or contact your Honeywell Account Manager
Process Solutions Honeywell 1250 W Sam Houston Pkwy S Houston, TX 77042
Honeywell Control Systems Ltd Honeywell House, Skimped Hill Lane Bracknell, England, RG12 1EB
Shanghai City Centre, 100 Jungi Road Shanghai, China 20061
https://process.honeywell.com/
34-ST-03-90 December 2023 ©2023 Honeywell International Inc.
Documents / Resources
![]() |
Honeywell RMA803 Smart Line Remote Field Bus Indicator [pdf] Owner's Manual RMA803 Smart Line Remote Field Bus Indicator, RMA803, Smart Line Remote Field Bus Indicator, Remote Field Bus Indicator, Field Bus Indicator, Bus Indicator |