Dwyer E-71 Series V4 Flotect Vane Operated Flow Switch

Dwyer E-71 Series V4 Flotect Vane Operated Flow Switch-fig1

PRODUCT OVERVIEW

Dwyer E-71 Series V4 Flotect Vane Operated Flow Switch-fig2

Rugged and reliable the Flotect® V4 Vane Operated Flow Switch operates automatically to protect equipment and pipeline systems against damage from reduction or loss of flow. The V4 is time tested being installed in thousands of pipelines and processing plants around the world. A unique magnetically actuated switching design gives superior performance. There are no bellows, springs, or seals to fail. Instead, a free-swinging vane attracts a magnet within the solid metal switch body, actuating a snap switch by means of a simple lever arm.

FEATURES

  • Leak proof body machined from bar stock
  • Choice of custom vane calibrated for your application, Model V4, or field adjustable multilayer vane, Model V4-2-U (see set point chart on page 4)
  • Weatherproof, designed to meet NEMA 4
  • Explosion-proof (listing included in specifications)
  • Installs directly and easily into pipeline with a thredolet, tee, or flange (see application drawings on page 4)
  • Can be used in pipes 1-1/2˝ and up
  • Electrical assembly can be easily replaced without removing the unit from installation so that the process does not have to be shut down
  • High pressure rating of 1000 psig (69 bar) with the brass body and 2000 psig (138 bar) with the 316 SS body

APPLICATIONS

  • Protects pumps, motors and other equipment against low or no flow
  • Controls sequential operation of pumps
  • Automatically starts auxiliary pumps and engines
  • Stops liquid cooled engines, machines and processing when coolant flow is interrupted
  • Shuts down burner when air flow through heating coil fails
  • Controls dampers according to flow

Notes:

  • Check all ratings given in the instructions and on the product to make sure that the product is suitable for your application. Do not exceed electrical ratings, pressure ratings, or temperature ratings of the product.
  • Disconnect power supply before beginning installation to prevent possible equipment damage or electrical shock.

MAINTENANCE

Inspect and clean wetted parts at regular intervals. The cover should be in place at all times to protect the internal components from dirt, dust, and weather, and to maintain hazardous location ratings. Disconnect device from the supply circuit before opening to prevent ignition of hazardous atmosphere. Repairs to be conducted by Dwyer Instruments, Inc. Units in need of repair should be returned to the factory prepaid.

SPECIFICATIONS

  • Service: Gases or liquids compatible with wetted materials.
  • Wetted Materials: Vane: 316 SS; Body: Brass or 316 SS standard; Magnet keeper: 430 SS standard, 316 SS optional; Options: Other materials also available, consult factory (e.g. PVC, hastelloy, nickel, monel, titanium).
  • Temperature Limit: -4 to 275°F (-20 to 135°C) standard, MT high temperature option 400°F (205°C) [MT option not UL, CSA, ATEX or IECEx] ATEX and IECEx options, ambient temperature -4 to 163°F (-20 to 73°C); Process temperature -4 to 163°F (-20 to 73°C).
  • Pressure Limit:
    • Brass body 1000 psig (69 bar), 316 SS body 2000 psig (138 bar), optional 5000 psig (345 bar) available with 316 SS body and SPDT switch only. Enclosure Rating: Weatherproof and explosion-proof. Listed with UL and CSA for Class I, Groups C and D;
    • Class II, Groups E, F, and G.
    • ATEX 2813 II 2 G Ex db IIB T6 Gb -20°C≤Tamb≤73°C.
    • -20°C≤Process Temp≤73°C.
    • EU-Type Certificate No.: KEMA 03 ATEX 2383.
  • ATEX Standards: EN60079-0: 2012 + A11: 2013; EN60079-1: 2014.
  • IECEx Certified: For Ex db IIB T6 Gb -20°C≤Tamb≤73°C. -20°C≤Process Temp≤73°C.
  • IECEx Certificate of Conformity: IECEX DEK 11.0071.
  • IECEx Standards: IEC 60079-0: 2011; IEC 60079-1: 2014.
  • Zone I. Also FM approved.
  • Switch Type: SPDT snap switch standard, DPDT snap switch optional. Electrical Rating: UL, FM, ATEX and IECEx models 10A @ 125/250 VAC (V~). CSA models: 5A @ 125/250 VAC (V~); 5A res., 3A ind. @ 30 VDC (V ). MV option: 1A @125 VAC (V~); 1A res., .5A ind. @ 30 VDC (V ). MT option: 5A @ 125/250 VAC (V~). [MT and MV option not UL, CSA, FM, ATEX or IECEx].
  • Electrical Connections: UL and CSA models: 16 AWG, 6˝ (152 mm) long. ATEX or IECEx unit: Terminal block.
  • Conduit Connection: 3/4˝ female NPT or M25 x 1.5 with -BSPT option.
  • Process Connection: 1-1/2˝ male NPT or 1-1/2˝ male BSPT.
  • Mounting Orientation: Within 5° of vertical for proper operation. Units for horizontal installation (vertical pipe with up flow) available.
  • Set Point Adjustment: For universal vane: five vane combinations.
  • Weight: 4 lb 8 oz (1.9 kg).
MODEL CHART
Example V4 -SS -3 1 6 -C -F 2 S 1 V4-SS-316-C-F2S1
Construction V4                 1 Brass body, SPDT switch
Construction Options   SS 2 D U                 316 SS body Type 2 body style DPDT switch

Universal vane (omit for a custom vane)

Magnet Keeper Material Options     1

3

              430 SS (standard)

316 SS

Vane Material Options       1

2

3

4

5

            316 SS (standard)

Carpenter 20 Hastelloy B Hastelloy C Monel

Body Material Options         1

2

3

4

5

6

7

          Brass (standard) Carpenter 20 CPVC*

Hastelloy B Hastelloy C

316 SS (must also use SS construction selection) Monel

Other Options           AT BSPT IEC EPOXY FSV FTR HP

HV MT MV NACE NB NH SW TBC TRD TRI

V

        ATEX

1-1/2˝ female BSPT process connection, M25 x 1.5 conduit connection IECEx

Epoxy coated housing Full swing vane

Flow test report

High pressure*, 5000 psi (345 bar) (only with SS body) Hinged vane

High temperature* (see specifications for rating)

Gold contact snap switch* (see specifications for rating) NACE heat treated body*

Neoprene boot*

No electrical housing* Socket weld connection*

Terminal block wire connections* Time delay relay* (on flow decrease) Time delay relay* (on flow increase) Vertical up flow applications

Flange*             F       Flange process connection
Flange Size               2

2.5

3

4

   

2-1/2˝

Flange Material                 C S M B H   Carbon steel 316 SS

Monel Hastelloy B Hastelloy C

Flange Rating                   1

3

6

9

150#

300#

600#

900#

Bushing*             B       Bushing process connection
Bushing Size               1

2

4

   

2-1/2˝

Bushing Type                 H F   Hex Flush
Bushing Material                   B C S 4 Brass Carbon steel 316 SS

304 SS

Tee*             T       Tee process connection
Tee Size               1     1-1/2˝
Tee with Bushing*             TB       Tee with bushing process connection (both same material)
Tee Size               2

3

   

Tee Material and Type                   B0 B1 B2 C CP S P Brass 125 #

Brass 150 #

Brass 250 #

Carbon steel 2000 # (only with 2˝ and 3˝) CPVC SCH 80

316 SS 150 #

PVC SCH 80

*Options that do not have ATEX or IECEx.
Attention: Units without the “AT” suffix are not Directive 2014/34/EU (ATEX) compliant. These units are not intended for use in potentially hazardous atmospheres in the EU. These units may be CE marked for other Directives of the EU.

INSTALLATION

  1. Remove packing material from switch body-cap and remove tape from magnet keeper. Adjust vane length if necessary on multi-layer vanes only (see flow rate charts on next page). Install switch in thredolet previously welded to line. In some cases, it may be necessary to install the switch in a flange or tee (see installation drawings on next page). Note: extreme care must be exercised in welding the fitting to the line so that it is plumb and level.
    Adjustment of Multi-layer Vane
    Remove only those layers which are too long. Leave the smaller layers to reinforce the vane. The longest vane fits 6˝ (150 mm) or larger pipe, the second longest vane fits 4˝ (100mm) pipe, etc. Actuation-Deactuation rates are shown in the charts on the next page. To remove vane layers, proceed as follows:
    • Remove the two screws and lockwashers holding the layers together. Do not lose these special corrosion resistant type 316 stainless steel screws and lockwashers.
    • Remove the unwanted layers.
    • Resecure the vane with the original two screws and lockwashers.
      1. If using a product with the 316 SS vane block option, a second pair of screws are included in the package. Resecure the vane with the correct screws per the below:
        # of Vanes Used Use Screw Length
        1,2 7/16˝ (included in box)
        3, 4, 5 1/2˝ (pre-installed)
    • With a hammer, lightly peen the ends of the screws so that they can’t back out.
    • If you lose the screws or lockwashers, don’t replace with other parts which may corrode and break. That will void the warranty and might cause severe damage to equipment located downstream of the switch.
      Note: Custom vane units have been calibrated at factory to meet requirements. Do not change.
  2. The arrow on the side of the switch must point in the direction of flow.
  3. Wiring: UL and CSA units only: thread connecting wires through conduit and connect. Wire in accordance with local electrical codes.
    • Black – Common
    • Blue – N.O.
    • Red – N.C.
      Note: Double pole, double throw switches have dual black, blue and red leads. These are connected in the same manner as single pole, double throw switches, as described above.
      ATEX and IECEx Installation Instructions
      • Cable Connection
        The cable entry device shall be certified in type of explosion protection flameproof enclosure “d”, suitable for conditions of use and correctly installed. Cable entry may exceed 70°C. Conductors and cable gland rated ≥95°C shall be used.
      • Conduit Connection
        An Ex d certified sealing device such as a conduit seal with setting compound shall be provided immediately to the entrance of the valve housing. Cable entry may exceed 70°C. Conductors and cable gland rated ≥95°C shall be used. Note: The switch is deactivated and contacts are in normal condition when there is no flow in the line.
  4. Make sure conduit or cable are properly sealed. Electrical components must be kept free of moisture, including condensation, at all times.
    CAUTION
    To prevent ignition of hazardous atmosphere, disconnect the device from the supply circuit before opening. Keep assembly tightly closed when in operation.
    Note: ATEX and IECEX units only: The temperature class is determined by the maximum ambient and or process temperature. Units are intended to be used in ambient of -20°C≤Tamb≤73°C. Units may be used in process temperatures up to 133°C providing the enclosure and switch body temperature do not exceed 73°C. The standard Temperature Class is T6 Process Temp ≤73°C.

    Dwyer E-71 Series V4 Flotect Vane Operated Flow Switch-fig3

  5. For units supplied with both internal ground and external bonding terminals, the ground screw inside the housing must be used to ground the control. The external bonding screw is for supplementary bonding when allowed or required by local code. When external bonding conductor is required, conductor must be wrapped a minimum of 180° about the external bonding screw. See below.

    Dwyer E-71 Series V4 Flotect Vane Operated Flow Switch-fig4 Dwyer E-71 Series V4 Flotect Vane Operated Flow Switch-fig5

    Dim V4 in [mm] V4-2 in [mm]
    A 8-3/16 [207.96] 8 [203.20]
    B 6 [152.40] 6-3/4 [171.45]
    C 4-11/16 [119.06] 3-15/16 [100.01]
    D 1 [25.40] 1-3/4 [44.45]
    E 1-5/16 [33.34] 9/16 [14.30]
    F 7/8 [22.23] 11/16 [17.63]
    G 11/16 [17.46] 1/2 [12.70]
    Ref # Standard V4 ATEX/IECEx
    1 N/A Cover lock.
    2 N/A External ground
    3 Explosion-proof housing with 3/4˝ Explosion-proof housing with 3/4˝
      female NPT conduit connection female NPT conduit connection
    4 16 AWG, 6˝ (152 mm) long terminal block
    5 Internal Internal ground
    6 Magnet arm and switch assembly Magnet arm and switch assembly
    7 Switch body of SAE 72 Brass or Switch body of SAE 72 Brass or
      316 SS 316 SS
    8 Five layer vane, 316 SS, designed Five layer vane, 316 SS, designed
      for 1/2˝ to 8˝ pipes. Usable in larger for 1/2˝ to 8˝ pipes. Usable in larger
      pipe sizes pipe sizes
    9 Magnet keeper of 430 SS Magnet keeper of 430 SS
    10 Vane block of 316 SS Vane block of 316 SS

V4 UNIVERSAL VANE FLOW CHARTS

Values shown in both charts are nominal. If normal flows exceed actuation rates by less than 10%, custom vanes are recommended. Figures are based on standard vertical installation in a 1-1/2˝ thredolet in a horizontal run of pipe.

APPROXIMATE ACTUATION/DEACTUATION FLOW RATES FOR COLD WATER – UPPER FIGURES IN GPM. LOWER FIGURES IN LPM
Vane Layers 1.5˝ Pipe 2˝ Pipe 3˝ Pipe 4˝ Pipe 6˝ Pipe 8˝ Pipe 10˝ Pipe 12˝ Pipe 14˝ Pipe 16˝ Pipe 18˝ Pipe 20˝ Pipe
1 7-3 15-8 45-22 95-40 210-120 375-175 600-300 900-450 1200-600 1400-800 2000-1000 2400-1200
  26.67-11.67 56.7-30 167-83.3 367-150 800-450 1417-667 2267-1133 3400-1700 4550-2267 5300-3033 7567-3783 9083-4550
1 and 2   7-4 23-14 50-35 130-90 230-150 450-250 650-350 900-500 1200-650 1450-800 1800-1000
    26.7-15 86.7-53.3 190-132 500-333 867-567 1700-950 2467-1317 3400-1900 4550-2467 5483-3033 6817-3783
1, 2, and 3     11-7 27-19 80-60 160-115 300-180 450-275 600-350 750-450 1000-600 1200-700
      41.7-26.7 102-71.7 300-233 600-433 1133-683 1700-1033 2267-1317 2750-2083 3783-2267 4550-2650
1, 2, 3, and 4       17-12 60-45 120-90 230-150 310-200 430-280 550-360 700-450 850-550
        65-45 233-167 450-333 867-567 1167-750 1633-1067 2083-1367 2650-1700 3217-2083
1, 2, 3, 4, and 5         40-30 80-65 135-100 200-140 290-200 360-250 460-325 575-400
          152-113 300-250 517-383 750-533 1100-750 1367-950 1733-1233 2183-1517
Note: Actuation rates are based on cold water at a specific gravity of 1.0. For fluids of different specific gravity, actuation rates may be approximated by dividing the rate shown by the square root of the specific gravity.
APPROXIMATE ACTUATION/DEACTUATION FLOW RATES FOR AIR – UPPER FIGURES IN SCFM. LOWER FIGURES IN LPS
Vane Layers 1.5˝ Pipe 2˝ Pipe 3˝ Pipe 4˝ Pipe 6˝ Pipe 8˝ Pipe 10˝ Pipe 12˝ Pipe 14˝ Pipe 16˝ Pipe 18˝ Pipe 20˝ Pipe
1 32-17 65-32 210-105 400-200 950-475 1550-850 2400-1300 3450-1900 4700-2600 6400-3500 8000-4400 10000-5500
  15-8 30-20 100-50 190-90 450-220 730-400 1100-600 1600-900 2200-1200 3000-1700 3800-2100 4700-2600
1 and 2   23-13 120-70 195-140 550-375 1100-700 1850-1200 2700-1750 3400-2200 4800-3100 6000-3900 7400-4800
    10-6 60-30 90-70 260-180 520-330 870-570 1300-800 1600-1000 2300-1500 2800-1800 3500-2300
1, 2, and 3     60-48 135-100 375-265 725-500 1200-850 1850-1300 2600-1800 3350-2350 4300-3000 5300-3700
      30-20 60-50 180-130 340-240 570-400 870-610 1200-800 1600-1100 2000-1400 2500-1700
1, 2, 3, and 4       65-50 260-200 500-400 875-700 1250-1000 1900-1500 2500-2000 3100-2500 3900-3100
        30-20 120-90 240-190 410-330 590-470 900-710 1200-900 1500-1200 1800-1500
1, 2, 3, 4, and 5         130-100 310-250 650-525 1000-800 1600-1250 2200-1750 2800-2250 3550-2850
          60-50 150-120 310-250 470-380 760-590 1040-830 1300-1100 1700-1300
Note: Actuation rates are based on air at standard conditions. For gases at other pressures, temperatures, or specific gravities, consult factory for equivalent flow approximations.

APPLICATION DRAWINGS FOR FLOTECT® AUTOMATIC FLOW SWITCHES

Dwyer E-71 Series V4 Flotect Vane Operated Flow Switch-fig6
Dwyer E-71 Series V4 Flotect Vane Operated Flow Switch-fig7