Danfoss-LOGO

Danfoss VLT FC 101 HVAC Basic Drive

Danfoss-VLT FC-101-HVAC-Basic-Drive-PRODUCT

Makes your buildings perform

Danfoss commitment
Danfoss’ longstanding experience in applying drives in HVAC systems has enhanced our ability to design a HVAC Basic drive to the exact needs in simple mass produced applications.

Save energy and CO2 emission
Energy savings through more than 1.5 million VLT® HVAC Drives installed worldwide are estimated at 285 million MWhrs a year. This equals the annual energy consumption of 60 million households and has an impact on the annual CO₂ emissions – a reduction of 180 million tonnes!

A wealth of knowledge
The various applications incorporated within high performance buildings are well understood by Danfoss and as global market leader we have built a wealth of knowledge and developed products and technology to ensure we meet and shape future trends in HVAC.

Danfoss experts with HVAC application knowledge support you in making an efficient system design and investing wisely for documented returns.

Certify your building
Today the prime focus is on overall buildings performance which includes design, construction, efficiency, sustainability and the environmental impact of buildings in the future.
Energy efficient products form part of this overall plan. In many countries around the world the evaluation of high performance buildings falls under the banner LEED. Danfoss drives help you to reduce the energy consumption in your building and to fulfill the highest standards set by these certification bodies.

Ideal for simple fans, pumps, and compressors

User-friendly, distributed intelligence and reduced power consumption are beneficial for fan applications. Basic AHU functions enable the VLT® HVAC Basic Drive to control a wide range of functions. Pump-specific features developed in cooperation with OEMs, contractors and manufacturers around the world.

Fire Override Mode

Fire Override Mode prevents the VLT® HVAC Basic Drive from stopping for self-protecting reasons. In this mode it will continue vital fan operation regardless of control signals, warnings or alarms.
Fire Override Mode helps keep fire escape routes free of smoke and ensures secure and continued operation within applications such as stair-well pressurization, car park exhaust fans, smoke exhaust and essential service functions.
Fire mode is clearly indicated on the display to prevent any confusion. When set, the drive will override self protection and will continue operation despite the possibility of permanent damage in case of over-heating or overload. The vital goal is to keep the motor running even if it means self-destruction.

Skip frequencies
By pressing a few buttons on the Local Control Panel the drive can be set to avoid frequency bands at which connected fans create resonances in the ventilation system. This reduces vibration, noises and wear on equipment.
No load / Broken Belt warning
Many fan applications are still operated by a belt. This function monitors whether the belt is still in use, has ceased operation due to wear and tear.
The built-in maintenance program helps you to ensure belt inspection at regular intervals.

Flying start
The drive can detect speed and direction of a freely spinning fan or pump and “catch” it at the right speed.
This feature prevents violent starts and tear on the equipment.

Sleep Mode
In situations with low or no flow, the drive enters sleep mode to conserve energy. When the pressure falls below the pre-defined setpoint, the drive starts automatically. Compared to continuous operation this method reduces energy costs and equipment wear and tear, extending the lifetime of the application.

Sensorless pump control
Eliminate the need for external pressure transmitters, using this drive.
The drive delivers sensorless pump control, meaning no external pressure transmitter is required.

Constant torque for air compressors
The drive has a dedicated constant torque mode for air compressor applications.

Quiet operation
Direct control of the cooling fan ensures that the drive operates as quietly as possible. The cooling fan adjusts precisely to the load, for optimum efficiency and energy savings.

Simple timer function
There is no need for an external timer, since you can use the integrated timer in the drive. This simple timer function is useful for testing the motor, for example in Fire Mode applications.

Use the motor of your choice
VLT® HVAC Basic Drive FC 101 is equally compatible with induction and permanent magnet (PM) motors for the full power range. There is no need to change out motor type when retrofitting the drive.

More robust when power is unstable
Voltage dips or power interruptions in the grid cause huge problems in your systems. It is reassuring to know that integrated power loss ride-through capability in the drive ensures more stable and robust operation.

Voltage sag immunity
With Semi 47 certification, you can be sure that this drive is performs robustly, whatever the quality of the power supply.

Improved power factor with VLT® Advanced Harmonic Filter AHF 010
Are you using VLT® Advanced Harmonic Filter AHF 010 to mitigate harmonics?
Use the relay output on the drive to control this passive harmonic filter, to achieve a higher power factor at zero load or partial load.

VLT® HVAC Basic Drive

The VLT® HVAC Basic Drive is a competitive drive for simple applications – with basic needs.

Easy commissioning
The Quick Menu wizard makes it easy to set up and operate the drive.
In situations where there is no mains power, use the VLT® Mains-Free Interface tool. It gives you an easy way to configure drives on the production line, and saves time and effort for installation and service technicians.

Maintenance free
Due to a series of self-protecting and monitoring features, the VLT® HVAC Basic Drive is maintenance free, except for general cleaning.
Replacement of internal fans or capacitors is normally not required during lifetime.

Save space
Due to its ultra compact design, the VLT® HVAC Basic Drive is easily mounted inside a HVAC unit or panel, reducing overall enclosure costs.

Built-in mains filters
The standard integrated DC coils comply with EN 61000-3-12 reducing losses in mains and ensuring reliable operation in the whole grid. The DC coils increase the lifespan of the DC link capacitors and they also ensure that the drive can operate motors to their full performance. Integrated DC coils save the cost for adding external filters.

Reduced installation costs

  • Built-in HVAC functions reducing need for other system components
  • Ease of installation and set-up

Competitive performance

  • Up to 98.5% efficiency
  • Automatic Energy Optimisation
  • System diagnostics

VLT® HVAC Basic Drive
The VLT® HVAC Basic Drive is a competitive drive for simple applications – with basic needs.
Categories according

VLT® HVAC Basic Drive product range:

  • 3 x 200 – 240 V……………. 0.25 – 45 kW
  • 3 x 380 – 480 V……………. 0.37 – 90 kW
  • 3 x 525 – 600 V……………. 2.2 – 90 kW

Available enclosure ratings:

  • IP 20
  • IP 21/UL Type 1 (separate option kit)
  • IP 54

Intuitive control panel

  • 2-line alphanumeric display
  • 7 languages + numeric menu
  • Status LED’s
  • Quick menus (wizard for open loop applications, closed loop applications, and motor setup)
  • IP 54 when mounted in a panel front
  • Password protection
  • Same parameter structure as the Danfoss VLT® FC – family drives
  • Removable under operation (IP20)
  • Upload and download parameters (LCP copy function)
  • VLT® Control Panel LCP 32 makes it easier to program the drive, with a choice of five languages in the display.

Comparision of limits EN 55011/61800-3

The built-in EMC filter makes the VLT® HVAC Basic Drive conform to the limits for category C1 and C2 according to EN 61800-3, with no additional external components needed, even with long motor cables.

However, more importantly in practice is the compliance with the environmental standard EN 55011, Class B (residential) and Class A1 (industrial). This ensures reliable system operation in full compliance with all requirements for EMC in the operating environments and eliminates required product warnings and restrictions prescribed by the standard, if the drive used does not conform to category C1.

Danfoss-VLT FC-101-HVAC-Basic-Drive-FIG- (1)

Enclosure protection options

Danfoss-VLT FC-101-HVAC-Basic-Drive-FIG- (2)

IP 20,Type1/IP21, IP54 enclosures
The installation volume and/or the mounting surfaces are minimized.

The functional sections nevertheless fulfil the highest requirements even for applications with ambient temperatures up to 50° C.

Compact design
Optimized efficiency and intelligent cooling technology ensure compact and service-friendly design.
Supplementary equipment such as EMC filters and harmonics suppression are integrated into the ultra compact enclosure.

Save installation time
The IP 20, Type 1/IP 21 (with option) and IP 54 series is designed for easy accessibility and time-saving installation. Mechanical fastening points are easy to access from the front even with automatic tools. All terminals are sufficiently dimensioned and clearly marked behind a plate. Accessories for bonding screened cables are included making compact enclosures easier to install.

Danfoss-VLT FC-101-HVAC-Basic-Drive-FIG- (3)

Freedom to change settings prior to installation

VLT® Mains-free Interface
Did you know you can change the settings of the FC 101 drive with no connection to mains power supply? Just connect to a PC using the VLT® Mains-free Interface.
The VLT® Mains-free Interface connects to the PC via a USB 2.0 interface.
A Mini-B USB connector is located at the front, and a standard drive connector is located on the back. Both the VLT® Mains-free Interface and the drive get a supply of current from the USB ports on the PC.

For drive enclosure sizes H1–H5 and I2–I4:
The required current is within the standard capability of a single USB port. Use a single USB type A connector.

For drive enclosure sizes H6–H10 and I6–I8:
More than 500 mA current is required (500 mA is the maximum standard current a USB port can deliver).

Connect to the PC using a double USB type A cable.
The drive obtains the required current via both of the USB ports. The second USB port is marked “Auxiliary power only”.

Danfoss-VLT FC-101-HVAC-Basic-Drive-FIG- (4)

Technical data

Main supply (L1, L2, L3)
Supply voltage 200 – 240 V ±10%
Supply voltage 380 – 480 V ±10%
Supply voltage 525 – 600 V ±10%
Supply frequency 50/60 Hz
Displacement power factor (cos ф) > 0.98 (near unity)
Switching on input supply L1, L2, L3 1–2 times/min.
Harmonic disturbance Meets EN 61000-3-12
Output data (U, V, W)
Output voltage 0 – 100% of supply voltage
Output frequency 0 – 400 Hz
Switching on output Unlimited
Ramp-up and -down times 1 – 3600 sec.
Digital inputs
Programmable digital inputs 4
Logic PNP or NPN programable
Voltage level 0 – 24 V DC
Maximum voltage on input 28 V DC
Input resistance, Ri Approx. 4 kΩ
Analog inputs
Analog inputs 2
Modes Voltage or current
Voltage level 0 to +10 V (scaleable)
Current level 0/4 to 20 mA (scaleable)
Accuracy of analog inputs Max. error: 0.5% of full scale
Analog output
Programmable analog outputs 2
Current range at analog output 0/4 – 20 mA
Max. load to common at analog output (terminal 30) 500 Ω
Accuracy on analog output Max. error: 1% of full scale

Analog outputs can be used as digital outputs

Control card
RS485 interface Up to 115 kBaud
Max. load (10 V) 25 mA
Max. load (24 V) 80 mA
Relay output
Programmable relay outputs 2
Max. terminal load (AC) on 1-3 (break), 1-2 (make) 240 VAC, 2 A and 400 VAC, 2 A
Surroundings/external
 

Enclosure

IP 20/Chassis

(IP 21/Type 1 optional kit)

IP 54

Vibration test 1.14 g
Max. relative humidity 5% – 95% (IEC 721-3-3; Class 3K3

(non-condensing) during operation

Ambient temperature up to 50° C
Galvanic isolation of all I/O supplies according to PELV
Aggressive environment Designed for coated/uncoated 3C3/3C2 (IEC 60721-3-3)
Fieldbus communication
 

Standard built-in:

BACnet Modbus RTU N2 Metasys FLN Apogee FC Protocol
Protection mode for longest possible up-time
– Electronic thermal motor protection against overload
– Temperature monitoring of the heatsink ensures that the frequency converter trips if the temperature reaches 95° C ± 5° C.
– The frequency converter is protected against short-circuits on motor terminals U, V, W.
– The frequency converter is protected against earth faults on motor terminals U, V, W.
– Protection against mains phase loss
Compliance
Semi 47 certified for voltage sag immunity compliance

Electrical data – H and I enclosures

200 – 240 VAC

Enclosure

200 – 240 VAC

IP 20/Chassis H1 H2 H3 H4 H5
PK25 PK37 PK75 P1K5 P2K2 P3K7 P5K5 P7K5 P11K
Typical Shaft Output [kW] 0.25 0.37 0.75 1.5 2.2 3.7 5.5 7.5 11
[HP] 0.33 0.5 1 2 3 5 7.5 10 15
Output Current

(3 x 200 – 240 V)

Continuous [A] 1.5 2.2 4.2 6.8 9.6 15.2 22 28 42
Intermittent [A] 1.7 2.4 4.6 7.5 10.6 16.7 24.2 30.8 46.2
Max. cable size

Mains, motor

[mm2] ([AWG]) 4/10 16/6
Max. Input Current

(3 x 200 – 240 V)

Continuous   [A] 1.1 1.6 2.8 5.6 8.8/7.2 14.1/12 21/18 28.3/24 41/38.2
Intermittent 1.2 1.8 3.1 6.2 9.5/7.9 15.5/13.2 23.1/19.8 31.1/26.4 45.1/42
Environment
Estimated power loss at rated max. load, best case [W] 12 15 21 48 80 97 182 230 369
typically 14 18 26 60 182 120 204 268 386
Weight [kg] 2.0 2.1 3.4 4.5 7.9 9.5
Efficiency [%], best case 97.0 97.3 98.0 97.6 97.1 97.9 97.3 97.5 97.2
typically 96.5 96.8 97.6 97.0 96.3 97.4 97 97.1
Enclosure IP 20/Chassis H6 H7 H8
200 – 240 VAC P15K P18K P22K P30K P37K P45K
 

Typical Shaft Output

[kW] 15.0 18.5 22.0 30.0 37.0 45.0
[HP] 20.0 25.0 30.0 40.0 50.0 60.0
Output Current

(3 x 200 – 240 V)

Continuous [A] 59.4 74.8 88.0 115.0 143.0 170.0
Intermittent [A] 65.3 82.3 96.8 126.5 157.3 187.0
Max. cable size

Mains, motor

[mm2] ([AWG]) 35/2 50/1 95/0 120/(4/0)
Max. Input Current

(3 x 200 – 240 V)

Continuous   [A] 52.7 65.0 76.0 103.7 127.9 153.0
Intermittent 58.0 71.5 83.7 114.1 140.7 168.3
Environment
Estimated power loss at rated max. load, best case [W] 512 658 804 1015 1459 1350
Weight [kg] 24.5 36.0 51.0
Efficiency [%], best case 97.0 96.9 96.8 97.0 96.5 97.3

380 – 480 VAC

 

Enclosure 380-480 VAC

IP 20/Chassis H1 H2 H3
IP 54 NA I2 I3
PK37 PK75 P1K5 P2K2 P3K0 P4K0 P5K5 P7K5
 

Typical Shaft Output

[kW] 0.37 0.75 1.5 2.2 3 4 5.5 7.5
[HP] 0.5 1 2 3 4 5 7.5 10
Output Current

(3 x 380-440 V)

Continuous   [A] 1.2 2.2 3.7 5.3 7.2 9.1 12 15.5
Intermittent [1 min. max] 1.3 2.4 4.1 5.8 7.9 9.9 13.2 17.1
Output Current

(3 x 440-480 V)

Continuous   [A] 1.1 2.1 3.4 4.8 6.3 8.2 11 14
Intermittent [1 min. max] 1.2 2.3 3.7 5.3 6.9 9.0 12.1 15.4
Max. cable size

Mains, motor

IP 20 [mm2] ([AWG])  

4/10

IP 54
Max. Input Current

(3 x 380-440 V)

Continuous   [A] 1.2 2.1 3.5 4.7 6.3 8.3 11.2 15.1
Intermittent [1 min. max] 1.3 2.3 3.9 5.2 6.9 9.1 12.3 16.6
Max. Input Current

(3 x 440-480 V)

Continuous   [A] 1.0 1.8 2.9 3.9 5.3 6.8 9.4 12.6
Intermittent [1 min. max] 1.1 2 3.2 4.3 5.8 7.5 10.3 13.9
Environment
Estimated power loss at rated max. load [W] 13 21 46 46 66 95 104 159
 

Weight

IP 20   [kg] 2.0 2.1 3.3 3.4 4.3 4.5
IP 54 5.3 7.2
Efficiency [%] 97.8 98.0 97.7 98.3 98.2 98.0 98.4 98.2
 

Enclosure 380-480 VAC

IP 20/Chassis H4 H5 H6 H7 H8
IP 54 I4 I6 I7 I8
P11K P15K P18K P22K P30K P37K P45K P55K P75K P90K
 

Typical Shaft Output

[kW] 11 15 18 22 30 37 45 55 75 90
[HP] 15 20 25 30 40 50 60 75 100 125
Output Current

(3 x 380-440 V)

Continuous   [A] 23 31 37 42.5 61 73 90 106 147 177
Intermittent [1 min. max] 25.3 34 40.7 46.8 67.1 80.3 99 116 161 194
Output Current

(3 x 440-480 V)

Continuous   [A] 21 27 34 40 52 65 80 105 130 160
Intermittent [1 min. max] 23.1 29.7 37.4 44 57.2 71.5 88 115 143 176
Max. cable size

Mains, motor

IP 20 [mm2] ([AWG]) 16/6 35/2 50/1 95/0 120/250
IP 54 10/7 35/2 50/1 95/(3/0) 120/(4/0)
Max. Input Current

(3 x 380-440 V)

Continuous   [A] 22.1 29.9 35.2 41.5 57 70 84 103 140 166
Intermittent [1 min. max] 24.3 32.9 38.7 45.7 62.7 77 92.4 113 154 182
Max. Input Current

(3 x 440-480 V)

Continuous   [A] 18.4 24.7 29.3 34.6 49-46 61-57 73-68 89-83 121-113 143-133
Intermittent [1 min. max] 20.2 27.2 32.2 38.1 54-50 67-62 80-74 98-91 133-124 157-146
Environment
 

Weight

IP 20   [kg] 7.9 9.5 24.5 36 51
IP 54 13.8 27 45 65
Efficiency [%] 98.1 98.0 98.1 98.1 97.8 97.9 97.1 98.3 98.3 98.3

525 – 600 VAC

Enclosure

525 – 600 VAC

IP 20/Chassis H9 H10 H6
P2K2 P3K0 P5K5 P7K5 P11K P15K P22K P30K
 

Typical Shaft Output

[kW] 2.2 3.0 5.5 7.5 11.0 15.0 22.0 30.0
[HP] 3.0 4.0 7.5 10.0 15.0 20.0 30.0 40.0
Output Current

(3 x 525 – 550 V)

Continuous   [A] 4.1 5.2 9.5 11.5 19.0 23.0 36.0 43.0
Intermittent 4.5 5.7 10.5 12.7 20.9 25.3 39.6 47.3
Output Current

(3 x 551 – 600 V)

Continuous   [A] 3.9 4.9 9.0 11.0 18.0 22.0 34.0 41.0
Intermittent 4.3 5.4 9.9 12.1 19.8 24.2 37.4 45.1
Max. cable size

Mains, motor

[mm2] ([AWG]) 4/10 10/8 35/2
Max. Input Current

(3 x 525 – 550 V)

Continuous   [A] 3.7 5.1 8.7 11.9 16.5 22.5 33.1 45.1
Intermittent 4.1 5.6 9.6 13.1 18.2 24.8 36.4 49.6
Max. Input Current

(3 x 551 – 600 V)

Continuous   [A] 3.5 4.8 8.3 11.4 15.7 21.4 31.5 42.9
Intermittent 3.9 5.3 9.2 12.5 17.3 23.6 34.6 47.2
Environment
Estimated power loss at rated max. load [W] 8.4 112.0 178.0 239.0 360.0 503.0 607.0 820.0
Weight [kg] 6.6 11.5 24.5
Efficiency [%] 97.0 97.5
Enclosure

525 – 600 VAC

IP 20/Chassis H7 H8
P45K P55K P75K P90K
 

Typical Shaft Output

[kW] 45.0 55.0 75.0 90.0
[HP] 60.0 70.0 100.0 125.0
Output Current

(3 x 525 – 550 V)

Continuous   [A] 65.0 87.0 105.0 137.0
Intermittent 71.5 95.7 115.5 150.7
Output Current

(3 x 551 – 600 V)

Continuous   [A] 62.0 83.0 100.0 131.0
Intermittent 68.2 91.3 110.0 144.1
Max. cable size

Mains, motor

[mm2] ([AWG]) 50/1 95/0 120/ (4/0)
Max. Input Current

(3 x 525 – 550 V)

Continuous   [A] 66.5 81.3 109.0 130.9
Intermittent 73.1 89.4 119.9 143.9
Max. Input Current

(3 x 551 – 600 V)

Continuous   [A] 63.3 77.4 103.8 124.5
Intermittent 69.6 85.1 114.2 137.0
Environment
Estimated power loss at rated max. load [W] 972.0 1182.0 1281.0 1437.0
Weight [kg] 36.0 51.0
Efficiency [%] 98.0 98.4 98.5

Accessories

IP 21/ Type 1 Kit
The IP 21/ Type 1 kit is used for installation of VLT® HVAC Basic Drives in dry environments where dripping water can occour. The enclosure kits are available for all frame sizes.

  • PG 16 and PG 21 holes for cable glands

LCP Panel Mounting Kit
For easy installation of the local control panel in a cabinet door.

  • IP 54 (front)
  • Thumb screws for tool-free installation
  • ncl. 3 meters of cables in industry quality (also available separately)
  • Easy to install

Ordering number LCP & kit

  • 132B0201 (Mounting kit for LCPi ncluding fasteners, 3 m cable and gasket).
  • 132B0200 Alpha-numeric VLT® Control Panel LCP 31 – to be ordered separately for IP20 units – it is delivered as standard for IP 54 units).
  • 132B9221
    VLT® Control Panel LCP 32
    Graphical local control panel with choice of 5 languages: English, Chinese, French, German, or Spanish
  • 132B0203
    FC 101 LCP RJ 45 Plug Converter
    This plug converter enables you to easily extend the cable for remote mounting. Minimum order quantity is 12 sets (1 box).

VLT® Mains-Free Interface

  • 132B9222
    Use this USB 2.0 based programming interface for PC programming of the drives, with no need for mains power.
    Set parameters and flash firmware.
    Use this interface together with VLT® Motion Control Tool MCT 10.

Ordering codes IP21/ Type 1 kit

Danfoss-VLT FC-101-HVAC-Basic-Drive-FIG- (5)

Enclosure IP 21 kit UL Type 1 kit Decoupling plate
H1 132B0212 132B0222 132B0202
H2 132B0213 132B0223 132B0202
H3 132B0214 132B0224 132B0204
H4 132B0215 132B0225 132B0205
H5 132B0216 132B0226 132B0205
H6 132B0217 132B0217 132B0207
H6 132B0217 132B0227 132B0242
H7 132B0218 132B0218 132B0208
H7 132B0218 132B0218 132B0243
H8 132B0219 132B0219 132B0209

Danfoss-VLT FC-101-HVAC-Basic-Drive-FIG- (6)

Minimize energy usage while maximizing comfort levels with VLT® HVAC Basic Drive

The VLT® HVAC Basic Drive is installed on a broad range of heating, ventilation and air conditioning applications in new and existing buildings and infrastructural systems all over the world.

VLT® drives enhance air quality and indoor comfort levels, improve control and save energy, ensure better asset protection, reduce maintenance costs  and increase reliability

The daily load variation in HVAC facilities is considerable. Variable speed control of electrical motors has proved to be one of the most effective costreducing measures available.

VLT® drive delivers reliable, low-energy ventilation for 40 years
Learn how the compact VLT® HVAC Basic Drive FC 101 was installed in an industrial kitchen.
It replaced a VLT® 5 drive, to reduce electricity consumption by 390 MWh each year.

Read the case story
Discover more case stories for the HVAC industry here: http://drives.danfoss.com/industries/hvac/case-stories/#/

Follow us and learn more about AC drives

Documents / Resources

Danfoss VLT FC 101 HVAC Basic Drive [pdf] User Guide
VLT FC 101 HVAC Basic Drive, VLT FC 101, HVAC Basic Drive, Basic Drive, Drive
Danfoss VLT FC 101 HVAC Basic Drive [pdf] User Guide
VLT FC 101 HVAC Basic Drive, VLT FC 101, VLT, HVAC Basic Drive, Basic Drive, Drive

References

Leave a comment

Your email address will not be published. Required fields are marked *