datanab-logo

DATA NAB MBus-WTH-LCD-ETH Wall Temp Humidity Sensor

DATA-NAB-MBus-WTH-LCD-ETH-Wall-Temp-Humidity-Sensor-product

Product Specifications: 

  • Model: MBus_WTH_LCD_ETH & MBus_WTH_LCD_ETH_EXT
  • Application: Temperature and Humidity Monitoring
  • Output Signals: 4-20mA, 0-5V, 0-10V
  • Communication Ports:
    • MBus_WTH_LCD_ETH: RS485 Modbus-RTU, Ethernet Modbus TCP
    • MBus_WTH_LCD_ETH_EXT: RS485 Modbus-RTU
  • Power Supply:
    • If not using analog output transducers: 12-24VAC/DC +/- 10%
    • If using analog output transducers: 15-24VAC/DC +/- 10%

Product Usage Instructions

Configuration:
The sensor can be configured using the buttons and LCD display.

Communication:
For MBus_WTH_LCD_ETH:

  • RS485 communications port for Modbus-RTU at 19.2/9600 Baud
  • Ethernet Port for Modbus TCP communication over IP

Modbus Register List:
Default RS485 Comm Parameters:

  • Baud Rate: 115200, Data Bits: 8, Parity: None, Stop Bit: 1

The default Modbus-ID for Modbus-RTU over RS485 communication is set to 1. The default IP Address for Modbus-TCP over IP communication is192.168.0.3. Use Function Code 3 (Read Holding Registers) to read values and Function Code 6 (Write Single Register) to write values.

Analog Output:
Analog output jumper settings:

  • 1=0-10V, 2=0-5V, 3=4-20mA (Read Only)

Room Temperature and Humidity Readings
Register Addresses:

  • Room Temp Reading in DegF x10: Register 100
  • Room Temp Reading in DegC x10: Register 101
  • Humidity Reading in %RH x10: Register 304

The MBus_WTH_LCD_ETH and MBus_WTH_LCD_ETH_EXT Modbus-enabled temperature and humidity sensors are designed for environment monitoring in industrial, commercial, and residential temperature & humidity applications.

Features

DATA-NAB-MBus-WTH-LCD-ETH-Wall-Temp-Humidity-Sensor-fig- (1)DATA-NAB-MBus-WTH-LCD-ETH-Wall-Temp-Humidity-Sensor-fig- (2)

  • The sensor can be configured using buttons & LCD Display
  • High-performance digital sensors and circuits to ensure accurate measurement and temperature compensation.
  • Good long-term stability and reliability
  • Fast response
  • Multiple output signals selectable: 4-20mA, 0-5V or 0-10V
  • RS845 communications port for Modbus-RTU, 19.2/9600 Baud
  • Ethernet Port for Modbus TCP communication over IP

Relative Humidity

  • Sensor: capacitance polymer
  • Operating Temperature: 0~50°C
  • Operating Humidity Range: 0~98% RH (Non condensing)
  • Output: 4-20mA, 0-5V or 0-10V, RS485 Modbus-RTU
  • Accuracy: 5% RH (25°C, 20~80% RH)
  • Hysteresis: < ±1% RH
  • Response time: < 10s (25°C, in slow air)
  • Drift: < ±0.5% RH / year

Temperature

  • Sensor: Internal 10K Thermistor
  • Operating Temperature Range: -30~50°C (-22~122°F)
  • Output: 4-20mA, 0-5V or 0-10V, RS 485
  • Accuracy: < ±0.5°C @ 25°C

General

  • Power Supply:
    • If NOT using 0-10V or 4-20mA output transducers: 12-24VAC/DC +/- 10%
    • If using 0-10V or 4-20mA output transducers: 15-24VAC/DC +/-10%
  • Power Consumption:
    • 12VDC Power supply: assume 2 watts per sensor
    • 24VAC Power supply: assume 1VA per sensor
    • Current Output Load: < 500Ω
    • Display: LCD screen for wall / outdoor mount and duct mount
    • Display Resolution: 0.1°C, 0.1% RH
    • Operating Temperature: -30~50°C, 0~98% RH (Non condensing) The humidity sensor only accurate from 0~50°C.
    • Storage Temperature: -30~60°C
    • Plastic Housing: Flammability rating UL 94V0 file E194560
    • Protection: IP65

Enclosure views and Dimensions

DATA-NAB-MBus-WTH-LCD-ETH-Wall-Temp-Humidity-Sensor-fig- (3)

Housing Dimensions (in mm) for both models. Probe Dimensions (in mm) for MBus_WTH_LCD_ETH

DATA-NAB-MBus-WTH-LCD-ETH-Wall-Temp-Humidity-Sensor-fig- (4)

Probe Dimensions for MBus_WTH_LCD_ETH_EXT (mm)

DATA-NAB-MBus-WTH-LCD-ETH-Wall-Temp-Humidity-Sensor-fig- (5)

Probe Dimensions for MBus_WTH_LCD_ETH_EXT (mm)

DATA-NAB-MBus-WTH-LCD-ETH-Wall-Temp-Humidity-Sensor-fig- (6)

Inside view & details

DATA-NAB-MBus-WTH-LCD-ETH-Wall-Temp-Humidity-Sensor-fig- (7)

Wiring Diagram

DATA-NAB-MBus-WTH-LCD-ETH-Wall-Temp-Humidity-Sensor-fig- (8)

Modbus Register List

  • Default RS485 Comm Parameters: 115200 baud, 8 data bits, no parity, 1 stop bit. (configurable under “misc” LCD menu)
  • Default Modbus-ID for Modbus-RTU over RS485 communication is: 1. (configurable under “misc” LCD menu)
  • Default IP Address for Modbus-TCP over IP communication is: 192.168.0.3 (configurable under “misc” LCD menu)
  • Use Function Code 3 (Read Holding Registers) to read values and Function Code 6 (Write Single Register) to write values.

DATA-NAB-MBus-WTH-LCD-ETH-Wall-Temp-Humidity-Sensor-fig- (9)

For more detailed modbus register information, please email support@datanab.com

FAQ

Q: How can I change the Modbus-ID for Modbus-RTU communication?
A: You can change the Modbus-ID under the LCD Miscellaneous menu.

Q: What is the default IP mode for Modbus-TCP communication?
A: The default IP mode is Static. You can change it to DHCP under the miscellaneous LCD menu.

Documents / Resources

DATA NAB MBus-WTH-LCD-ETH Wall Temp Humidity Sensor [pdf] Owner's Manual
MBus_WTH_LCD_ETH, MBus_WTH_LCD_ETH_EXT, MBus-WTH-LCD-ETH Wall Temp Humidity Sensor, Wall Temp Humidity Sensor, Temp Humidity Sensor, Humidity Sensor, Sensor

References

Leave a comment

Your email address will not be published. Required fields are marked *