Elimko E-200 Series Universal Advanced Controller User Guide
Elimko E-200 Series Universal Advanced Controller

DESCRIPTION

E-200 Series general purpose process controllers are industrial devices in 1/4 DIN (96×96 mm IEC/TR 60668) dimensions designed by using new generation microcontrollers with on/off, PID and other control forms. Inputs and outputs can be easily programmed by the user.

In E-200 Series controllers, set value and measured value can be displayed from -1999 to 9999 on two 4-digit displays and general purpose inputs (T/C, R/T, mV, mA) can be programmed.

DIMENSIONS and PANEL CUT-OUT

DIMENSIONS and PANEL CUT-OUT

CONNECTION DIAGRAM

CONNECTION DIAGRAM

Warning icon Operating voltage suitable for the device type shall be applied

1st and 2nd control outputs can be selected as either Relay (RL1, RL2) or SSR (SSR1, SSR2).

Analog outputs (AO1, AO2 ) can be selected as either mA or 0-10 V DC.

Digital inputs are used by connecting a dry contact output between the COM terminal and the desired input (DI1, DI2 or DI3)
Digital inputs

WARNINGS

Warning icon E-200 controller is designed for panel mounting and should be used in an industrial environment.

EU DIRECTIVE COMPLIANCE

Low Voltage Directive: EN 61010-1
EMC Directive: EN 61326-1

TYPE CODING

E-200 Series Universal Advanced Controller
TYPE CODING

Relay Outputs

  • 2 relays (RL1, RL2)
  • 3 relays (RL1, RL2, RL3)
  • 4 relays (RL1, RL2, RL3, RL4)
  • 1 SSR (SSR1) + 1 relay (RL2)
  • 1 SSR (SSR1) + 2 relays (RL2, RL3)
  • 1 SSR (SSR1) + 3 relays (RL2, RL3, RL4)
  • 2 SSR (SSR1, SSR2) + 1 relays (RL3)
  • 2 SSR (SSR1, SSR2) + 2 relays (RL3, RL4)

Analog Outputs 

  • 1 adet 0-20 / 4-20 mA (AO1)
  • 2 adet 0-20 / 4-20 mA (AO1, AO2)
  • 1 adet 0-10 V DC (AO1)
  • 2 adet 0-10 V DC (AO1, AO2)
  • 1 adet 0-20 / 4-20 mA (AO1) + 1 adet 0-10 V DC (AO2)

Communication

None
RS-485 **

Operating Voltage

85-265 V AC / 85-375 V DC
20-60 V AC / 20-60 V DC

* Analog outputs are isolated from each other.
**When E-200 Series devices are ordered with communication, the E-IB-11 USB-RS485 converter can be used for PC connection. There are various control and monitoring software provided by Elimko.

TECHNICAL SPECIFICATION

Parameter Description
Control Type On/Off, PID, Heat/Cool, Floating and Feedback Control of Valves
Operating Voltage 20..60 V AC / 20..60 V DC or 85..265 V AC / 85..375 V DC
Relays I SSR 4 Adet SPST – NO 250 V AC 5A relays or 24 V DC 25 mA (SSR) drives
Dimensions (mm) 96 (Lenght) x 96 (Height) x 100 (Width)
Panel Cut-Out (mm) 92 (Lenght) X 92 (Height)
Analog Output 2 x 0..20 / 4-20 mA or 0..10 V DC optional
Analog Girl§ Universal (Note 1), 1 x External set (mA)
Communication (RS-485) Available (optional)
Digital Input 3 inputs
Valve Feedback Available (Note 2)
Transmitter Supply Available
Weight 430 g
Power Consumption Max. 7 W (10 VA)
Operating Temperature 10 °C … 55 °C
Storage Temperature 25 °C … 65 °C
Memory Maks. 100.000 write
Protection Class IP-65 Front Panel, IP-20 Rear Case

Notes:

  1. Universal Input:
    Thermocouple: B, E, J, K, L, N, R, S, T, U
    Resistance Thermometer: Pt-100
    Current: 0-20 mA, 4-20 mA (Linear)
    Voltage: 0-50 mV, 0-1 V, 0.2-1 V (Linear),
    0-10 V DC, must be specified in the order.
    Resolution: 16 bit
    Accuracy: Thermocouple, Max. ±1.0 °C (Conversion and CJC error)
    Resistance Thermometer, Max. 10.5 °C (Conversion and wire resistance compensation)
    Linear Input, Max. % 0.1
  2. Valve Feedback are supplied as potentiometer input in standard controllers. If the feedback type is requested as mA, it must be specified in the order

PARAMETER TABLE

Description Min Maks Unit
INPUT SETTINGS g n INP1 Analog Input 1 Type Table 1
DP Decimal Point 0 3
S LO Analog Input 1 Linear Scale Lower Value -199.9 999.9 EU
S HI Analog Input 1 Linear Scale Upper Value -199.9 999.9 EU
UNI Temperature Unit * *
O S Analog Input 1 Offset Value -100.0 100.0 EU
L R Analog Input 1 Filter 1 15 s
SNBR Analog Input 1 Sensor Broken Behaviour LO HI
INP2 Analog Input 2 Type -2 -2
S2LO Analog Input 2 Linear Scale Lower Value -199.9 999.9 EU
S2HI Analog Input 2 Linear Scale Upper Value -199.9 999.9 EU
S2BR Analog Input 2 Sensor Broken Behaviour LO HI
DRS Modbus Adress 1 127
B UD Modbus Baud Rate [ .8, . , 1 .2, 8. kbaud] .8 8.
PR Y Modbus Parity [None, O , Even]
CONTROL SET SETTINGS SE P SPSR Control Set Point Source Table 2
SPLL Control Set Point Lower Limit -199.9 SPHL EU
SPHL Control Set Point Upper Limit SPLL 999.9 EU
SPRR Control Set Point Ramping Rate O 60.0 EU/min
S-1 1. Step Set Value SPLL SPHL EU
-1 1. Step Time O 999.9 min
S-2 2. Step Set Value SPLL SPHL EU
-2 2. Step Time O 999.9 min
S- 3. Step Set Value SPLL SPHL EU
- 3. Step Time O 999.9 min
SE 1 Digital Input Selectable Set 1 SPLL SPHL EU
SE 2 Digital Input Selectable Set 2 SPLL SPHL EU
SE Digital Input Selectable Set 3 SPLL SPHL EU
SE Digital Input Selectable Set 4 SPLL SPHL EU
ALARM  SETTINGS 1dUJB R 1LP Alarm 1 Type Table 3
R ISP Alarm 1 Set Point -199.9 999.9 EU
R 11-N Alarm 1 Hysteresis 0.0 999.9 EU
R ILE Alarm 1 Lock dSb Enb
RaP Alarm 2 Type Table 3
R2SP Alarm 2 Set Point -199.9 999.9 EU
1121-1 Alarm 2 Hysteresis 0.0 999.9 EU
Rab Alarm 2 Lock dSb Enb
R3LP Alarm 3 Type Table 3
R3SP Alarm 3 Set Point -199.9 999.9 EU
R3tiy Alarm 3 Hysteresis 0.0 999.9 EU
R3LL Alarm 3 Lock dSb Enb
R4hp Alarm 4 Type Table 3
F1’iSP Alarm 4 Set Point -199.9 999.9 EU
R’iti3 Alarm 4 Hysteresis 0.0 999.9 EU
IT-ILL Alarm 4 Lock dSb Enb
ELF) Control Type Table 4
CFrFf Control Form [d Jr. rEu] d tr rEu
[Prd Control Period 1 250 s
F■nPr Manual Mode Selection d5b Enb
hrha; Floating Control Valve Travel Time 10 2500 s
dbnd Dead Band 0.1 25.0 °A
oLL Control Output Lower Limit 0.0 oHL °A
ofIL Control Output Upper Limit oLL 100.0 °A
°Fir Control Output Manual Reset oLL oHL crA
Pon[ PID Power On Behaviour 0 4
ErLL Retransmission Scale Lower Value -199.9 ErlIL EU
Er HL Retransmission Scale Upper Value bra 999.9 EU
rL Id Relay 1 Function Table 5
r L 2d Relay 2 Function Table 5
r L3d Relay 3 Function Table 5
r L 9d Relay 4 Function Table 5
Ro Id Analog Output 1 Function Table 6
Ro Ir Analog Output 1 Type Table 7.1 ve Table 7.2
Ro2d Analog Output 2 Function Table 6
Ro2r Analog Output 2 Type Table 7 1 ve Table 7.2
SruL Feedback Valve Fully-Closed Position
Sro1-1 Feedback Valve Fully-Open Position
SDNI113S aid 31-’11 3 RE PID Auto Tune oFF on
P Id PID Parameter Type SE d Rdu
Pb- I Proportional Band + 0.1 999.9 EU
Pb-2 Proportional Band – 0.1 999.9 EU
ILH Integral Time + oFF 9999 S
ILL Integral Time – oFF 9999 S
dEH Derivative Time + oFF 2500 S
dEE Derivative Time – oFF 2500 S
PN5 Hysteresis 0.0 999.9 EU
nano3s 2•3-‘d 5Cod Security Code 0 9999
dPr I Parameter Access Level 0 9
RPr I Parameter Setting Level 0 9
FESb Factory Settings [oFF. LoRd. SR„ E. dab]

ACCESSING PARAMETERS

ACCESSING PARAMETERS

APPLICATION EXAMPLES

  1. Input: Pt-100 Relay / Alarm1: 50 °C Low, Relay2 / Alarm2: 55 °C High A01: 4-20 mA PID Control Output
    Display
  2. Input: TC Type J, Relay1: On-Off Control Output, Relay2 / Alarm2: 350 °C High
    Display
  3. Input: TC Type K, Profile Control (Ramp up to 400°C in 10 minutes and wait for 60 minutes), Relay1: PID Control Output, A01: Retransmission Output (4-20 mA, 0-1200 °C)
    Display
  4. Input: 4-20 mA, Scale: 0-600, External Set Point: 4-20 mA, Scale: 0-600, Floating Valve Control (Travel Time 30 s), Relay1: Valve Open, Relay2: Valve Close InP SCLO SCH! InP2 52L 52H CEYP Erth Lid L2d
    Display

For detailed information, you can access the comprehensive user manual of the device under the heading “User Manuals” at www.elimko.com.tr.
You can also use the QR Code on the front for this.

Elimko logo

Documents / Resources

Elimko E-200 Series Universal Advanced Controller [pdf] User Guide
E200_rev0_eng_Quick_Start_Guide.pdf, H zl _E200_rev0_eng11, E-200 Series, E-200 Series Universal Advanced Controller, Universal Advanced Controller, Advanced Controller, Controller