EBERLE logoOperating Instructions
ATR 4500
ATR 4800EBERLE ATR 4500 Surface Mounted Digital Temperature Controller

ATR 4500 Surface Mounted Digital Temperature Controller

Important!
The device may only be opened by an electrically skilled person and must be installed as shown on the circuit diagram on the device and in these instructions. The existing safety regulations must be followed.
The relevant installation measures must be taken to achieve the requirements of protection class II. This independently mountable electronic device is used to control the temperature in dry and enclosed rooms only, with normal environment. This device conforms to EN 60730, it operates according to type 1Y.

Areas of Use

The electronic temperature controllers ATR 4100/4500/4800 can be used to control the floor and room temperature. The products are suitable for water-based and (with usage of external contactor/relay) for electric heating systems.

Installation site

  • The controller should be mounted in a place in the room that is easy to access for operation.
  • Mounting height: approx. 1.5 m above the floor.
  • Preference should be given to installation on an internal wall.
    Avoid external walls and draughts from windows and doors.
  • Ensure that the room’s normal convection air reaches the controller freely without restriction. The controller should therefore not be mounted inside shelf units or behind curtains and similar coverings.
  • Extraneous heat has a negative influence on the control accuracy.
  • Direct sunshine, proximity to televisions, radios and heaters, lamps, stoves and heating pipes must be avoided.

Electrical connection / mounting

Installation in the following steps:

  1. Connect the backplate terminals according to the circuit dia- gram (see laser marking on backplate or these instructions)
  2. Snap the front part onto the backplate

Dimensions

EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Dimensions

Wiring diagrams

Abbreviations

L = outer conductor (phase)
N = neutral conductor
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol = Universal input (H/C | setback | presence)
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 1 = Heating load connection
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 2 = Heating / Cooling load connection

Attention EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 3
Risk of fatal injury, due to electric shock. The appliance is not safety extra-low voltage device (SELV ). The sensor cables are connected to 230 V AC mains voltage. Only use sensors with insulated cables. Failure to do so may result in serious injury or death.

ATR 4500EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - ATR 4500ATR 4800EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - ATR 4800

Technical data

ATR 4500 ATR 4800
Article number 567 1954 57 600 567 1944 58 600
Supply voltage 230 V AC, 50 Hz 230 V AC, 50 Hz
Temperature setting range 5 … 30 °C 5 … 30 °C
10 … 40 °C
Output Triac Triac
No of switchable actuators 6 thermal actuators – 3 W each (18 W) 6 thermal actuators – 3 W each (18 W)
Display PMVA black with backlight PMVA black with backlight
Stand-by consumption < 0,5 W < 0,5 W
Control algorithm PWM or ON/OFF
selectable
PWM or ON/OFF
selectable
PWM cycle time 5.. 20 min selectable 5.. 20 min selectable
Hysteresis 0,1 K or 0,5 K selectable 0,1 K or 0,5 K selectable
Universal input Heating/ Cooling Change-over or Setback or Presence selectable Heating/ Cooling Change-over or Setback or Presence selectable
Frost protection 5 °C 5 °C
10 °C for floor control
Valve protection Duration and timing adjustable Duration and timing adjustable
EN 50559 temp. limit 5 min / 60 min if activated 5 min / 60 min if activated
Floor probe Example: F 193 720, NTC, Length 4 m, Max. extension: 50 m
Probe value selectable via menu
Setpoint range limitation Via user menu Via user menu
Window open detection Temp. drop & duration adjustable via menu Temp. drop & duration adjustable via menu
Heating schedules Timer Auto / Holiday / @Home / Timer
Parametrization Installer & User menu directly at device Installer & User menu directly at device
Ambient temperature 0 … 40 °C 0 … 40 °C
Storage temperature –25 … 60 °C –25 … 60 °C
Overvoltage category III III
Rated pulse voltage 4 kV 4 kV
Voltage / current for EMC emission testing 230 V, 0.1A 230 V, 0.1A
Protection class
w/ appropriate instal- lation measures
II II
Degree of protection IP 30 IP 30
Pollution degree 2 2
Temperature ball intendation test 75 °C 75 °C
Energy class
(acc. EU 811/2013)
IV = 2 % IV = 2 %
Eco design directive LOT 20 F(x) correction para- meters upon request F(x) correction para- meters upon request

Universal input

The function of the universal input can be set in the Installer Menu (Heating/Cooling change-over OR Setback OR Presence) When the H/C input is energized (230 V ), the device switches to Cooling Mode.
When the setback input is energized (230 V), the device switches to Unoccupied Mode (Unoccupied temperature is settable via User Menu).
When the presence input is energized (230 V), the controller switches to Occupied Mode.
AUTO/HOLIDAY/@HOME/TIMER selections are ignored while the device is in Unoccupied Mode.

Display

EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Display

EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 4 Measured Temperature
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 5 Day of the week (ATR 4800)
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 6 Current time (ATR 4800) or TIMER duration
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 7 Text line
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 8 Heating EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 14 At home
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 9 Cooling EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 15 Manual
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 10 Lock mode EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 16 Auto
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 11 Off mode EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 17 Timer
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 12 Settings EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 18 Window open
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 13 Holiday EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 19 Eco Mode

EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 20

Normal Operation

Change setpoint with [+] or [–] Press [Esc] or [OK] for mode selection, info and menu entry Scroll with [+] or [–]

INFO Scroll with [+]/[–] through the displayed options:
Next upcoming event
Holiday start
Holiday end
AUTO schedule
AT HOME schedule
AUTO Start AUTO mode, weekly schedule set under User
Menu 2, item 01 is applied
MANUAL Manual operation, setpoint change via [+] or [–], no
schedules active
AT HOME Start AT HOME mode, schedule for the day set under User Menu 2, item 02 is applied
TIMER Selected setpoint is applied for selected timer durati- on, once time expired, device goes back to previous mode and latest specified setpoint before timer was started
MENU Entry for User Menu Level 1, User Menu Level 2 and Installer Menu

Manual override
Even during a currently active mode/schedule or absence mode, the setpoint can be changed manually at any time using [+]/[–].
The manually changed setpoint value remains active until the next event occurs. Example: In AUTO mode, the manually changed setpoint value remains active until the next timed event of the AUTO schedule. From the next event onwards, the AUTO schedule continues to be applied as defined.
Manual override is indicated by the hand symbol in addition to the active mode symbol.

Installer Presets (depending on application)

Selection after first start of device or via menu

Use case / Heating system ATR 4500 ATR 4800
P2 Hydronic Underfloor Heating – Room EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
P3 Hydronic Radiator – Room EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
P4 Blow convector – Room (Attention: Use only with external relay) EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
P5 Electrical Radiator, Infrared – Room (Attention: Use only with external relay) EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
P6 Hydronic Underfloor Heating – Limiter EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
P7 Electrical Underfloor heating – Floor (Attention: Use only with external relay) EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
P8 Electrical Underfloor Heating – Limiter (Attention: Use only with external relay) EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
Function description P2 P3 P4 P5 P6 P7 P8
02 Application type (Control sensor) Room sensor Room sensor Room sensor Room sensor Room sensor with floor limit Floor probe Room sensor with floor limit
03 Floor probe type (resistance in Ohm) 33 k 33 k 33 k
04 Min. floor limit in °C 10 10 10
05 Max. floor limit in °C 40 40 40
06 Control method PWM 20 Min PWM 10 Min 2 point control 0,5 K 2 point control 0,5 K PWM 20 Min PWM 5 Min 2 point control 0,5 K
2 point control: On/Off time in min 2 2 2
07 Actuator type Normally closed valve Normally closed valve Normally closed valve
08 Universal input configuration Heating/Cooling Heating/Cooling Setback input Setback input Heating/Cooling Setback input Setback input
09 Optimum Start Yes Yes Yes Yes Yes Yes Yes
10 Valve protection Yes Yes No No Yes No No
Valve protection – Max. idle time in days 14 14 14
Valve protection – Min. exercise time in min 3 3 3
11 Temporal limit acc. to EN 50559 No No No Yes No Yes Yes
12 Window open detection No No No No No No No
13 Frost protection Yes Yes Yes Yes Yes Yes Yes

Menu

EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 21 User Settings Menu level 1

User Menu item Function description Options Default values ATR 4500 ATR 4800
01 HOLIDAY settings Delete holiday – once upcoming holiday has been specified Set temp with start and end date EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
02 Heating OFF No – Cancel and return Yes – Output always off No EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
03 Key lock
To disable press [OK] & [ESC] for 5 s
No – Cancel and return
YES – Enable – Any button press without effect
No EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
04 Access protection
To disable press [OK] & [ESC] for 5 s
No – Cancel and return
YES – Enable, manual setpoint change only (no menu access)
No EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
05 On time of load h/week – display of how many hours per week the load has been active h/30 days – display of how many hours per 30 days the load has been active h/year   – display of how many hours per year the load has been active EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
06 Display brightness in idle Device goes to idle after 60 s without button-press 0 %
10 %
25 %
50 %
75 %
100 %
0% EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
07 Unoccupied Setpoint (Heating only) min. setpoint … max. setpoint 18 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25

EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 22 User Settings Menu level 2

User Menu item Function description Options Default values ATR 4500 ATR 4800
01 AUTO settings Change existing schedule – only available once a schedule has been specified Preset 1 – Weekly heating program @work 5 days/week
Preset 2 – Weekly heating program @home
Custom  – creation of weekly program from scratch – 6 events/day
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
02 AT HOME settings Specification of schedule for 1 day – max 6 events (temperature & time) EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
03 Min. setpoint 5 … 30 °C (room control range) 10 … 40 °C (floor control range) room: 5 °C
floor: 10 °C
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
04 Max. setpoint 5 … 30 °C (room control range) 10 … 40 °C (floor control range) room: 30 °C
floor: 40 °C
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
06 Room sensor correction –5.0 … +5.0 K 0 K EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
07 Clock Setting Year ➔ month ➔ day ➔ time EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
08 Auto daylight saving time No – disable
Yes – enable auto daylight saving time
Yes EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
09 Language German, English, French, Italian German EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
10 Firmware info Firmware version EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
88 Reset User data No: Cancel and return
Yes: Long hold [OK] to confirm
No EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25

EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 23 Installer Settings
Access Code for Installer settings: 32
Code Validity: 5 min after first entry
Default values depending on selected preset (see overview presets)

Menu item Function description Options ATR 4500 ATR 4800
01 Preset selection Preset 02 Hydronic UFH – Room            Preset 03 Hydronic Radiator – Room
Preset 04 Blow Convector – Room       Preset 05 Electrical Radiator, Infrared – Room Preset 06 Hydronic UFH – Limiter       Preset 07 Electrical UFH – Floor
Preset 08 Electrical UFH – Limiter
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
02 Application type (control sensor) ROOM      – Room sensor (internal) FLOOR     – Floor probe (external) LIMITER – Room sensor with floor limit EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
03 Floor probe type No – No floor probe fitted 2 kOhm
10 kOhm
12 kOhm
15 kOhm
33 kOhm
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
04 Min. floor limit in °C 10 … 39 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
05 Max. floor limit in °C 11 … 40 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
06 Control method PWM              ➔ 20 min, 15 min, 10 min, 5 min
2 point control ➔ 0.5 K Hysteresis ➔ ON/Off time 1…10 min
0.1 K Hysteresis
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
07 Actuator type nC: normally closed valves no: normally open valves EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
08 Universal input configuration HEAT/COOL – Automatic Heat/Cool changeover depending on input status HEAT ONLY  – Output off in Cool Mode
SETBACK      – Unoccupied Mode when input is energized PRESENCE    – Unoccupied Mode when input is de-energized DEACTIVATE – Ignore input signals
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
09 Optimum start No – disable
YES – enable optimum start (Heating/Cooling will start in adaptive way to have reached demanded temperature at specified event time
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
10 Valve protection No – Disable
YES – Enable à Max. idle time: 0…14 days à Min exercise time: 0 …10 min
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
11 Temporal limit acc. to EN50559 No – Disable
YES – Enable (5 Min off time per hour)
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
12 Window open detection No – Disable
YES – Enable ➔ WOD Threshold 0.1…5.0 K ➔ WOD Guard period: 0 … 9 min ➔ WOD
➔ event duration: 10 … 90 min
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
13 Frost protection No – Disable
YES – Enable (Min temp: 5 °C ROOM/LIMITER, Min temp: 10 °C FLOOR)
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25
99 Ex-factory reset No – Cancel & go back
YES – Long hold [OK] to confirm
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25 EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 25

AUTO Schedule Presets

Preset 1 – At work 5 days / week
Monday – Thursday

Event / Schaltzeit 1 2 3 4
Zeit 06h00 08h30 17h00 22h00
Sollwert 21,5 °C 19,0 °C 21,5 °C 18,0 °C

Friday

Event / Schaltzeit 1 2 3 4
Zeit 06h00 08h30 17h00 23h00
Sollwert 21,5 °C 19,0 °C 21,5 °C 18,0 °C

Saturday

Event / Schaltzeit 1 2
Zeit 08h00 23h00
Sollwert 21,5 °C 18,0 °C

Sunday

Event / Schaltzeit 1 2
Zeit 08h00 22h00
Sollwert 21,5 °C 18,0 °C

Preset 2 – At home 7 days/week
Monday – Thursday

Event / Schaltzeit 1 2
Zeit 06h00 22h00
Sollwert 21,5 °C 18,0 °C

Friday

Event / Schaltzeit 1 2
Zeit 06h00 23h00
Sollwert 21,5 °C 18,0 °C

Saturday

Event / Schaltzeit 1 2
Zeit 08h00 23h00
Sollwert 21,5 °C 18,0 °C

Sunday

Event / Schaltzeit 1 2
Zeit 08h00 22h00
Sollwert 21,5 °C 18,0 °C

Error indication

The device indicates a temperature sensor error as follows.EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Error indicationIn case of the error indication, please check the proper functioning of the connected probe.
EBERLE ATR 4500 Surface Mounted Digital Temperature Controller - Symbol 24 This product should not be disposed of with household waste. Please recycle the products where facilities for electronic waste exist. Check with your local authorities for recycling advice.

EBERLE logoEBERLE Controls GmbH
Klingenhofstr. 71
90411 Nuremberg
Germany
info@eberle.de
www.eberle.de

Documents / Resources

EBERLE ATR 4500 Surface Mounted Digital Temperature Controller [pdf] Instruction Manual
5671954 57 600, 5671944 58 600, ATR 4500 Surface Mounted Digital Temperature Controller, ATR 4500, Surface Mounted Digital Temperature Controller, Mounted Digital Temperature Controller, Digital Temperature Controller, Temperature Controller, Controller

References

Leave a comment

Your email address will not be published. Required fields are marked *