EMS logoFireCell LOGOEMS 2X-A Series FireCell Wireless Alarm System2X-A Series
QUICK START GUIDE
FREE mobile phone app

2X-A Series FireCell Wireless Alarm System

EMS 2X-A Series FireCell Wireless Alarm System - QR code EMS 2X-A Series FireCell Wireless Alarm System - QR code 1

2x-A Series introduction

The 2X-A range of control panels are compatible with the EMS FireCell system and EMS Fusion RLM (Radio Loop Module). All installation guidelines are the same as when fitting other XP95 control panels, although panel operation will vary.

Programmed or unprogrammed system?

This guide covers the installation of both programmed and unprogrammed systems.EMS 2X-A Series FireCell Wireless Alarm System - figure 1DO NOT press the device log on buttons if the system is supplied pre-programmed.
Doing this will unprogramme the device from the system.EMS 2X-A Series FireCell Wireless Alarm System - figure 2More detailed FireCell instructions are available on www.emsgroup.co.uk.
Programming can be achieved either manually or via computer programs.EMS 2X-A Series FireCell Wireless Alarm System - figure 3

Add devices to the 2x-A panel

Program the 2X-A panel using the panel’s Autosetup feature, as outlined: EMS 2X-A Series FireCell Wireless Alarm System - figure 4

Setting devices as wireless

To ensure that device information is displayed correctly on the 2X-A panel, the devices must be set as wireless devices:EMS 2X-A Series FireCell Wireless Alarm System - figure 5

FireCell Hub on 2X-A – location recap

The FireCell Hub is powered from the 2X-A panel’s loop connection. If a radio survey has been carried out, the survey will detail the recommended Hub and panel locations.
The Hub is required to be connected via glands, close coupled above the panel.
The recommended minimum distance between metal objects from the aerial is 600 mm. The recommended minimum distance to any other electrical equipment is 2 metres.EMS 2X-A Series FireCell Wireless Alarm System - figure 6

Hub to 2X-A wiring connections

The Hub has up to four separate sets of loop connections: LOOP IN -, LOOP IN +, LOOP OUT – and LOOP OUT + for each available loop. The cable must be passed through the entry points provided.
Connections are detailed:EMS 2X-A Series FireCell Wireless Alarm System - figure 7NOTE: Repeat for loops 2-4 if used

Fusion RLMs on 2X-A – location recap

RLMs are powered from the 2X-A panel’s loop connection. For optimum wireless performance, the following must be observed:
Ensure RLMs are installed as per the site survey
Ensure the RLM is not installed within 2 m of other wireless or electrical equipment (not including the 2X-A panel).
Ensure the RLM is not installed within 0.6 m of metal work.EMS 2X-A Series FireCell Wireless Alarm System - figure 8

RLM to 2X-A wiring connections

Each RLM has; LOOP IN -, LOOP IN +, LOOP OUT -, LOOP OUT + and 2x screen connections. The cable must be passed through the entry points provided.
Connections are detailed below:
Single RLM
EMS 2X-A Series FireCell Wireless Alarm System - figure 9Multiple RLMs (max 4 per loop)EMS 2X-A Series FireCell Wireless Alarm System - figure 10

EMS logoWIRELESS FIRE SYSTEMS
www.emsgroup.co.ukEMS 2X-A Series FireCell Wireless Alarm System - QR code 2EMS 2X-A Series FireCell Wireless Alarm System - symbol