Honeywell RMA803 Smart Line Remote Field Bus Indicator Owner’s Manual

RMA803 Smart Line Remote Field Bus Indicator

Specifications:

  • Number of Devices/Segment Entity IS model: 6
    devices/segment
  • Schedule Entries: 30 maximum schedule entries
  • Number of VCR’s: 50 max
  • Compliance Testing: Tested according to ITK 6.1.1
  • Software Download: Utilizes Class-3 of the Common Software
    Download procedure as per FF-883
  • Operating Conditions:
    • Ambient Temperature:
      • Reference Condition: 25°C (77°F)
      • Operative Limits: -40 to 70°C (-4 to 158°F)
      • Transportation and Storage: -30 to 80°C (-22 to 175°F)
    • Humidity: 10% to 55% RH (0% to 100% RH)

Product Usage Instructions:

Display Features:

The RMA803 SmartLine Fieldbus Remote Indicator features an
advanced graphics LCD display with the following capabilities:

  • Up to 8 displays in Large PV, Bar Graph, and Trend Display
    formats
  • User-configurable display rotation timing and contrast
    settings

Integral Keypad:

The RMA803 comes with an integral three-button keypad for
limited display set-up and operation. Full setup capabilities are
available using DD/DTM based configuration tools.

Function Blocks:

The RMA803 supports function blocks for enhanced control and
monitoring capabilities.

FAQ:

Q: How many devices can be connected per segment?

A: The IS model allows for connection of up to 6 devices per
segment.

Q: What is the maximum number of schedule entries
supported?

A: The device supports a maximum of 30 schedule entries.

Q: How many displays can be shown on the graphics LCD?

A: The graphics display can show up to 8 displays in Large PV,
Bar Graph, and Trend Display formats.

“`

SmartLine
Technical Information
RMA803 SmartLine Remote Fieldbus Indicator Specification 34-ST-03-90, December 2023

Introduction The Honeywell RMA803 is a Foundation Fieldbus remote indicator suitable for use with any Foundation Fieldbus measuring device. The RMA803 allows users to display up to eight (8) values and associated status from devices connected on the same H1 link. The RMA803 can be located anywhere along the Foundation Fieldbus H1 segment providing easy to access data for inaccessible measuring devices or control devices not equipped with displays. The RMA can also provide advanced calculation and or control capability via the use of the optional PID, signal characterizer, arithmetic, input selector, and integrator function blocks.

Best in Class Features:
· Foundation Fieldbus Interoperability tested · Up to eight values can be displayed · Full graphic display provides bar graph and trending · Link master capability · Wide variety of function blocks · Remote Meter diagnostic displays · Polarity insensitive electrical connections · Modular design characteristics · Dual compartment housing
Link Active Scheduler Transmitters can perform as a backup Link Active Scheduler (LAS) and take over when the host is disconnected. Acting as a LAS, the device ensures scheduled data transfers typically used for the regular, cyclic transfer of control loop data between devices on the Fieldbus.
Number of Devices/Segment Entity IS model: 6 devices/segment
Schedule Entries 30 maximum schedule entries
Number of VCR’s: 50 max Compliance Testing: Tested according to ITK 6.1.1

Figure 1 ­RMA803 Remote Indicator
Software Download Utilizes Class-3 of the Common Software Download procedure as per FF-883.
Integral Keypad The RMA803 utilizes an integral three button keypad permitting limited display set-up and operation. Full set up capabilities are available using DD/DTM based configuration tools
Advanced Graphics LCD Display Features
· 0, 90, 180, & 270 degree viewing position adjustments · Standard and custom measurement units available. · Up to eight display screens with 3 formats are possible · (Large PV or PV with Bar Graph or PV with Trend
Graph)
· Configurable screen rotation timing (4 to 30 sec) · Multiple language capability. (EN, GE, FR, IT, SP, RU,
TU, CH & JP)
· Ability to enable/disable screen rotation

2

RMA803 SmartLine Fieldbus Remote Indicator

Display Screens & Diagnostics The RMA803 graphics display is capable of up to 8 displays in any one of 3 formats (Large PV, Bar Graph, and Trend Display). Certain diagnostics for the RMA803 are also accessible (see the accessible parameter listing for details).

Accessible Parameter Listing

Large PV

Trend Display

Bar Graph

Similar to all other SmartLine products, the display rotation timing and contrast settings are user configurable.
Function Blocks

x- Not available, – Available, R ­ Read Only, R/W ­ Read/Write, W ­ Write Only

RMA803 SmartLIne Fieldbus Remote Indicator

3

Specifications Operating Conditions Parameter
Ambient Temperature1

Reference Condition

C

F

25±1 77±2

Operative Limits

C -40 to 70

F -4 to 158

Transportation and Storage

C -30 to 80

F -22 to 175

Humidity (%RH)

10 to 55

0 to 100

0 to 100

LCD display operating temperature is ­20 to 70°C. At temperatures beyond this operating limit, display may not be readable but the loop will remain intact.

Physical/Functional Specifications

Parameter

Description

Supply Voltage

9 – 32Vdc Terminal Voltage

Current Consumption Vibration: Electromagnetic Compatibility Lightning Protection Option
Electronic Housing
Wiring Mounting Bracket Electrical Connections

Steady State: 17.5mAdc Code Download: 28mA

IEC 60770-1 field or pipeline, vibration (10-2000 Hz: 0.21mm displacement / 3g max acceleration)

IEC 61326-3-1

Leakage Current: 10uA max @ 42.4VDC 93C

Impulse rating:

8/20uS

5000A (>10 strikes) 10000A (1 strike min.)

10/1000uS 200A (> 300 strikes)

Pure Polyester Powder Coated Low Copper (<0.4%)-Aluminum. Meets NEMA 4X,

IP66, IP67 and NEMA 7 (explosion proof). All stainless steel housing is optional.

Cover O-Ring material : Silicone

Accepts up to 16 AWG (1.5 mm diameter).

Carbon Steel (Zinc-Chromate plated) or 316 Stainless Steel. Suitable for wall or 2″ (50mm) vertical or horizontal pipe mounting.

½”-14 NPT or M20

Dimensions

See Figure 2, Figure 3, Figure 4 and Figure 5

Net Weight

2.5 lbs (1,1 kg) with aluminum housing

Performance Parameter
Accuracy
Display Resolution
Display Capacity
Standard Function Blocks (Execution Times)
Optional Function Blocks (Execution Times)

Description Equivalent to connected devices
Digital Readout: 7 digits, Bar Graph: 128 divisions or 0.78%, Trend: 2.5% of scale
Up to eight (8) function block outputs Resource (n/a), Transducer (n/a), LCD (n/a), Diagnostic (n/a) & Multiple Analog Output (30ms)
PID (45ms), Signal Characterizer (30ms), Arithmetic (30ms), Input Selector (30ms), Integrator (30ms),

4

Mounting & Dimensional Drawings

Reference

Dimensions:

millimeters inches

RMA803 SmartLine Fieldbus Remote Indicator

Figure 2 ­ RMA Dimensions
* Note 1: Housing adapter may not be present on all transmitter models. If the housing adapter is not present, subtract 24,5mm (0,96 inches) from the dimension specified.

RMA803 SmartLine Fieldbus Remote Indicator

5

Mounting & Dimensional Drawings TRANSMITTER ENCLOSURE CAN BE ROTATED A TOTAL OF 90O FROM THE STANDARD MOUNTING POSITION

Figure 3 ­Horizontal Wall Mounting

Figure 4 ­ Pipe Mount, Horizontal & Vertical
* Note 1: Housing adapter may not be present on all transmitter models. If the housing adapter is not present, subtract 24,5mm (0,96 inches) from the dimension specified.

6

RMA803 SmartLine Fieldbus Remote Indicator

Figure 5 – Pipe Mount, Vertical
*Note 1: Figure 5. Housing adapter may not be present on all transmitter models. If the housing adapter is not present,
subtract 24,5mm (0,96 inches) from the dimension specified.

RMA803 SmartLine Fieldbus Remote Indicator

7

Approval Certifications:

MSG CODE

Agency

FM

A

Approvals TM

(USA)

Type of Protection

Electrical Parameters

Ambient Temperature

Explosion proof Class I, Division 1, Groups A, B, C, D; T6..T4 Dust Ignition Proof: Class II, III, Division 1, Groups E, F, G; T4 Class 1, Zone 1, AEx d IIC T4 Gb Class 2, Zone 21, AEx tb IIIC T 95oC IP 66 Db

Note 1

T6: -50ºC to +65ºC
T4, T5: -50 ºC to 85ºC

Intrinsically Safe: Class I, II, III, Division 1, Groups A, B, C, D, E, F, G; T4 Class I Zone 0 AEx ia IIC T4 Ga Non-Incendive Class I, Division 2, Groups A, B, C, D; T4 Class I Zone 2 AEx nA IIC T4 Gc

Note 2 Note 1

-50 ºC to 70ºC -50 ºC to 85ºC

Enclosure: Type 4X/ IP66/ IP67

ALL

ALL

Standards: FM 3600: 2018;FM 3611: 2018; ANSI/ UL 60079-0: 2013; ANSI/ UL 60079-1:

2015; FM 3610: 2018; ANSI/ UL 60079-11: 2014; FM 3810: 2018; ANSI/ UL 60079-15: 2013; ANSI/ UL 60079-31 : 2015; FM Class 3615: 2018; FM 3616: 2011

Explosion proof:

CSA 14.2689056

Class I, Division 1, Groups A, B, C, D;T6..T4
Dust Ignition Proof: Class II, III, Division 1, Groups E, F, G; T4
Class I Zone 1 Ex db IIC T4 Gb Ex db IIC T4 Gb

Note 1

T6: -50ºC to +65ºC T4, T5: -50 ºC to 85ºC

Zone 21 Ex tb IIIC T 95oC Db

Ex tb IIIC T 95o C Db

Intrinsically Safe:

B

CSA-Canada CSA 14.2689056

Class I, II, III, Division 1, Groups A, B, C, D, E, F, G;

Note 2

-50°C to 70°C

T4

Ex ia IIC T4 Ga

Non-Incendive

CSA 14.2689056

Class I, Division 2, Groups A, B, C, D; T4

Note 1

-50°C to 85°C

Class I Zone 2 Ex nA IIC T4 Gc

Ex nA IIC T4 Gc

Enclosure: Type 4X/ IP66/ IP67

ALL

ALL

Standards: CSA C22.2 No. 0: 2015; CSA C22.2 No. 30: 2016; CSA C22.2 No. 94-M91; CSA C22.2 No. 25: 2017; CSA C22.2 No. 61010-1: 2017; CSA-C22.2No.157: 2016; C22.2 No. 213: 2017; C22.2 No. CSA 60079-0:2015; C22.2 No. 60079-1: 2016; C22.2 No. 60079-11: 2014; C22.2 No. 60079-15: 2016; C22.2 No. 60079-31: 2015;

ANSI/ ISA12.12.01-2017; ANSI/ ISA 61010-1: 2016; ANSI/ UL 60079-0: 2013; ANSI/ UL 60079-1: 2015; ANSI/ UL 60079-11: 2014; ANSI/ UL 60079-15: 2013; ANSI/ UL 60079-31: 2015 ; FM 3600: 2011; FM 3615: 2006; FM Class 3616: 2011; ANSI/ UL 913: 2015; UL 916: 2015; ANSI/ UL 12.27.01: 2017; ANSI/UL 50E: 2015

Flame-proof:

C

ATEX

II 2 G Ex d IIC T6..T4 Gb II 2 D Ex tb IIIC T 95°C Db

Note 1

T6: -50ºC to +65ºC T4, T5: -50 ºC to 85ºC

8

RMA803 SmartLine Fieldbus Remote Indicator

Intrinsically Safe:
II 2 G Ex ia IIC T4 Ga

Note 2

-50°C to 70°C

Non-Incendive II 3 G Ex ec IIC T4 Gc

Note 1

-50°C to 85°C

Enclosure: Type 4X/ IP66/ IP67

ALL

ALL

STANDARDS: EN IEC 60079-0: 2018; EN 60079-1: 2014; EN 60079-11: 2012; EN 60079-

31: 2014; EN 60079-7: 2015+A1 : 2018;

Flame-proof: II 2 G Ex d IIC T6..T4 Gb
II 2 D Ex tb IIIC T 95°C Db

Note 1

T6: -50ºC to +65ºC T4, T5: -50 ºC to 85ºC

Intrinsically Safe:
II 2 G Ex ia IIC T4 Ga

Note 2

-50°C to 70°C

C

UKEX

Non-Incendive

Note 1

-50°C to 85°C

II 3 G Ex ec IIC T4 Gc

Enclosure: Type 4X/ IP66/ IP67

ALL

ALL

STANDARDS: EN IEC 60079-0: 2018; EN 60079-1: 2014; EN 60079-11: 2012; EN

60079-31: 2014; EN 60079-7: 2015+A1 : 2018;

Flame-proof:

T6: -50ºC to +65ºC

Ex db IIC T6..T4 Gb Ex tb IIIC T 95o C Db

Note 1

T4, T5: -50 ºC to 85ºC

D

IECEx

Intrinsically Safe:

Ex ia IIC T4 Ga

Note 2

-50°C to 70°C

Non-Incendive Ex nA IIC T4 Gc

Note 1

-50°C to 70°C

Enclosure: Type 4X/ IP66/ IP67

ALL

ALL

STANDARDS: IEC 60079-0: 2017; IEC 60079-1: 2014;
IEC 60079-11: 2011; IEC 60079-7: 2017; IEC 60079-31: 2014 Flame-proof:

T6: -20°C to 65°C

Ex db IIC T6..T5 Gb Ex tb IIIC T 95o C Db

Note 1

T95°C, T5: -20°C to 85°C

Intrinsically Safe:

Ex ia IIC T4 Ga

E

SAEx

Ex ic IIC T4 Gc

Non-Incendive

Ex ec IIC T4 Gc

Enclosure: IP66/ IP67

Note 2
Note 1 ALL

-20°C to 70°C
–20°C to 85°C ALL

STANDARDS: IEC 60079-0: 2011; IEC 60079-1: 2014; IEC 60079-11: 2011;

IEC 60079-7: 2006; IEC 60079-31: 2013

Flame-proof: Ex db IIC T6..T5 Gb

Note 1

T6: 50°C to 65°C T5: -50°C to 85°C

Intrinsically Safe:

P

CCoE/ PESO Ex ia IIC T4 Ga

Enclosure: IP66/ IP67

Note 2 ALL

-50°C to 70°C ALL

STANDARDS: IEC 60079-0: 2017; IEC 60079-1: 2014; IEC 60079-11: 2011; IEC 60079-7: 2017; IEC 60079-31: 2013

Notes:

Operating Parameters:

Voltage= 12 to 42 V

Current = 25 mA

Intrinsically Safe Entity Parameters

For details see Control Drawing, 50089981.

RMA803 SmartLine Fieldbus Remote Indicator

9

Model Selection Guide
The Model Selection Guide is subject to change and is inserted into the specification as guidance only.

Model RMA800 Remote Indicator

Section 13 Page: RMA8-1
Effective Date: December 01,2023
Model Selection Guide

34-ST-16-90 Issue 22

Instructions: Make selections from all Tables Key through VI using column below the proper arrow. Asterisk indicates availability. Letter (a) refer to restrictions highlighted in the restrictions table. Tables delimited with dashes. List Price: Price equals the sum of prices for all selections made.

Key

I

II

III

IV

V

VI

RMA80_ – _ – _ _ _ – _ _ – _ _ _ _ – _ _, _ _,_ _ – 00000

KEY NUMBER Remote DE Protocol or Analog (4-20mA DC) Indicator Foundation Fieldbus

BASE MODEL

TABLE I

AGENCY APPROVALS (see data sheet for Approval Code Details)

No Approvals Required

FM Explosion proof, Intrinsically Safe, Non-incendive, & Dustproof

CSA Explosion proof, Intrinsically Safe, Non-incendive, & Dustproof

ATEX Explosion proof, Intrinsically Safe & Non-incendive

Approvals

IECEx Explosion proof, Intrinsically Safe & Non-incendive cCSAus Explosion proof, Intrinsically Safe, Non-incendive, & Dustproof-Canada & US SAEx/CCoE Explosion proof, Intrinsically Safe & Non-incendive

INMETRO Explosion proof, Intrinsically Safe & Non-incendive NEPSI Explosion proof, Intrinsically Safe & Non-incendive KOSHA Explosion proof, Intrinsically Safe & Non-incendive

CCoE Explosion proof, Intrinsically Safe & Non-incendive

TABLE II
a. Electronic Housing Material &
Connection Type
b. Protocol Compatibility
c. Customer Interface Selections

TRANSMITTER ELECTRONICS SELECTIONS

Material

Connection

Polyester Powder Coated Aluminum

1/2 NPT

Polyester Powder Coated Aluminum

M20

Polyester Powder Coated Aluminum

1/2 NPT

Polyester Powder Coated Aluminum

M20

316 Stainless Steel (Grade CF8M)

1/2 NPT

316 Stainless Steel (Grade CF8M)

M20

316 Stainless Steel (Grade CF8M)

1/2 NPT

316 Stainless Steel (Grade CF8M)

M20

Communications Protocol

DE protocol or Analog (4-20mA DC)

Foundation Fieldbus Enabled

Lightning Protection None None Yes Yes None None Yes Yes

Display Standard

External Config Buttons None (Integrated on Display)

Languages English

Advanced Advanced Advanced Advanced

None External
None External

EN, GE, FR, IT, SP, RU, TU EN, GE, FR, IT,SP, RU, TU
EN, CH, JP EN, CH, JP

TABLE III
a. Application Software

CONFIGURATION SELECTIONS
Application Software Standard Software Additional Function Blocks (Fieldbus Only: Adds PID, Char, Arith, Selector & Integ blocks)

b. Configuration

Factory Configuration Factory Standard Factory Standard

Write Protection
Disabled
Enabled

List Price equals the sum of prices
for all selections.
Selection RMA801 RMA803

0

**

A

*

B

*

C

**

D

**

K

*

E

**

F

**

G

**

H

*

P

*

A _ _ B _ _ C _ _ D _ _ E _ _ F _ _ G _ _ H _ _

** **
* * ** ** * *

_ D _ _ F _
_ _ A
_ _ D _ _ E _ _ H _ _ J

* *
* * * * *

1 _

**

2 _

*

_S

**

_T

*

10

RMA803 SmartLine Fieldbus Remote Indicator

TABLE IV

ACCESSORY SELECTIONS

Bracket Type

Material

None

None

a. Mounting Bracket

Flat Pipe Mounting Bracket Flat Pipe Mounting Bracket Wall Mounting Bracket Wall Mounting Bracket

Carbon Steel 316 Stainless Steel Carbon Steel 316 Stainless Steel

Marine Approved Mounting Bracket

316 Stainless Steel

Angle Pipe Mounting Bracket Angle Pipe Mounting Bracket

Carbon Steel 316 Stainless Steel

b. Customer Tag

Customer Tag Type No customer tag One Wired Stainless Steel Tag (Up to 4 lines 26 char/line) Two Wired Stainless Steel Tag (Up to 4 lines 26 char/line)

Unassembled Conduit Plugs & Adapters

c. Unassembled No Conduit Plugs or Adapters Required

Conduit Plugs &

1/2 NPT Male to 3/4 NPT Female 316 SS Certified Conduit Adapter

Adapters 1/2 NPT 316 SS Certified Conduit Plug

M20 316 SS Certified Conduit Plug

RMA803 RMA801

0 _ _ _ 1 _ _ _ 2 _ _ _ 3 _ _ _ 4 _ _ _ 5 _ _ _ 6 _ _ _ 7 _ _ _

** ** ** ** ** ** ** **

_ 0 _ _ _ 1 _ _ _ 2 _ _

** ** **

_ _ A0 _ _ A2 _ _ A6 _ _ A7

** nn nn mm

TABLE V
a. Additional Options

OTHER Certifications & Options:(String in sequence comma delimited (XX, XX, XX,..) None – No additional options required Certificate of Conformance Certificate of Origin Extended Warranty Additional 1 year Extended Warranty Additional 2 years Extended Warranty Additional 3 years Extended Warranty Additional 4 years Extended Warranty Additional 15 years

00

**

F3

**

F5

**

01

**

02

**

03

** b

04

**

15

**

TABLE VI MANUFACTURING SPECIALS Factory Factory Identification

0000 * *

MODEL RESTRICTIONS

Restriction

Available Only with

Letter

Table

d

IIa

m

IIa

n

IIa

b

Not Available with

Selection(s)

Table

Selection(s)

C, D, G, H _ _

IVa

1,2,3,4,6,7 _ _ _

B, D, F, H_ _

A, C, E, G _ _

Select only one option from this group

PRODUCT MANUALS Description
RMA801 Remote Meter Assembly HART / DE manual – English RMA803 Remote Meter Assembly Foundation Fieldbus manual – English
All product documentation is available at www.process.honeywell.com

Part Number 34-ST-25-62 34-ST-25-51

RMA803 SmartLine Fieldbus Remote Indicator

11

Sales and Service
For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor, contact one of the offices below.

ASIA PACIFIC
Honeywell Process Solutions, (TAC) hfs-tacsupport@honeywell.com
Australia Honeywell Limited Phone: +(61) 7-3846 1255 FAX: +(61) 7-3840 6481 Toll Free 1300-36-39-36 Toll Free Fax: 1300-36-04-70
China ­ PRC – Shanghai Honeywell China Inc. Phone: (86-21) 5257-4568 Fax: (86-21) 6237-2826
Singapore Honeywell Pte Ltd. Phone: +(65) 6580 3278 Fax: +(65) 6445-3033
South Korea Honeywell Korea Co Ltd Phone: +(822) 799 6114 Fax: +(822) 792 9015

EMEA
Honeywell Process Solutions, Phone: + 80012026455 or +44 (0)1344 656000
Email: (Sales) FP-Sales-Apps@Honeywell.com or (TAC) hfs-tac-support@honeywell.com

AMERICA’S
Honeywell Process Solutions, Phone: (TAC) 1-800-423-9883 or 215/641-3610 (Sales) 1-800-343-0228
Email: (Sales) FP-Sales-Apps@Honeywell.com or (TAC) hfs-tac-support@honeywell.com

Specifications are subject to change without notice.

For more information To learn more about SmartLine RMA Remote Meter, visit https://process.honeywell.com/ Or contact your Honeywell Account Manager

Process Solutions Honeywell 1250 W Sam Houston Pkwy S Houston, TX 77042
Honeywell Control Systems Ltd Honeywell House, Skimped Hill Lane Bracknell, England, RG12 1EB
Shanghai City Centre, 100 Jungi Road Shanghai, China 20061
https://process.honeywell.com/

34-ST-03-90 December 2023 ©2023 Honeywell International Inc.

Documents / Resources

Honeywell RMA803 Smart Line Remote Field Bus Indicator [pdf] Owner's Manual
RMA803 Smart Line Remote Field Bus Indicator, RMA803, Smart Line Remote Field Bus Indicator, Remote Field Bus Indicator, Field Bus Indicator, Bus Indicator

References

Leave a comment

Your email address will not be published. Required fields are marked *