FIRE CONTROL INSTRUMENTS FC-72 Series Fire Alarm System Instruction Manual

FC-72 Series Fire Alarm System

Product Specifications

  • Product Name: FC-72 Series Fire Alarm System
  • Part Number: 9000-0007 Version 5.1
  • Manufacturer: [Manufacturer Name]
  • Location: 301 2nd Ave. Waltham, MA 02451-1133 USA
  • Telephone: 781-487-0088
  • Fax: 781-370-4132

Product Usage Instructions

1. Functional Switches

Refer to the user manual for specific instructions on the
functional switches.

2. Ground Fault Detection

The system is equipped with ground fault detection for safety
purposes. Ensure proper grounding during installation.

3. Short Circuit Detection

The system has short circuit detection capabilities. Avoid short
circuits in the wiring to prevent malfunctions.

4. Jumpers and Matrix

Use the provided jumpers and matrix according to the wiring
diagram in the manual for proper configuration.

5. Municipal Box Connection

Connect the system to the municipal box as per the instructions
provided in section 5 of the manual.

6. Auxiliary Notification Appliance Circuits

Follow the guidelines in section 6 for setting up auxiliary
notification circuits.

7. Notification Appliance Circuits

Properly wire the notification appliance circuits as detailed in
section 7 of the manual.

8. Common Alarm Dry Contacts

Utilize the common alarm dry contacts for specific alarm
functions as required.

9. Common Trouble Dry Contacts

Refer to section 9 for information on the common trouble dry
contacts and troubleshooting guidance.

10. Remote Trouble Indicator

Set up and use the remote trouble indicator according to the
instructions provided in the manual.

11. Earth Ground

Ensure proper earth grounding to maintain system safety and
functionality.

12. Polarity Reversal Output

Refer to section 12 for details on polarity reversal output and
its application.

13. Auxiliary Power Output

Connect devices requiring auxiliary power to the designated
output following the manual’s guidelines.

14. Smoke Detector Output

Use the smoke detector output as specified in section 14 for
smoke detection applications.

Frequently Asked Questions (FAQ)

Q: How do I troubleshoot issues with the notification appliance
circuit?

A: Refer to section 7.2 of the manual for troubleshooting
guidance specific to the notification appliance circuit.

Q: What is the purpose of the presignal feature in the
auxiliary notification appliance circuits?

A: The presignal feature allows for pre-warning notifications
before full alarm activation, providing additional safety
measures.

“`

FC-72 SERIES FIRE ALARM SYSTEM
INSTRUCTION/OPERATING MANUAL

Copyright © 1988 Published in the U.S.A. All rights reserved

Part Number: 9000-0007 Version 5.1

Serial Number____________________ 301 2nd Ave. Waltham, MA 02451-1133 USA TEL: 781-487-0088 FAX: 781-370-4132

TABLE OF CONTENTS

Section

Page

IMPORTANT INFORMATION …………………………………………………………………………………………..2

Diagram 1. BMFC-6 Diode Matrix……………………………………………………………………………………..5

Diagram 2. BMFC-6 Test Points ……………………………………………………………………………………….6

1.0 Functional Switches…………………………………………………………………………………………………..7

2.0 Ground Fault Detection………………………………………………………………………………………………7

3.0 Short Circuit Detection……………………………………………………………………………………………….7

4.0 Jumpers and Matrix …………………………………………………………………………………………………..8

5.0 Municipal Box Connection ………………………………………………………………………………………….8

5.1 Troubleshooting the City Box Circuit ………………………………………………………………………….9

6.0 Auxiliary Notification Appliance Circuits ………………………………………………………………………..9

6.1 Presignal Feature……………………………………………………………………………………………………9

7.0 Notification Appliance Circuits …………………………………………………………………………………….10

7.1 Wiring

……………………………………………………………………………………………………………10

7.2 Troubleshooting the Notification Appliance Circuit ……………………………………………………….11

7.3 Notification Appliance Wiring Estimator ……………………………………………………………………..12

8.0 Common Alarm Dry Contacts ……………………………………………………………………………………..12

9.0 Common Trouble Dry Contacts …………………………………………………………………………………..12

10.0 Remote Trouble Indicator …………………………………………………………………………………………13

11.0 Earth Ground ………………………………………………………………………………………………………….13

12.0 Polarity Reversal Output…………………………………………………………………………………………..13

13.0 Auxiliary Power Output …………………………………………………………………………………………….13

14.0 Smoke Detector Output ……………………………………………………………………………………………14

15.0 Zone Alarm Dry contacts ………………………………………………………………………………………….14

16.0 Initiating Circuits ……………………………………………………………………………………………………..14

16.1 Zone Detector Module (ZDM) …………………………………………………………………………………14

16.2 Verification Zone Detector Module (VZM) …………………………………………………………………16

16.3 Double Density Zone Detector Module (ZDM-D) ……………………………………………………….17

16.4 Sprinkler Supervisory Service ………………………………………………………………………………..18

17.0 Remote Zone Annunciation ……………………………………………………………………………………..19

17.1 Remote Zone Annunciation with ZDM or VZM Module ……………………………………………….19

17.2 Remote Zone Annunciation with ZDM-D Module ……………………………………………………….19

18.0 Accessory Zone Output ……………………………………………………………………………………………19

19.0 Standby Battery Connections ……………………………………………………………………………………20

20.0 Power Supply………………………………………………………………………………………………………….20

21.0 Fuses ………………………………………………………………………………………………………………….20

22.0 Locating a Trouble …………………………………………………………………………………………………..20

23.0 Central Station Transmitter Connections …………………………………………………………………….22

24.0 Proprietary Protective Signaling System Connections ………………………………………………….23

25.0 FCI Approved UL Listed (Multiple Listed), Compatible Two-wire Smoke Detectors …………..24

25.1 Model PSD/CPD Smoke Detector wiring information …………………………………………………24

25.2 Model SBS Smoke Detector wiring information …………………………………………………………26

25.3 Model 301 Smoke Detector wiring information ………………………………………………………….26

9000-0007

Page 1 of 28

IMPORTANT INFORMATION
READ THE FOLLOWING INFORMATION BEFORE INSTALLING:
The contents of this manual are important, and the manual must be kept with the fire alarm control panel at all times. If building ownership is changed, this manual, including any testing and maintenance information, must be passed along to the new owner(s).
The fire alarm control panel is part of a system. Manuals and instructions for other devices forming part of the system should be kept together. Purchasers who install this system for use by others must leave the instructions with the user. A copy of these instructions is included with each product and is available from the manufacturer.
This equipment is Listed by various listing agencies for use in fire alarm systems. Use only components which are compatible with the FCI system. The installation MUST be in accordance with the instructions in this manual.
THEREFORE: · DO NOT deviate from the procedures described in this manual. · DO NOT assume any details not shown in the instructions. · DO NOT modify any electrical or mechanical features. · DO comply with all codes and standards set forth by the authority having jurisdiction.
The term “Authority Having Jurisdiction” has become a standard term in the fire alarm industry. An acceptable definition of “Authority Having Jurisdiction” is:
Systems installed in the USA fall under the jurisdiction of some authority. In some areas this may be a local fire department; in other areas it may be a building inspector, insurance firm, etc. Different authorities may have their own local requirements for the way the fire alarm system is installed and used. Most local authorities base their requirements on the NFPA codes, but there may be important differences. You must install this system in the way in which the authority having jurisdiction requires. If you do not know which authority has jurisdiction in your area, contact your local fire department or building inspector for guidance.
It is important that you tell users to be aware of any requirements defined by the Authority Having Jurisdiction.
The installation MUST be in accordance with the following standards: · National Fire Alarm Code (NFPA 72) · National Electrical Code (NFPA 70) · Life Safety Code (NFPA 101)
Touching components that are improperly installed, applied or operated could be hazardous and possibly fatal. Short circuits could cause arcing that could result in molten metal injuries. Therefore, only qualified technicians familiar with electrical hazards should perform checkout procedures. Safety glasses should be worn, and test equipment used for voltage measurements should be designed for this purpose and should be in good working order.
WARNING – Improper installation, application, or operation can result in death or serious injury.

ENVIRONMENTAL CONSIDERATIONS:
It is important that this equipment be operated within its specifications:

Recommended operating temperature range: Absolute maximum operating temperature range:

60 to 80o F (15 to 27o C) 32 to 120o F (0 to 49oC)

Operating humidity:

not to exceed 85%, non-condensing at 90o F (32o C)

Operating this equipment within the recommended temperature range will extend the useful life of the system

standby batteries.

Page 2 of 28

9000-0007

INSTALLATION CONSIDERATIONS:
Check that you have all the equipment you need to make the installation. Follow the field wiring diagrams and installation notes in this manual.
Install the equipment in a clean, dry environment (minimal dust). Avoid installing equipment where vibrations will occur.
Remove all electronic assemblies prior to drilling, filing, reaming, or punching the enclosure. When possible, make all cable entries from the sides, being careful to separate the power limited conductors from the non-power limited conductors. Before making modifications, verify that they will not interfere with battery, transformer and printed circuit board location.
Do not over-tighten screw terminals. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
Disconnect all sources of power before servicing, removing, or inserting any circuit boards. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized.
WIRING CONSIDERATIONS:
This fire alarm control panel contains power limited circuits. You cannot connect external sources of power to these circuits without invalidating their approval.
Verify that wire sizes are adequate for all initiating device and notification appliance circuits. Most devices cannot tolerate more than a 10% drop from the specified device voltage.
The installer must make sure that the wiring and devices installed in the system meet the current National Electrical Code, NFPA 70, and all applicable state and local building code requirements.
Use the conductor size and type required by local codes. (see NFPA 70, Article 760). Wiring resistance must not be more than that shown on the field wiring diagrams.
To reduce errors and help in servicing the system, all conductors should be tagged or otherwise coded and logged at installation to identify circuit assignment and polarity. If the conductors are logged with a code, keep the log that explains the code with the manual, so that it is available to other people working on the panel.
Like all solid state electronic devices, this system may operate erratically or be damaged when subjected to lightning induced transients. Although no system is completely immune to lightning transients and interference, proper grounding will reduce susceptibility. We do not recommend the use of overhead or outside aerial wiring due to the increased susceptibility to nearby lightning strikes. Consult with the FCI Technical Support Department if any problems are anticipated or encountered.
To prevent the spread of fire, use proper patching materials to areas where system wiring passes through fire-rated walls or floors.
DO NOT RUN LINE VOLTAGE IN THE SAME RACEWAYS AS FIRE ALARM CONDUCTORS.
WARNING – Several different sources of power can be connected to this fire alarm control panel. Disconnect all sources of power before servicing. The control panel and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the panel is energized. Failure to do so can damage circuits. Do not attempt to install, service, or operate this control panel until this manual is read and understood.
WHEN APPLYING POWER TO THIS FIRE ALARM CONTROL PANEL, CONNECT THE AC LINE VOLTAGE FIRST, THEN CONNECT THE BATTERIES.
OTHER CONSIDERATIONS:
The equipment was tested according to EC directive 89/336/EEC for Class A equipment and was verified to the limits and methods of EN 55022.
CAUTION – System Reacceptance Test: To ensure proper system operation, this product must be tested in accordance with NFPA 1996, Chapter 7 after any change, addition or deletion of product components, or after any repair to system wiring. All components, circuits, or system operations known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, should also be tested and proper system operation verified.

9000-0007

Page 3 of 28

FCC WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for Class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
If these instructions are not clear, or if additional information or clarification is needed, please consult your local authorized Fire Control Instruments, Inc. distributor.
Because of design changes and product improvements, the information in this manual is subject to change without notice. FCI reserves the right to change hardware and/or software design, which may subsequently affect the contents of this manual. FCI assumes no responsibility for any errors that may appear in this manual.
Neither this manual nor any part of it may be reproduced without the advance written permission of Fire Control Instruments, Inc.

FIRE ALARM SYSTEM LIMITATIONS
An automatic fire alarm system – Typically made up of smoke detectors, heat detectors, manual pull stations, audible/visual warning devices, and a fire alarm control panel with remote notification capability – can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.

Any fire alarm system may fail for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second floor smoke detector, for example, may not sense a first floor or basement fire. Furthermore, all types of smoke detectors – both ionization and photoelectric types – have sensing limitations. No type of smoke detector can sense every kind of fire caused by carelessness and safety hazards such as smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson.

Audible/visual warning devices such as horns, bells or strobes, may not alert people if these devices are located on the other side of closed or partly closed doors or are located on another floor of the building.

A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time.

Rate-of-rise heat type detectors may be subject to reduced sensitivity over time. For this reason, the rate-ofrise feature of each heat detector should be tested at least once per year by a qualified fire protection specialist.

Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with this control panel.

Telephone lines required to transmit alarm signals from the premise to a central monitoring station may be out of service or temporarily disabled.

The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices and system wiring should be tested and maintained by professional fire alarm installers following written procedures supplied with each device. System inspection and testing should be scheduled monthly or as required by National and/or local fire codes. Adequate written records of all inspections should be kept.

While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire

insurance!

CAUTION

To keep your fire alarm system in excellent working order, ongoing

maintenance is required per the manufacturer’s recommendations and UL

and NFPA Standards. At a minimum, the requirements of Chapter 7 of

NFPA 72, The National Fire Alarm Code, shall be followed. A preventive

maintenance agreement should be arranged through the manufacturer’s

local representative. Though smoke detectors are designed for long life,

they may fail at any time. Any smoke detector, fire alarm system or any

component of that system which fails shall be repaired or replaced

immediately.

Page 4 of 28

9000-0007

Page 5 of 28

9000-0007

Zone Alarm Output

ZMC-6 AND/OR BMFC-6

MINI JUMPER MATRIX (NEW)

Diode Jumper Position

Zone B 3,5, Etc.

Zone A 3,5, Etc.

Function

J1A

J1B

ALARM WILL ACTIVATE MASTER BOX OUTPUT ONLY

J2A

J2A

ALARM WILL ACTIVATE BUS 2

J3A J4A J5A J6A

J3B J4B J5B J6B

ALARM WILL ACTIVATE A/V SIGNAL CIRCUITS. REVERSING RELAY AND MASTER BOX OUTPUT
ALARM WILL ACTIVATE AUXILIARY ALARM OUTPUT
ONLY (TERM. 3-5)
ALARM WILL ACTIVATE BUS 5
ALARM WILL ACTIVATE BUS 6

4 Pin “JPS” Matrix J8

Zone Alarm Output

J6

J7

J1

4 Pin “JPS” Matrix (old style)

BMFC-6 Diode Matrix

Master Box Activate

Term 5 Activate

Term 3 Activate

Alarm Bus Reversing

(Signal Relay) Relay

Activate

Activate

Bus #3 (J7) CR22
Bus #6

CR23

CR24

Bus #5

Bus #1 (J1) CR25
Bus #2
Bus #4 (J6)

CR26

CR27

Diodes Shown in Standard Configuration

BMFC-6 TEST POINTS
(For location of a specific trouble)
INSTRUCTIONS:
Place negative ( – ) lead of DC voltmeter on Terminal 30 and positive (+) meter lead on indicated test point.

BMFC-6 Test Points

TEST POINT
TP-1 TP-2 TP-3 TP-4 TP-5 LED 4
LED 5
TP-8 TP-11 TP-12 TP-13 TP-14 TP-15

CIRCUIT
Zone 1 Zone 2 Transfer relay Card supervision Short circuit Positive Ground Fault Negative Ground Fault RTI supervision Master Box Ground Fault Pwr Supply Fault Gen. Syst. Trbl Supv. of K4 relay contacts

SATISFACTORY VOLTAGE READINGS Zero VDC Zero VDC Zero VDC Zero VDC Zero VDC LED OFF
LED OFF
Zero VDC Zero VDC Zero VDC Zero VDC Zero VDC Zero VDC

UNSATISFACTORY READINGS
1.2 to 24 VDC 1.2 to 24 VDC 1.2 to 24 VDC 1.2 to 24 VDC 1.2 to 24 VDC LED lit
LED lit
1.2 to 24 VDC 1.2 to 24 VDC 1.2 to 24 VDC 1.2 to 24 VDC 1.2 to 24 VDC 1.2 to 24 VDC

NOTE: All the above voltages are approximate and it is entirely possible to have a trouble condition with readings other than shown. If your voltage readings differ and you cannot solve your trouble condition by consulting this manual, please contact your local authorized FCI Distributor.

Page 6 of 28

9000-0007

1.0 FUNCTIONAL SWITCHES

1.1 BMFC Switches
Operational switches located on the BMFC basic fire card are as follows:
· Trouble Silence Switch (Fig. 1) This switch, when operated, will silence the System Trouble audible sounder. Upon correction of the trouble condition, the audible will sound again to indicate that the switch should be returned to the normal position.

· Battery/Bell Test Switch (Fig. 1) This switch, when operated, de-energizes the Transfer Relay disconnecting the power supply from the panel circuitry. It also energizes the alarm relay operating all local notification appliances from the stand-by batteries. Operating this switch will not reverse telephone lines or activate the city box output.

· Lamp Test Switch (Fig. 1) This switch, when operated, will light all red LED alarm indicators, all yellow LED trouble indicators on zone modules, and all Remote Zone Annunciators (RZAs). All alarm indicators are supervised.

· Reset Switch (Fig. 1) This switch, when operated, resets all zones from the alarm condition, as well as interrupting the Smoke Detector Power Output to reset the detectors. It will also cause all the yellow LED zone trouble indicators to light.

· City Box Disconnect Switch (Fig. 1) This switch, when operated, will disable the City Box Output and/or Polarity Reversal Output (JRR must be cut for Polarity Reversal disabling). The yellow LED above the switch will light, and a System Trouble will occur when the switch is in the OFF position, or when the control is in the alarm mode. The yellow LED will remain lit until the master box and the control are reset.
1.2 Zone Module Switches
Operational switches mounted on the zone modules are as follows: · Zone Maintenance Switch – Each zone has a maintenance switch. Operation of this switch will disconnect
the zone alarm output. This will also cause both a System and a Zone Trouble. Other zones are not affected by the operation of any one zone maintenance switch.

2.0 GROUND FAULT DETECTION
External wiring leaving the FC-72 is supervised for ground faults. When a ground is present on the external wiring the yellow “GROUND FAULT” LED will light and a System Trouble will occur. Separate positive (LED 4) and negative (LED 5) indicators are provided to determine the type of ground fault present. This will help when trouble shooting. To locate the source of the ground fault, remove each external wire from the FC-72 one at a time, then connect a voltmeter to Terminals 24 and 30. Normal voltage should be from 5.5 to 6.5 VDC. If not, check the field wiring.
NOTE: Terminal 24 of the FC-72 must be connected to an earth ground per Article 760 of the National Electrical Code. Conduit ground is not acceptable. Failure to make this connection will result in a reduction in lightning protection.

GROUND FAULT

SHORT CIRCUIT FAULT

TROUBLE NORMAL

BATT BELL TEST

LAMP RESET

SILENCE TEST TEST

ON

C

B

I

O

T

X

Y

OFF

Figure 1

3.0 SHORT CIRCUIT DETECTION
The notification appliance circuit wiring Terminals (6-13) are supervised for short circuits across either notification appliance circuit. When a short circuit is present the yellow “SHORT CIRCUIT” LED will light, and a System Trouble will occur. See Section 7.

9000-0007

Page 7 of 28

4.0 JUMPERS AND JUMPER MATRIX
The jumpers and jumper matrix for the BMFC are shown in Table 1.
Table 1

JUMPER J-11 J-12 J-13 J-10A,B
J-RA,B
JRR J-RTI JT
JS3 JL J20 J5 J22 JS5 J31-34

FUNCTION Cut if TCM-6, BMC-6 or CCM-6 module is installed. Cut when Reversing Relay is being used to transmit an alarm via telephone lines. Cut if RTI (Remote Trouble Indicator)is NOT used. Install to the right of the last zone in system unless followed by an auxiliary module (ADAM, SRB, etc.) Remove this jumper on each zone where an RZA (Remote Zone Annunciator) is used or when a ZDM-D is used. Cut if the City Box Switch is required to disable the Polarity Rev. Output in alarm. Cut if RTI is used–jumper located next to Terminals 17-19. Cut to transmit a system trouble to Remote Station via telephone lines. (Terms. 25 & 26). Cut for supervision of Terminals 3 & 4. Cut if K2 Reversing relay is to be non-latching Cut for remote reset function. Factory use only Cut if Alarm Bus 6 is being used. Cut for supervision of Terminals 4 & 5. Install when using a ZDM-D module.

DIODE JUMPER

FUNCTION

POSITION

ZONES

ZONES

1, 3, 5 etc. 2, 4, 6 etc.

JIA

JIB

Alarm activates master box output only.

J2A

J2B

Alarm activates bus 2.

J3A

J3B

Alarm activates notification appliance circuits, reversing relay and city box circuit.

J4A

J4B

Alarm activates aux. alarm output only. (Terminals 3 – 5)

J5A

J5B

Alarm activates Bus 5.

J6A

J6B

Alarm activates Bus 6.

NOTE: If Alarm Busses 2 or 5 are used:

Cut CR71 and CR72 on BMFC,

Cut CR5 and CR22 on ZMC

5.0 MUNICIPAL BOX CONNECTION
BMFC Terminals 1 and 2 are for the supervised connection of a local energy city box or solenoid. The alarm output on these terminals is 20 VDC for municipal box, and 24 VDC for solenoid. A “CITY BOX DISCONNECT” Switch is provided for use when testing and servicing the control. When the switch is in the OFF position, operation of the master box/solenoid is inhibited, the yellow LED above the switch will light, and a System Trouble will occur.
When a solenoid is connected, the switch will inhibit the alarm dry contacts from transferring on alarm if Jumper JRR DISC. is cut.

NOTE: This output is is fused at 4 amps. Do not exceed 3 amps. The output voltage depends on which device is connected to the circuit. A minimum battery voltage of 23.3 VDC is required to operate the solenoid circuit.

To connect the master box or solenoid, remove the 220 ohm, 5 watt resistor from Terminals 1 and 2. DO NOT connect this resistor to the master box or transmitter. Leave it in the bottom of the control cabinet for trouble shooting purposes. Connect master box or solenoid wiring to Terminals 1(+) and 2 ( – ). For solenoid, verify that R24 is replaced by a fuse, 4 amps @ 24 VDC. For master box, verify that field wiring does not exceed 35 ohms. For solenoid field wiring, refer to the table. Check with a meter before making final connections. To disable the city box switch, consult the factory.

Page 8 of 28

9000-0007

FM Approved, UL Listed solenoids are as follows:

Approved/ Listed FM, UL FM FM FM

Solenoid Model LV2LBX25 T8210A107 R8210A107 8210A107

Current Max. Line

@ 24 VDC Res.

0.458 A 2.0 ohms

0.70 A

0.7 ohms

0.70 A

0.7 ohms

0.70 A

0.7 ohms

NOTE: Wiring to a municipal city master box must comply with NFPA 72 “Auxiliary Fire Alarm Systems.”

NOTE: Factory Mutual approves only Class A, Style D initiating circuits when using a solenoid for Deluge/Preaction Service
5.1 Troubleshooting the City Box Circuit

5

UL LISTED

AUDIBLE/VISIBLE

NOTIFICATION

4

APPLIANCES

3

ANY LISTED LOCAL ENERGY CITY BOX
MAX. TRIPPING COIL 14.5 OHM MUST COMPLY WITH NFPA 72 MAX. LINE RES. 35 OHMS
SUPV. CURRENT .0016 A.
MAX. CURRENT .510 A.

2
1 SUPERVISED WIRING

Figure 2

PROBLEM “CITY BOX” LED Lit.

CAUSE
Control in alarm. Switch in the ON position. Master Box not reset. Open in master box coil wiring

ACTION TO BE TAKEN Reset Control.
Return the switch to the OFF position. Reset the master box. Replace EOL resistor of master box. If the LED restores, check for coil opens.

6.0 AUXILIARY ALARM OUTPUTS

BMFC Terminals 3, 4, and 5 comprise two auxiliary alarm outputs. These outputs are a function of the jumper

matrix; the most common use is with presignaling systems. These outputs may be configured for either

supervised or non-supervised operation.

Terminal 4 is negative ( – ) and Terminals 3 and 5 are positive (+). Connect only the notification appliances

listed in FCI Addendum, P/N 9000-0427 to these terminals per Figure 2:

To make any zone activate the Auxiliary Notification Appliance Outputs, Install a J4A, J4B diode jumper to the

right of each zone used for this output.

To supervise these outputs, cut Jumper JS3 on the BMFC for the supervision between Terminals 3 & 4 and/or

cut Jumper JS5 on the BMFC for supervision between Terminals 4 & 5.

(This output is only supervised to the first appliance–DO NOT exceed one appliance per output)

The output parameters of the Auxiliary Notification Appliance Output are as follows:

Voltage

24 VDC (nominal)

Max. ripple voltage .071 VAC (max.)

Standby current

.002 amp.

Alarm current

0.5 amp. (max.)

Power Limited

6.1 Presignal Feature
To configure the FC-72 for presignaling, install the J3A, J3B diode jumper for general alarm, as described in Table 1. Install J4A, J4B diode jumper to the right of all presignaling zones. (See Table 1). Then connect general alarm notification appliances to the common alarm output, Terminals 6 through 13. Connect the presignal appliance to Terminals 3, 4, and 5 using the directions above. Do not exceed 0.5 amp. per output. If more than one device is used, the additional device(s) will not be supervised.

NOTE: A presignaling notification appliance and its wiring must be installed within the same room as the control. Also, the notification appliance circuit conductors must be installed in conduit or have equivalent protection against mechanical injury and tampering.

9000-0007

Page 9 of 28

7.0 NOTIFICATION APPLIANCE CIRCUITS
The voltage on these circuits is 24 VDC (nominal). Connect only the UL Listed notification appliances shown in FCI Addendum, P/N 9000-0427 to these circuits. Follow the installation instructions furnished with each appliance.
The BMFC contains two notification appliance circuits, each rated at 1.75 amps, which operate only in unison. Terminals 6, 7, 8, and 9 are for Circuit 1, and Terminals 10, 11, 12, and 13 are for Circuit 2. Each circuit is individually protected and supervised for opens, grounds and shorts.
The output of these circuits is controlled through a notification appliance circuit module. There are four standard modules that can be used with the FC-72 notification appliance circuits.
· BCM-6, Bell Card Module – Provides a continuous, non-coded output on the notification appliance circuits.
· TCM-6, Temporal Coder Module – Provides a Temporal Pattern Emergency Evacuation Signal per ANSI S3.41
· BMC-6, Master Coder Module – Provides an adjustable on-off duty cycle (march time pattern).
· CCM-6, Common Coder Module – Provides a variety of common coded signals, programmable in the field.

The output parameters of the notification appliance circuits are as follows:

Voltage

24 VDC (nom.)

Max. ripple voltage

.071 VAC (RMS)

Supervisory current

.0017 amp.

Alarm Current

1.75 amp.

Power Limited

Supervised

Each notification appliance circuit module has a yellow LED which indicates the following trouble conditions: · An open in the notification appliance circuit wiring. · An open in the Signal Relay (K3) coil. · An open overload device in either notification appliance circuit.

7.1 Wiring
Class A, Style Z Wiring Notification Appliance Circuit 1 – Remove the 3.9K ohm, 1/2 watt, resistor from Terminals 6 ( – ) and 9 (+). Connect resistor to Terminals 7 and 8. Connect field wiring to terminals per Figure 3.

NOTE: J-11 Must be cut when using coder modules TCM-6, BMC-6 OR CCM-6) on the BMFC.

13 + 12
11 10 –

3.9K 1/2 W.
EOL

9+ 8
7 6-

3.9K 1/2 W.
EOL

NOTE: Use only appliances specified above. BE SURE TO OBSERVE POLARITY
Figure 3

Page 10 of 28

3.9K 1/2 W.
EOL

13 + 12 11 10 –

3.9K 1/2 W.
EOL

9+ 8 7 6-

NOTE: Use only appliances specified above. BE SURE TO OBSERVE POLARITY
Figure 4
9000-0007

Notification Appliance Circuit 2 – Remove the 3.9K ohm, 1/2 watt, resistor from Terminals 10 ( – ) and 13 (+), and connect resistor to Terminals 11 and 12. Connect field wiring to terminals per Figure 3.
Class B, Style Y Wiring Notification Appliance Circuit 1 – Remove the 3.9K ohm, 1/2 watt, resistor from Terminals 6 ( – ) and 9 (+), then connect it in parallel within the last device on the circuit. Connect field wiring to these terminals per Figure 4. Be sure to observe polarity, and check all wiring prior to connection.
Notification Appliance Circuit 2 – Follow the same procedure as above, except Terminal 10 is negative ( – ), and Terminal 13 is positive (+).
NOTE: Divide the load evenly between both notification appliance circuits. Be sure to observe polarity, and check all wiring prior to connection.

7.2 Troubleshooting the Notification Appliance Circuit

PROBLEM Yellow LED on TCM/BCM is lit
“SHORT CIRCUIT” LED lit.
Notification appliances will not operate

CAUSE
1. Open in ckt. wiring. 2. PTC open. 3. Relay coil defective
1. Short circuit in the field wiring 2. Non-polarized appliances used. 1. Reversed polarity on appliance. 2. PTC open. 3. Signal relay

ACTION TO BE TAKEN Remove the wiring and check for opens. Hold the System Reset switch down for five (5) seconds. Check the coil for 700 ohms resistance. Replace if necessary. Check notification appliance circuits for shorts. (See section on “SHORT CIRCUIT” LED)
Use only approved appliances.
Correct polarity of notification appliances Hold the System Reset switch down for five (5) seconds

9000-0007

Page 11 of 28

7.3 Notification Appliance Circuit Wiring Estimator
Use the chart (Figure 5) to determine the required wire size for each notification appliance circuit. 1) Compute the required current. (Number of appliances multiplied by appliance current = amperes) 2) Compute the distance in feet from panel to the last appliance. 3) Locate the total appliance load (amperes) on the vertical axis of the chart. Locate the wire length (feet) on the horizontal axis of the chart. Find where they intersect. 4) Read the wire size in AWG on the curved line to the right of the point of intersection.
For wire lengths less than 100 feet, use 18 AWG minimum.

Figure 5
8.0 COMMON ALARM DRY CONTACTS
These contacts transfer and latch whenever the reversing relay is energized. Terminal 16 is common, 15 is normally open and 14 is normally closed. See Figure 6. Reversing relay K2 (P/N 4500-0024) must be installed in the socket provided.
These contacts are rated 5 amps @ 26 VDC (resistive). Intended for connection to circuits powered from a Listed power limited source of supply.

16 COM 15 N/O 14 N/C

20 21 22
C N/O N/C RELAY K1 MUST BE INSTALLED

Figure 6 Common Alarm Dry contacts

Figure 7 System Trouble Dry Contacts

9.0 COMMON TROUBLE DRY CONTACTS
Whenever a System Trouble occurs, the trouble dry contacts will transfer. Terminal 20 is common, 21 is normally open, and 22 is normally closed. See Figure 7. the contacts are rated 5 amps @ 26 VDC (resistive). Trouble relay K1 (P/N 26592) must be installed in the socket provided. Intended for connection to circuits powered from a Listed power limited source of supply.

Page 12 of 28

9000-0007

10.0 REMOTE TROUBLE INDICATOR CONNECTION
Terminals 17, 18 and 19 are for the connection of the optional 3-wire remote trouble indicator (RTI). The RTI is supervised for grounds and opens. Should an open occur, the system will indicate trouble.
To use the RTI, install trouble relay K1 (4500-0024). Cut the jumper (JRTI) which is located to the LEFT of Terminals 17, 18 and 19. Connect the RTI per Figure 8.
Circuit ratings: 24 VDC @ .004 amps max. Power limited.
11.0 EARTH GROUND
The FC-72 control must be connected to (earth) ground, per Article 760 of the National Electrical Code. The connection is made to Terminal 24. This connection will provide maximum protection in the event of lightning, transients, or electrical disturbance. Failure to connect a ground will result in a reduction in lightning protection. MINIMUM wire size 14 AWG.

RED

19

WHITE 18 GREEN
17

CUT JUMPER ON BOARD NEXT TO TERMINALS. RELAY K1 MUST BE INSTALLED
Figure 8 Remote Trouble Indicator

RELAY K2 MUST BE

INSTALLED. CUT JUMPER J12

CONNECT TO

SEPARATE

TELE. LINES

EARTH GROUND

PER ARTICLE 760 OF THE NATIONAL

24 25 26

ELECTRICAL CODE. PANEL NEUTRAL

+-

OR CONDUIT GROUND IS NOT

ACCEPTABLE.

Figure 9 Earth Ground/Polarity Reversal

12.0 POLARITY REVERSAL OUTPUT

Terminals 25 and 26 are for the connection of a polarity sensitive remote station receiver via leased telephone

lines. The output is 24 VDC, current limited to 0.13 amp. Reversing relay K2 (4500-0024) must be installed

in the socket provided. Cut Jumper J12 and connect the telephone lines to Terminals 25 (+) and 26 ( – ). In the

alarm condition the relay will operate, reversing the polarity on the telephone lines (Term. 25 will now be

negative and Term. 26 will be positive).

To transmit a trouble signal to the remote station, cut Jumper JT, which is located above relay K1. This will

remove power from the output in the event of a System Trouble, but will not inhibit an alarm signal. Relay K1

must be installed in order to transmit a trouble. The output parameters for the Polarity Reversal circuit are

as follows:

Voltage

19.9 VDC minimum

26.4 VDC maximum

Max. ripple voltage .071 VAC (RMS)

Standby Current

.010 amp. @ 24 VDC

Alarm Current

.130 amp.

Power limited

Supervised

13.0 AUXILIARY POWER OUTPUT

Terminals 29 (+) and 30 ( – ) supply a continuous 24

VDC nominal output for use only with the Model

301DH duct detector remote test station. This output

is NOT interrupted by the reset switch. See Figure 10.

Voltage

24 VDC (nominal)

Max. ripple voltage .071 VAC (RMS)

Current

1.75 amp. max.

Power limited

Unsupervised

44 43 31 30 29
EXT. OUTPUT COMMON (NEG) SMOKE DETECTOR OUTPUT
TO STANDBY BATTERY STANDBY BATTERY FUSED AT 6 AMPS.

Figure 10 Power Outputs

9000-0007

Page 13 of 28

14.0 SMOKE DETECTOR OUTPUT

Terminals 30 ( – ) and 31(+) are only for the power connection of 4-wire Model SPB-24 projected beam smoke

detectors. Operation of the reset switch interrupts this output to reset all detectors. See Figure 10.

Voltage

24 VDC (nominal)

Max. ripple voltage .071 VAC (RMS)

Current

1.75 amp.

Power limited

Unsupervised

Two-wire photoelectric or ionization smoke detectors must not be connected to these terminals. See Section

16.1 on the ZDM.

15.0 ZONE ALARM DRY CONTACTS
A set of Form “C” dry contacts rated 2 amps at 24 VDC (resistive), are provided for each zone when a ZDM or VZM is installed. They are intended for connection to circuits powered from a Listed power limited source of supply. Terminal 35 is common, 34 is normally open, and 33 is normally closed. See Figure 11. These contacts transfer only when there is an alarm on that individual zone, and they will remain in the alarm condition until the control is reset. The position of the zone maintenance switch WILL NOT AFFECT THESE CONTACTS. Jumpers in the matrix are not required to operate these contacts.

35 34 33 C N/O N/C Figure 11 Zone Dry Contacts

16.0 INITIATING CIRCUITS
16.1 Zone Detector Module (ZDM)
Terminals 37 through 40 are provided for each zone, and will accept U.L. Listed normally open initiating devices such as heat detectors, thermostats, and manual stations. See Figures 12 and 13.
FCI approved, U.L. Listed compatible, two-wire photoelectric and ionization smoke detectors that use the supervisory current from the initiating circuit as their power source can be used. Each zone is capable of powering a specified number of FCI approved detectors. See FCI Addendum, P/N 9000-0427 for a list of approved detectors.
One ZDM is required for each active zone and will accept either Class A, Style D or Class B, Style B 4-wire or 2-wire circuits. Each zone module has an individual maintenance switch as well as a supervised red “ALARM” LED and a yellow “TROUBLE” LED.
CAUTION: Fire Control Instruments, Inc. does not warrant the integrity of systems using FCI control panels and two-wire smoke detectors that have not been tested and approved by FCI. See Addendum, P/N 9000-0427

3.9K EOL

+

37

38

39

40

3.9K EOL

+

37

38

39

40

+

37 38 39 40

+

37 38 39 40

UL LISTED N/O DEVICES

UL LISTED N/O DEVICES

UL LISTED N/O DEVICES
Figure 12

UL LISTED N/O DEVICES

3.9K EOL

3.9K EOL

Figure 13

Page 14 of 28

9000-0007

The output parameters for the initiating circuits with ZDM modules are as follows:

Voltage

24 VDC (nominal)

Max. ripple voltage .672 VAC (RMS)

Standby Current

.006 amp.

Alarm Current

.032 amp.

Zone Alarm

2 amp. (resistive) @ 26 VDC dry contacts. Intended for connection to circuits

powered from a Listed power limited source of supply.

A. CODED OPERATION All ZDM modules are normally configured for the “latching” mode of operation. If coded operation (from coded initiating devices) is desired, cut the latch diode CR5 on the appropriate ZDM(s). CR5 is located directly above the relay. (See Fig. 14 )

ZONE TROUBLE LED (YELLOW)

ZONE ALARM LED (RED)

MINI-JUMPER 2110-0014

B. WATERFLOW DETECTION
When a zone is to be used for waterflow alarm detection, the zone maintenance switch must be bypassed (per U.L. 864).
Install Mini-jumper W1 as shown in Figure 14. The notification appliances can only be silenced after the waterflow device has been restored to normal. This circuit may be wired Class A, Style D or Class B, Style B .

S1

CR5

W1 ZONE

MAINTENANCE SWITCH

K1

ZDM W2

Figure 14

MICROFUSE 4300-0018

C. GENERAL ALARM — ZONE JUMPER CONFIGURATION
The zone jumper matrix and zone supervision jumpers should be configured in the following ways for general alarm zones. (For other configurations see Table 1, Section 4.)

ONE ZONE – When only one zone is used, the J10A jumper to the right of the zone (Zone 1) should NOT be removed. A diode jumper (1N4004) should be installed in position J3A.

TWO OR MORE ZONES – When two or more zones are used, diode jumpers should be installed in positions J3A and J3B. The J10A, J10B jumper to the LEFT of each zone should be removed for supervision.
D. WIRING U.L. Listed N.O. Detection Devices or 4- wire smoke detectors may be used. For FCI approved, U.L. Listed, and Multiple Listed 2-wire smoke detectors, see FCI Addendum, P/N 9000-0427.
Class A, Style D Operation Remove the 3.9K ohm, 1/2 watt resistor from Terminals 37 and 40, and connect it to Terminals 38 and 39. Then connect field wiring per Figure 12. The maximum allowable resistance in the field wiring is 100 ohms per zone for the ZDM/ZDM-D modules, and 50 ohms per zone for the VZM module.

Class B, Style B Operation
Remove the 3.9K ohm, 1/2 watt resistor between Terminals 37 and 40, and install it in parallel within the last device on the circuit. Then connect wiring to Terminal 37 ( – ) and 40 (+). See Figure 13.
The maximum allowable resistance in the field wiring is 100/750 ohms per zone for the ZDM, 100 ohms per zone for the ZDM-D and 50 ohms per zone for the VZM. Prior to installing the wires on Terminals 37 and 40, read the resistance across the circuit. It should be between 3,900 and 4,000 ohms for the ZDM or ZDM-D and 3,900 and 3,950 ohms for the VZM.

E. OPTIONAL END OF LINE RESISTOR With the ZDM only, a Class B circuit, when used with 3.3K EOL resistor, may have a maximum DC line resistance of up to 750 ohms. (Not FM Approved)

9000-0007

Page 15 of 28

F. ZDM TROUBLE SHOOTING

PROBLEM
“ZONE TROUBLE” led IS LIT.

CAUSE

ACTION TO BE TAKEN

“MAINTENANCE” switch is in the “OFF” position. Initiating circuit
Remote alarm indicator defective, field wiring open or Jumper JRA, JRB cut.
Zone alarm LED defective

Place the “MAINTENANCE” switch in the normal position.
Check BMFC/ZMC circuit for opens. It should read between 3,900 and 4,000 ohms. (The reading will be between 3,300 and 4,050 ohms if a 3.3K EOL resistor is used)
Press the LAMP TEST switch on the BMFC while someone observes the remote indicator. If the remote indicator does not light, check the field wiring. If no remote indicator is used, be sure Jumpers JRA, JRB are not removed, or that BMFC/ZMC Terminals 36 and 41 are connected.
Press the “LAMP TEST” Switch; If the red LED does not light, replace the ZDM.

16.2 Verification Zone Detector Module (VZM)
The Verification Zone Module (VZM) may be used to replace the ZDM in applications where verification of alarm is required. Each VZM has an individual zone maintenance switch as well as a red “ZONE ALARM” LED and a yellow “ZONE TROUBLE” LED; placement of these is the same as on the ZDM (see Fig. 14). The VZM will accept FCI approved, U.L. Listed, and Multiple Listed two-wire smoke detectors, four-wire smoke detectors, and normally open contact initiating devices wired either Class A, Style D or Class B, Style B at Terminals 37 through 40 of the BMFC or ZMC. Each zone is capable of powering a specific number of FCI approved two-wire detectors.
The VZM differentiates between two-wire smoke detectors and normally open contact initiating devices, allowing a verification time cycle with the two-wire smoke detectors. However, for normally open contact initiating devices and four-wire smoke detectors, the verification time cycle is automatically bypassed.

The Verification Time Cycle has a fixed time out, totaling 124 seconds. It begins with a 20 second presignaling alarm window, initiated by an active FCI approved, U.L. Listed, and Multiple Listed two-wire smoke detector, (indicated by the flashing yellow trouble LED on the VZM). The presignaling alarm window is followed by a 4 second automatic reset time, (indicated by the constant yellow “TROUBLE” LED), and a 100 second alarm verification window, (indicated by a flashing yellow LED). The alarm verification window holds the circuit in the presignaling alarm state, waiting for the first alarm to be verified. If a subsequent alarm comes in from a smoke detector in the circuit, the VZM will initiate a System Alarm, (indicated by the red LED). If a subsequent alarm is not received within 100 seconds, the VZM will return to its normal supervisory condition.
The output parameters of an initiating circuit with a Verification Zone Module are as follows:

Voltage Max. ripple voltage Standby current Alarm current Power limited Supervised

24 VDC regulated .672 VAC (RMS) .006 amp. (normal standby) .035 amp. max. (alarm)

Verification Time

Alarm in (From smoke detector)
Normal Supervisory condition

20 second 4 sec. Presignal- Reset alarm window

100 sec. alarm Verification window

Normal Supervisory condition

ZONE TROUBLE LED (YELLOW) ZONE ALARM LED (RED)

ZONE

J1

MAINTENANCE

SWITCH

J2

TEST

MINI-JUMPER

2110-0014

J2 VZM

K1 K2 J1

LATCH
CR6

MICROFUSE 4300-0018
F1

Page 16 of 28

Figure 15

9000-0007

A. CODED OPERATION All VZMs are normally configured in the “latch” mode of operation. If coded operation (from coded initiating devices) is desired, cut the latch diode CR6. See Fig. 15. When using the Verification Zone Module VZM for waterflow alarm detection, the zone maintenance switch must be bypassed (per U.L. 864). Install mini-jumper J2 as shown in Figure 15. The notification appliances can only be silenced after the waterflow device has been restored to normal.
B. GENERAL ALARM — ZONE JUMPER CONFIGURATION The zone jumper matrix and zone supervision jumpers should be configured per the instructions in Section 16.1.
C. WIRING The wiring should be configured per the instructions in Section. 16.1.
D. SMOKE DETECTOR TEST The VZM has an optional two-pin mini-jumper connector J2, P/N 2110-0014, which is installed when testing smoke detectors without activating the verification time cycle.
IMPORTANT: Remove the test mini-jumper connector J2 after completing the test.

16.3 The Double Density Zone Detector Module (ZDM-D)
The Double Density Zone Detector Module (ZDM-D) provides two zones in the space of one. Each zone of the ZDM-D has an individual zone maintenance switch as well as a supervised red “ZONE ALARM” LED and yellow “ZONE TROUBLE” LED. The ZDM-D is not directly interchangeable with the ZDM; some modifications are required on the BMFC and/or ZMC (see Fig. 17). The ZDM-D will accept two-wire smoke detectors, four-wire smoke detectors, and normally open contact initiating devices wired either Class B, Style B in both circuits (Zone A and Zone B) or Class A, Style D in Zone A and Class B, Style B in Zone B at Terminals 36 through 40 of the BMFC or ZMC. NOTE: When wiring Zone A for Style D operation, a Model V.E.O.L. must be used (consult factory). Each zone on the ZDM-D is capable of powering a specific number of two-wire smoke detectors.
NOTE: When using two-wire smoke detectors, ONLY FCI Approved, U.L. Listed (Multiple Listed) two-wire smoke detectors should be used. See FCI Addendum, P/N 9000-0427.

The output parameters of the initiating circuits with a ZDM-D module are as follows:

Voltage (per zone)

24 VDC nominal

Max. ripple voltage

.672 VAC (RMS)

Standby; Current (per zone) .006 amp.

Alarm current

.035 amp.

Power limited

Supervised

When using a ZDM-D module, the jumpers on the BMFC and/or ZMC must be configured

as follows (refer also to Fig. 17):

ZDM-D POSITION
Zone 1 (BMFC)
Zone 2 (BMFC)
Zone 3, 5, 7, etc. (ZMC) Zone 4, 6, 8, etc. (ZMC)

JUMPER CONFIGURATION
Cut: JRA, CR47; Install: J31, J33 Cut: JRB, CR48; Install: J32, J34 Cut: JRA, CR20; Install: J11A, J33 Cut: JRB, CR21; Install: J11B, J34

NOTE: Jumpers J11A, J11B, J31, J32, J33 and J34 are wire jumpers, NOT 1N4004 diode jumpers. IMPORTANT: If the required jumpers are not configured as described above, contact the factory.

R23

R24

ZDM-D

YELLOW ZONE TROUBLE LED. ZONE A YELLOW ZONE TROUBLE LED. ZONE B RED ZONE ALARM LED. ZONE A RED ZONE ALARM LED. ZONE B
W4 W3

W1

F2

W2

F1

MAINTENANCE SWITCH ZONE B
MAINTENANCE SWITCH ZONE A

Figure 16

9000-0007

Page 17 of 28

A. CODED OPERATION All ZDM-D modules are normally configured in the “latching” mode of operation. If coded operation (from
coded initiating devices) is desired, cut the latch resistor: R23 for Zone A and R24 for Zone B.

B. WATERFLOW DETECTION
When using the ZDM-D module for waterflow alarm detection, the maintenance switch of the appropriate zone must be bypassed (per U.L. 864). For Zone A, install mini-jumper W3, for Zone B, install jumper W4. The notification appliances can only be silenced after the waterflow device has been restored to normal.

C. GENERAL ALARM — ZONE JUMPER CONFIGURATION The zone jumper matrix and zone supervision jumpers should be configured per the instructions in Section
16.1C.

D. WIRING

Field wiring is configured (Fig. 16) as:

Zone A —

Class A or B, Style D or B

Zone B —

Class B, Style B

Using Figure 17 as a guide, connect the field wiring to Terminals 36 through 40.

NOTE: The maximum allowable resistance in the field wiring is 100 ohms per zone, Class B, Style B, 50 ohms per zone, Class A, Style D.

Figure 17
16.4 Sprinkler Supervisory Service
The ZDM module may be used for sprinkler supervisory service by observing the following procedure: A. Remove jumper J3A (or J3B, depending on the zone to be used) if there is to be no municipal notification for supervisory purposes. B. Insert jumper J4A (or J4B depending on the zone to be used). C. Connect a notification appliance (such as the HEM mini-horn) to Terminals 3 and 5 on the BMFC-6. D. Label the ZDM to indicate it is used for supervisory signaling. Thus, off-normal positioning of any supervisory switch will cause the notification appliance to activate, but will not cause a alarm condition unless desired.

Page 18 of 28

9000-0007

17.0 REMOTE ZONE ANNUNCIATION

17.1 Remote zone annunciation with Zone Detector Module (ZDM) or Verification Zone Module (VZM)
BMFC Terminals 36 and 41 are provided for connection of a supervised remote zone annunciator with either LED or incandescent lamp. Should an open in the field wiring or annunciator occur, a zone and system trouble will activate. Connect as follows:
1) Cut JRA, JRB (on BMFC or ZMC) for each zone annunciated. 2) If an FCI LED annunciator is used, go to Step 4. 3) If an incandescent lamp annunciator is used, ensure that the corresponding zone(s) on the BMFC and/or ZMC is configured as follows:

BMFC – J31 (Zone 1) and/or J32 (Zone 2) ZMC – J11A (Zone 3, 5 etc.) and/or J11B (Zone 4, 6 etc.)

Install a jumper. Install a jumper.

IMPORTANT – When an incandescent lamp annunciator is used, only #1820 lamps (28 VDC/0.100 A) or #1829 lamps (28 VDC/0.070 A) are to be used. F1 microfuse, P/N 4300-0018, MUST be installed in socket W2 of the ZDM or VZM. (Consult factory for assistance).

4) Connect the annunciator common to Terminal 41 between Zones 1 and 2. 5) Connect the individual LED/lamp wires to Terminal 36 of each zone annunciated.

17.2 Remote Zone Annunciation With Double Density Zone Detector Module (ZDM-D)
Terminals 34, 35, and 41 are provided for connection of supervised remote zone annunciators, either LED or incandescent lamp. Should an open in the field wiring of an annunciator occur, a zone (Zone A or Zone B) and system trouble will activate. Connect as follows:

1) Cut W1 for Zone A, or W2 for Zone B (jumpers are located on ZDM-D).

2) Connect the annunciator common to Terminal 41 between Zones 1 and 2.

3) Connect the individual LED/lamp wires to Terminal 35 for ZDM-D Zone A, and Terminal 34 for Zone B for each zone annunciated.
IMPORTANT – When an incandescent lamp annunciator is used, only #1820 lamps (28 VDC/0.100 A) or #1829 lamps (28 VDC/0.070 A) are to be used. Microfuse F1, P/N 4300-0018, for Zone A, or Microfuse F2, for Zone B, on the ZDM-D MUST be installed. (Consult factory for assistance).

18.0 ACCESSORY ZONE SIGNAL OUTPUT
A. Alarm by Zone Output – Terminal 42.
This is to be used only with FC-72 series accessories, SRB-6, RB-6, etc. It provides a power limited 24 VDC alarm output per zone.

NOTE: When using ZDM-D module, Terminal 33 is used as alarm output for Zone A and Terminal 42 for Zone B. (See Figure 17)
B. Trouble-By-Zone Output – Terminal 47. This is to be used only with FC-72 series accessory, trouble by zone board (TBZ/TBZ-U). It provides a power limited 24 VDC trouble output per module.
NOTE: Do not connect any external devices to these terminals.

9000-0007

Page 19 of 28

19.0 STAND-BY BATTERY CONNECTIONS
These (non-power limited) terminals are for the connection of sealed lead calcium (gel type) rechargeable batteries. BE SURE TO OBSERVE POLARITY. Terminal 43 is positive (+) and 44 is negative ( – ). The automatic float charge circuitry is capable of maintaining batteries with capacity ratings between 1.9 and 17 ampere/hours. The maximum charge rate is limited to 0.9 amperes.
If the batteries are connected in reverse, the panel protection circuitry will immediately cause the 6 ampere battery fuse to open.
Stand-by Requirements – To determine the size of standby batteries, you must first determine how much current will be drawn in the standby mode. Refer to the Battery Standby Calculation Chart, Table 2.
20.0 POWER SUPPLY
The output of this power supply is 24 VDC at 4 amperes and complies with U.L. Standard 864. The transformer secondary is fused at 6 amperes. Connect the power supply to a 120 VAC source. This connection must be to a dedicated branch circuit and mechanically protected. All means of disconnecting the circuit must be clearly marked “FIRE ALARM CIRCUIT CONTROL” and accessible only to authorized personnel. Fusing of this circuit must comply with local codes for over current protection, and/or Article 760 — “Fire Protective Signaling Systems” of the National Electric Code, NFPA 70. The transfer relay will automatically transfer the system to the stand-by batteries upon reduction to 85% or total loss of AC power.
21.0 FUSES
The standby battery circuit is fused as shown. A 5 amp. permanent fuse (F7) serves as main power limiter in the BMFC and a 6 amp. fuse on the PS-6 protects the power supply.
22.0 LOCATING A TROUBLE
All vital circuits of the FC-72 have an associated yellow “TROUBLE” LED which will identify the circuit in trouble. Refer to the appropriate section of this m manual for further instructions.
The following problems will cause a common System Trouble condition, but will not be indicated individually.

PROBLEM

ACTION TO BE TAKEN

Power supply Module unplugged Remote trouble Supervisory signal
Transfer relay coil open

Check 120 VAC input. Check fuse on PS-6. Check green AC LED. Check all fuses. Check for 24-26 VDC across voltmeter terminals on power supply.
Replace the missing module or install J10A, J10B after last active zone.
Connect a jumper between Terminals 17 and 19. If the trouble clears, check the RTI and associated wiring.
Disconnect the wiring on the transmitter or Terminals 3, 4, 5, and connect a 220 ohm, 5 watt resistors between 3-4, 4-5. If trouble clears, check the lines for an open circuit. Check for open.

TROUBLE CIRCUIT COMPONENTS
If the failure of a component associated with the trouble circuits should occur, and field repairs are not possible, all initiating and notification appliance circuits will continue to function, but THERE WILL BE NO ELECTRICAL SUPERVISION DURING THIS PERIOD.

ZONE DETECTOR MODULES
Should a failure occur, a spare module may be used, or if additional zones are in use you may remove the EOL resistor from the faulty zones’ wiring and temporarily connect the zone wiring in parallel with a known good zone. Once you have removed the zone module from its connector, a System Trouble will occur.
Connecting J9, J-10 to the RIGHT of the missing module will clear the trouble but will not supervise any further zones.

NOTIFICATION APPLIANCE CIRCUIT MODULES Failure of one of these modules will result in loss of supervision on both notification appliance circuits. Both
circuits will still operate with the module removed, as will the Polarity Reversal output and the City Box output. If using BMC-6, Jumper J-11 must be in place.
The Main Power Limiter on BMFC-6 is independently fused by permanent fuse F7, 5 amp., Type 2AG.

Page 20 of 28

9000-0007

Table 2 FC-72 System Battery Standby Calculation Chart

Supv.

Alarm

Total Supv. Total Alarm

Qty Model Description

Current Current Current

Current

1 FC-72-1 1 Zone Control Panel

.063 A

.370 A(*) .063 A

.370 A

BMFC-6 Basic Master Fire Card (*)

(*)

—-

—-

ADAM-6-1 Aux. DC Actuation Module

.013 A

.073 A

ADAM-6-2 Aux. DC Actuation Module

.026 A

.133 A(#)

APS-6 Aux. Power Supply

.020 A

—-

—-

AVM

Alarm Verification Module

.012 A

.030 A

BCM-6 Notification Appl. Circuit Module (**)

(**)

—-

—-

BMC-6 Master Coder Module

(**)

(**)

—-

—-

BCM-6 Notification Appl. Circuit Module (**)

(**)

—-

—-

TCM-6 Temporal Pattern Module

(**)

(**)

—-

—-

PNIS

PNIS Zone Coder Module

.004 A/zone .150 A

PS-6

Power Supply

—-

—-

—-

—-

RB-6

Aux. Relay Module

—-

.070 A (#)

—-

RDF

Releasing Device Interface

.002 A

.047 A

RRT

Remote Reset Capability

(##)

(##)

RTI

Remote Trouble Indicator

.002 A

.002 A

RZA

Remote Zone Annunciator (LED) —-

.002 A

—-

SRB-6 Supervised Aux. Relay Module

.019 A

.079 A (#)

TBZ

Trouble By Zone Module

.003 A

.021A/zone

TDS438 Time Delay Switch

—-

.001

—-

VZM

Verification Zone Module

.010 A

.175 A

WTM

Walk Test Module

—-

.040 A

—-

ZMC

Zone Mother Card

—-

—-

—-

—-

ZDM

Zone Detector Module

.006 A

.163 A

ZDM-D Zone Det. Module, Dual Density .018 A

.298 A (#)

CPD-7051 Smoke Det., Ionization

.00005 A

—-

PSD-7155/

PSD-7156 Smoke Det., Photoelectric

.00005 A

—-

SBS-1101 Smoke Det., Ionization

.00010 A

—-

SBS-1201 Smoke Det., Photoelectronic

.00012 A

—-

301 Series Smoke Det.

.00012 A

—-

4WSD 4 Wire Smoke Det/EOL Relay

NOTES: (*) FC-72-1 contains BMFC-6, PS-6, one ZDM and one BCM-6, BMC-6, TCM-6, or CCM-6.

(**) Included in BMFC-6 and/or ADAM-6. Power requirements are as above.

(#) With both circuits in alarm.

(##) Consult factory.

Alarm current is limited by zone module circuitry and is not involved in battery calculation.

Modules DMM, ABM and DBM do not consume current and are not involved in calculations.

Battery Calculations

A

Total Supv. Current from above chart

B

Enter number of standby hours (24 hrs for NFPA Local, Proprietary,

Central Station, 60 hrs for NFPA Auxiliary, Remote Station,

90 hours for FM Deluge/Preaction)

C

Multiply Line A times hours in Line B–enter

D

Total alarm current from above chart

E

Enter alarm sounding period in hours. (5 minutes = .084 hr.)**

F

Multiply Line D times Line E –enter

G

Total of Lines C&F–enter

H

Multiply Line G by 1.2 — enter (Total ampere/hours required*)

* Use next size battery with capacity greater than required.

**5 minute alarm period for NFPA, 10 minute period for FM Deluge/Preaction Service

9000-0007

Page 21 of 28

23.0 CENTRAL STATION TRANSMITTER CONNECTIONS
The FC-72 control panel may be used in conjunction with the below listed units to meet the requirements for Central Station protective Signaling Service per NFPA 72. Signals for fire and trouble are transmitted over two (2) separate circuits · Potter Model ATE-B Alarm and Trouble Transmitter. · Versus Subscriber Terminal Units STU-2Z-UL, or STU-11Z-UL · Keltron DMP-703/704 Central Station Alarm receiving unit.
See Figures 18, 19 and 20 for connections to the various units.

15

3 16

4 POTTER

20

ATTE-B

5 TRANSMITTER

21

6

29

7

8 30
NOTE: CONNECT BMFC TERMS. 16, 20, 29 TOGETHER CONNECT ATTE-B TERMS. 4, 6, 7 TOGETHER

STU-2Z-UL, STU-4Z-UL OR
STU-11Z-UL
1 23 45 6
S2 S1

J1 J2

TROUBLE CIRCUIT

STU EOL UNIT
21024-0001

ALARM CIRCUIT

STU EOL
UNIT 21024-0001

20 21
BMFC 15 16

Figure 18 Connection of Potter ATTE-B Transmitter

Figure 19 Connection to Versus STU Units

Page 22 of 28

TO KELTRON DMP703/704 TROUBLE CIRCUIT

LISTED 11K EOL RESISTOR

LISTED 11K EOL
RESISTOR
TO KELTRON DMP703/704 ALARM CIRCUIT

TROUBLE

CONTACTS BMFC-6

MODULE

16 (C)

ALARM

15 (N/O) CONTACTS

14

Figure 20 Connection to Keltron DMP-703/704

9000-0007

24.0 PROPRIETARY SUPERVISING STATION SYSTEM CONNECTIONS
The FC-72 control may be used in conjunction with Keltron Model DMP703 or DMP704 Proprietary alarm receiving units to meet the requirements for Proprietary Alarm Service per NFPA 72. Signals are transmitted for fire, trouble and supervisory functions over three (3) separate circuits.
See Figure 23 for connections for fire and trouble transmissions. Figure 21 contains wiring for waterflow and supervisory transmission.
WATERFLOW ALARMS Remove the associated Zone Module, ZDM, from the mother card and install a jumper across the two waterflow jumper pins on the module. Reinstall the module into the mother card. This will prevent the silencing of notification appliances during a waterflow alarm.
SPRINKLER SUPERVISORY Remove the associated Zone Module ZDM, from the mother card and cut the 1N4004 diode labeled “latch”. On the diode matrix at the right of the Sprinkler Supervisory ZDM module, move the program diode down one position from the factory installed position. Reinstall the module into the mother card. This will cause an output on BMFC Terminals 4 and 5. Connect a UL Listed notification appliance to these terminals and install the appliance inside the control panel if audible, or outside if visual.

TO KELTRON DMP-703/704 SPRINKLER SUPERVISORY CIRCUIT
UL LISTED NOTIFICATION APPLIANCE

35 34 33

LISTED 11K EOL
RESISTOR

SUPERVISORY ZDM ZONE TERMINALS

BMFC-6

5

MODULE

4

Figure 21 Sprinkler Supervisory Connection to DMP703/704

9000-0007

Page 23 of 28

25.0 FCI APPROVED, U.L. LISTED, MULTIPLE LISTED, TWO-WIRE PHOTOELECTRIC AND IONIZATION SMOKE DETECTORS
Only FCI approved, compatible two-wire photoelectric and/or ionization smoke detectors, which are U.L. Listed, and Multiple Listed for use with the FC-72 Control may be used. FCI Addendum, P/N 9000-0427 lists those models that should be used, together with the maximum that may be connected to each zone.
Manual stations and heat detectors may be added to the same zone circuit with smoke detectors. Operation of a manual station or heat detector in the same zone as a smoke detector will prevent the operation of smoke detectors on that zone.
All installation wires must be free from grounds, opens or shorts. Test each installation circuit wire with an ohmmeter before connection to the control panel. Ensure that the detectors are wired (spliced) in supervisory position per the wiring diagram.
All wiring must be installed in compliance with the National Electrical Code and local codes. Proper gauge wire should be used. Each conductor should be identifiable to prevent wiring errors. For wiring between detectors, it is recommended that the wire be no smaller than 18 gauge.
Refer to the drawing mounted on the enclosure door for proper terminal connections.
GENERAL NOTES: To Insure proper installation of the detector head to the base, be sure wires are properly dressed at installation · Position all wires flat against the base. · Take up all slack in the outlet box. · Route wires away from connector terminals. · For system supervision – Do not use looped wire under the terminals. Break the wire run to provide supervision of connections.
WIRING INFORMATION Refer to the installation instructions furnished with each detector.
IMPORTANT: Any one initiating circuit should contain the same series smoke detector. We do not recommend mixing 301/SBS series detectors with CPD/PSD series detectors in the same circuit.

25.1 PSD/CPD Series Detectors
Different CPD/PSD detector/base models may be mixed and matched without restrictions. If you have installed a jumper between Terminals 6 and 7 to test detector circuit continuity, be sure to remove the jumper before installing detector head.

DETECTOR BASE OPTIONS

BASE

IDENTIFIER

2-WB

FE51A Connects to a 2-wire detection circuit via screw terminals.

2WRLT FE52A Same as above plus provision for remote LED indicator and remote test.

Min. alarm current: .019 amp.

2WRB FE55A Connects to a 2-wire detection circuit via wire leads. Equipped with SPDT aux. relay.

Minimum alarm current: .015 amp. Also has remote indicator and test capability.

4WRB N/A

Connects to a 4-wire detection circuit via wire leads. Equipped with SPDT

supplementary relay. Min. alarm current .035 amp.

2040-24 N/A

End of line supervisory relay, 24 VDC.

MA-001 MAFE

Retrofit adapter. Allows installation of detectors in old CPD series bases,

CPD-001(compatibility identifier FE01A), CPD-002 (Compatibility identifier

FE02A) and CPD-003 identifier FE03A).

WARNING: To prevent detector contamination and subsequent warranty cancellation, smoke detectors must remain covered until the area is clean and dust free.

Page 24 of 28

9000-0007

2-WB Base less options
2WRLT Base with Remote Indicator option
2WRLT Base with Remote Indicator and Remote Test Switch options
2WRB Base with relay option
9000-0007

Page 25 of 28

25.2 Model SBS Smoke Detectors

Figure 22 Typical Wiring diagram – Model SBS Detectors
· Installation wiring to detector is NON-POLARIZED unless a remote indicator is used. · For best system performance, it is recommended that the circuit wires be twisted pair and installed
in separate grounded conduit to protect the circuit from extraneous electrical interference. · Different SBS/301 series detectors may be mixed and matched without restrictions.

Figure 23 Typical wiring diagram – Model 301 Detectors
25.3 Model 301 Smoke Detectors
· For best system performance, it is recommended that the circuit wires be twisted pair and installed in separate grounded conduit to protect the circuit from extraneous electrical interference.
· Different SBS/301 series detectors may be mixed and matched without restrictions.

Page 26 of 28

9000-0007

NOTE: To determine the maximum number of FCI approved, UL Listed, (compatible) two-wire photoelectric or ionization detectors, FCI CPD, PSD, 301 and SBS series per circuit, see FCI Addendum, P/N 9000-0427. When configuring the initiating circuits for Class A, Style D, the FCI model VEOL (P/N 1120-0141) may be required.

9000-0007

Page 27 of 28

NOTES

1. JT

Cut to transmit system trouble to remote station via telephone line. (Terminals 25 & 26)

Relay K1 required.

2. JL

Cut if reversing relay (K2) latch is NOT desired.

3. J12

Cut when using remote station signal via telephone line. (Terminals 25 & 26)

4. J13

Cut if RTI Remote Trouble Indicator is NOT used.

5. JRT1

Cut if RTI Remote Trouble Indicator is used.

6. J11

Cut if TCM-6, BMC-6 or CCM-6 is installed.

7. JS3

Cut if supervision of Terminals 3 & 4 is desired.

8. JS5

Cut if supervision of Terminals 4 & 5 is desired.

9. JRA/JRB Cut on each zone where remote zone LED annunciator is used. Cut on each zone where

Double Density Zone Detector Module (ZDM-D) is used.

10. J10A/10B Install to the right of the last zone in system unless followed by an auxiliary module

(ADAM, SRB, etc.)

11. J22

Cut to disable the Battery Bell Test from activating Bus 6.

12. JRR

Cut to enable the city box switch to control the reversing relay.

13. Diode Jumper Position:

(Odd Zones- 1, 3, 5, etc.) (Even Zones- 2, 4, 6, etc.)

Function

J1A

J1B

Alarm will activate master box/rel. output only.

J2A

J2B

Alarm will activate Bus 2.

J3A

J3B

Alarm will activate notif. appliance circuits,

Rev. relay, master box.

J4A

J4B

Alarm will activate aux. notif. appl. output only.

(Terms. 3 & 5)

J5A

J5B

Alarm will activate Bus 5.

J6A

J6B

Alarm will activate Bus 6.

14.

Denotes supervised wiring.

·

Denotes optional or accessory.

*

Except for master box output, A.C. supply circuit and standby battery circuit.

15. Relay

Number Location

Part No.

Power Transfer Relay

K4

BMFC-6

26592

Rev. & Signal Relay

K2 & K3 BMFC-6

4500-0024

Trouble Relay

K1

BMFC-6

4500-0024

Transfer Relay

K1

PS-6

26592

16. EOL-D = 3.9K 1/2 watt, 5% resistor.

Optional EOL-D = 3.3K 1/2 watt 5% resistor (For use with ZDM module only in Class B,

Style B circuits of up to 750 ohms circuit resistance.) (Not FM Approved)

17. When system is supplied in two or more enclosures, mount adjacent with inter-connection cable in

metallic raceway.

18. To determine the appropriate standby batteries needed, see Section 19.

19. Main supply circuit input: 120 VAC, 60 Hz @ 2 amp./non-power limited circuit, output 24 VDC

nominal @ 4 amp. See Sections 11 & 20.

20. Standby battery circuit: Input 24 VDC nom. non-power limited circuit, output 27.2 VDC, 0.9 amp. max.

21. Initiating circuit output: 24 VDC nom. supervisory, 0.035 amp. max. alarm, power limited circuit.

See Section 16.

22. Notification appliance circuits: Output 24 VDC nom., 1.75 amp. max. alarm, power limited circuit.

See Section 7.

23. Supplementary notification appliance circuits-auxiliary alarm output: 24 VDC nom., 0.50 amp. max.

alarm per output, power limited circuit. See Section 6.

24. Polarity reversal circuit: 24 VDC nom., 0.13 amp. max., power limited circuit. See Section 12.

25. City Master box output: 24 VDC nom., 0.5 amp. max. alarm, non-power limited circuit. See Section 5.

26. Annunciator circuit: 24 VDC nom., 0.5 amp. max. alarm, power limited circuit. Do not connect

any load in excess of 0.1 amp.

27. RTI circuit: 24 VDC nom., 0.005 amp. max., power limited circuit. See Section 10.

28. Central Station connection per NFPA 72. See Section 24.

29. Proprietary Supervising Station System connection per NFPA 72, see Section 25.

30. Fuses:

F2 – Standby battery

F8 – Main Power Limiter, permanent. 5A

Page 28 of 28

9000-0007

301 2nd Ave. Waltham, MA 02451-1133 USA TEL: 781-487-0088 FAX: 781-370-4132