XCT-7 Variable Refrigerant Flow Controls
Owner’s ManualMODEL NAME:
KNX Gateway
Installation and Owner’s Manual
40VCBK17FQEE
1-T-40VCQUE-231020-EN-0
KNX gateway —40VCBK17FQEE 40VCBK27FQEE 40VCBK37FQEE
40VCBK17/27/37FQEE allows a complete and natural integration of air conditioners with KNX control systems.
Compatible with all models of XCT7 line of air conditioners. Each SD outdoor unit, 40VCCR17FQEE required.
Main features:
Compatible with all models of XCT7 line of air conditioners.
- Reduced dimensions. Installation even inside the A.C. indoor unit.
- Quick and non-visible installation.
- External power not required.
- Direct connection to the KNX EIB bus.
- Direct connection to the AC indoor unit.
- Fully KNX interoperable, configuration from ETS.
- Multiple objects for control (of different types: bit, byte, characters…).
- Control of the AC unit based in the ambient temperature read by the own AC unit, or in the ambient temperature read by any KNX thermostat.
- Total Control and Monitoring of the AC unit from KNX, including monitoring of AC unit’s state of internal variables, running hours counter (for filter maintenance control), and error indication and error code.
- AC unit can be controlled simultaneously by the IR remote control of the AC unit and by KNX.
- Max. 8/16/64 indoor units can be connected in one system
Technical Specifications
Connection
Connection of the interface to the AC indoor unit:
Disconnect mains power from the AC unit. Open the front cover of the indoor unit in order to have access to the internal control board. In the control board locate the socket connector marked as ABG1.
Using a 3-wire cable, connect the ABG1 connector from the 40VCBK17/27/37FQEEto the A B G1 connector of the AC unit’s control board.
Fix the 40VCBK17/27/37FQEEinside or outside the AC indoor unit depending on your needs – remember that 40VCBK17/27/37FQEEmust be also connected to the KNX bus. Close the AC indoor unit’s front cover again.
Connection of the interface to the KNX bus:
Disconnect power of the KNX bus. Connect the interface to the KNX TP-1 (EIB) bus using the KNX standard connector (red/grey) of the interface, respect polarity. Reconnect power of the KNX bus.
Connections diagram:
Each Communication Adaptor connects to a single Outdoor Unit.
The 40VCBK17/27/37FQEE can be connected to more than one Communication Adaptor simultaneously.
NOTE: More than one Communication Adaptor can be present in the installation. Please make sure that the address of the Communication Adaptor is correctly set in the ETS. Check section 4.6 for more information.
Configuration and setup
This is a fully compatible KNX device which must be configured and setup using standard KNX tool ETS.
ETS project for this device can be downloaded from: https://www.intesisbox.com/en/carrier-knx-ac-ha-acknx-8_16_64/gateway/ Please consult the README.txt file, located inside the downloaded zip file, to find instructions on how to install the database.
ETS Parameters
When imported to the ETS software for the first time, the gateway shows the following default parameter configuration:
1.1.1 Interface (multiple indoor units)> General configurationWith this configuration it’s possible to send On/Off (Control_ On/Off), change the AC Mode (Control_ Mode), the Fan Speed (Control_ Fan Speed) and also the Setpoint Temperature (Control_ Setpoint Temperature). The Status_ objects, for the mentioned Control_ objects, are also available to use if needed. Objects Status_ AC Ambient Reference Temperature and Status_ Error/Alarm are shown too.
4.1 General configuration
Inside this parameter’s dialog it is possible to activate or change the parameters shown in the Figure 4.1.
4.1.1 Download latest database entry for this product and its User Manual from:
The first field shows the URL where to download the database and the user manual for the product.4.1.2 Intesis Product
This parameter is used to check, before sending the programing, the maximum number of AC units your device supports. Select the version of the gateway that you have:
- 40VCBK17FQEE, if you only want to control up to 8 AC unit.
- 40VCBK27FQEE, if you only want to control up to 16 AC units.
- 40VCBK37FQEE, if you only want to control up to 64 AC units
4.1.3 Number of Indoor Units in ETS
This parameter is used to hide/show communication object according to the number of AC units you need to configure. Value ranges go from 1 to 64. In case you introduce a number higher than the maximum number of units allowed by your license, you will get a warning message. This is just for information and will not block the configuration process. Configurations with more indoor units configured than the ones allowed by the license will not be downloaded correctly.
4.1.4 First Status Updated to KNX
This parameter defines how fast the status is updated to KNX. Depending on the value selected, more or less priority will be assigned to this action. As there are so many parameters available, it is important to consider carefully how to set this parameter.
- If set to “ASAP”, all status communication objects will send its value (if needed).
- If set to “Slow”, all status communication objects will send its value (if needed), but slower than in the previous option (ASAP).
- If set to “Super Slow”, all status communication objects will send its value (if needed), but slower than in the previous option (Slow).
4.1.5 Enable object “Error Code [2byte]”
This parameter shows/hides the Status_ Error Code communication object which shows the indoor unit errors, if occurred, in numeric format.o If set to “Disabled” the object will not be shown.
o If set to “Enabled” the Status_ Error Code [2byte signed value] object will appear.
This object can be read and also sends the indoor unit error, if occurred, in numeric format. If a “0” value is shown that means no error.
4.1.6 Enable object “Error Text Code [14byte]”
This parameter shows/hides the Status_ Error Text Code communication object which shows the indoor unit errors, if occurred, in text format.o If set to “Disabled” the object will not be shown.
o If set to “Enabled” the Status_ Error Text Code object will appear.
This object can be read and also sends the indoor unit error, if occurred, in text format. The errors shown have the same format as in the remote controller and in the error list from the indoor unit manufacturer. If the object’s value is empty, that means there is no error.
4.2 Global mode configuration
1.1.1 Interface (multiple indoor units)> Global Mode ConfigurationAll the parameters in this section are related with the different mode properties and communication objects
The byte-type communication object for Mode works with the DTP_20.105. Auto mode will be enabled with a “0” value, Heat mode with a “1” value, Cool mode with a “3” value, Fan mode with a “9” value and Dry mode with a “14” value.
4.2.1 Enable use of “Operating Mode” objects
This parameter shows/hides the Control_ and Status_ Mode Operating Mode communication objects.4.2.2 Enable use of Mode Heat/Cool objects
This parameter shows/hides the Control_ and Status_ Mode Cool/Heat communication objects.o If set to “Disabled” the objects will not be shown.
o If set to “Enabled” the Control_ and Status_ Mode Cool/Heat objects will appear.
• When a “1” value is sent to the Control_ communication object, Heat mode will be enabled in the indoor unit, and the Status_ object will return this value.
• When a “0” value is sent to the Control_ communication object, Cool mode will be enabled in the indoor unit, and the Status_ object will return this value.
4.2.3 Enable use of + / – object for Mode
This parameter shows/hides the Control_ Mode +/- communication object which let’s you change the indoor unit mode by using two different datapoint types.o If set to “Disabled” the object will not be shown.
o If set to “Enabled” the Control_ Mode +/- object and a new parameter will appear.
. DPT type for +/- Mode Object
This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 1- Decrease / 1-Increase [DPT_1.007] for the Control_ Mode +/- object. The sequence followed when using this object is shown below: Keep in mind that depending on the indoor unit you have and the available features, Auto mode and Dry mode may not be present.
4.2.4 Enable use of bit-type Mode objects (for control)
This parameter shows/hides the bit-type Control_ Mode objects.o If set to “no” the objects will not be shown.
o If set to “yes” the Control_ Mode objects for Auto, Heat, Cool, Fan and Dry will appear. To activate a mode by using these objects a “1” value has to be sent.
4.2.5 Enable use of bit-type Mode objects (for status)
This parameter shows/hides the bit-type Status_ Mode objects.o If set to “no” the objects will not be shown.
o If set to “yes” the Status_ Mode objects for Auto, Heat, Cool, Fan and Dry will appear. When enabled, a mode will return a “1” through its bit-type object.
4.2.6 Enable use of Text object for Mode
This parameter shows/hides the Status_ Mode Text communication object. o If set to “no” the object will not be shown.
o If set to “yes” the Status_ Mode Text object will appear. Also, in the parameters, will be shown five text fields, one for each mode, that will let modify the text string displayed by the Status_ Mode Text when changing mode. 4.3 Global Fan Speed Configuration dialog
All the parameters in this section are related with the Fan Speed properties and communication objects.
4.3.1 DPT object type for fan speed
With this parameter is possible to change de DPT for the Control_ Fan Speed and Status_ Fan Speed byte-type communication objects. Datapoints Scaling (DPT_5.001) and Enumerated (DPT_5.010) can be selected.
o When “Enumerated [DPT 5.010]” is selected, Control_ Fan Speed and Status_ Fan Speed communication objects for this DPT will appear. Also, depending on the number of fan speeds selected, these objects will be different. The first fan speed will be selected if a “1” is sent to the Control_ object. The second one will be selected sending a “2”, and the last one sending a “3”.
The Status_ object will always return the value for the fan speed selected.
Important: If a “0” value is sent to the Control_ object, the minimum fan speed will be selected. If a value bigger than “3” is sent to the Control_ object, then the maximum fan speed will be selected.
o When “Scaling [DPT 5.001]” is selected, Control_ Fan Speed and Status_ Fan Speed communication objects for this DPT will appear. Also, depending on the number of fan speeds selected, these objects will be different. When a value between 0% and 49% is sent to the Control_ object the first fan speed will be selected.
When a value between 50% and 83% is sent to the Control_ object, the second speed will be selected.
When a value between 84% and 100% is sent to the Control_ object, the third speed will be selected.
The Status_ object will return a 33% when the first speed is selected, a 67% for the second one and a 100% for the third one. 4.3.2 Enable use of “Fan Speed Man/Auto” objects (for Control and Status)
This parameter shows/hides the Control_ Fan Speed Man/Auto and Status_ Fan Speed Man/Auto communication object which lets you set the Fan Speed into Manual or Auto mode. 4.3.3 Enable use of +/- object for Fan Speed
This parameter shows/hides the Control_ Fan Speed +/- communication object which lets you increase/decrease the indoor unit fan speed by using two different datapoint types. If set to “no” the object will not be shown.
- If set to “yes” the Control_ Fan Speed +/- object and a new parameter will appear.
- Fan speed +/- operation
This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 0-Decrease / 1-Increase [DPT_1.007] for the Control_ Fan Speed +/- object. - Sequence for +/- object
This parameter lets choose between the different modes available: - S1>S2>….>SN
Select this option if you don’t have Auto mode and you don’t want roll-over to be enabled. - S1>S2>….>SN>S1>…
Select this option if you don’t have Auto mode and you want roll-over to be enabled. - Auto>S1>S2>….>SN
Select this option if you have Auto mode and you don’t want roll-over to be enabled. - Auto>S1>S2>….>SN>Auto>S1>…
Select this option if you have Auto mode and you want roll-over to be enabled.
4.3.4 Enable use of bit-type Fan Speed objects (for Control)
This parameter shows/hides the bit-type Control_ Fan Speed objects.o If set to “no” the objects will not be shown.
o If set to “yes” the Control_ Fan Speed objects for Speed 1, Speed 2 and Speed 3 (if available) will appear. To activate a Fan Speed by using these objects a “1” value has to be sent.
4.3.5 Enable use of bit-type Fan Speed objects (for Status)
This parameter shows/hides the bit-type Status_ Fan Speed objects. o If set to “no” the objects will not be shown.
o If set to “yes” the Status_ Fan Speed objects for Speed 1, Speed 2 and Speed 3 (if available) will appear. When a Fan Speed is enabled, a “1” value is returned through its bit- type object.
4.3.6 Enable use of Text object for Fan Speed
This parameter shows/hides the Status_ Fan Speed Text communication object. o If set to “no” the object will not be shown.
o If set to “yes” the Status_ Fan Speed Text object will appear. Also, in the parameters, will be shown two (or three, depending on the number of fan speeds selected) text fields, one for each Fan Speed, that will let modify the text string displayed by the Status_ Fan Speed Text when changing a fan speed.4.4 Global temperature configuration
All the parameters in this section are related with the Temperature properties and communication objects.
4.4.1 Enable use of +/- obj for Setpoint
This parameter shows/hides the Control_ Setpoint Temp +/- communication object which lets you change the indoor unit setpoint temperature by using two different datapoint types.o If set to “no” the object will not be shown.
o If set to “yes” the Control_ Setpoint Temp +/- object and a new parameter will appear.. DPT type for +/- Setp Temp object
This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 1- Decrease / 1-Increase [DPT_1.007] for the Control_ Setpoint Temp +/- object. 4.4.2 Ambient Ref. Temp. is provided from KNX
This parameter shows/hides the Control_ Ambient Temperature communication object which lets you use an ambient temperature reference provided by a KNX device. o If set to “no” the object will not be shown.
o If set to “yes” the Control_ Ambient Temperature object will appear. Meant to be enabled when you want the temperature provided by a KNX sensor to be the reference ambient temperature for the air conditioner. Then, the following formula applies for the calculation of real Control_ Setpoint Temperature sent ot the AC unit:
“AC Setp. Temp” = “Ambient ref. Temp” – (“KNX Amb. Temp.” – “KNX Setp Temp.”)
- AC Setp. Temp: AC indoor unit setpoint temperature
- Ambient Ref. Temp: AC indoor unit return temperature
- KNX Amb. Temp.: Ambient temperature provided from KNX
- KNX Setp. Temp: Setpoint temperature provided from KNX
As an example, consider the following situation:
User wants: 19ºC (“KNX Setp. Temp.”)
User sensor (a KNX sensor) reads: 21ºC (“KNX Amb Temp.”) Ambient temp. read by system is: 24ºC (“Ambient Ref. Temp”)
In this example, the final setpoint temperature that 40VCBK17/27/37FQEEwill send out to the indoor unit (shown in “Setp. Temp.”) will become 24ºC – (21ºC – 19ºC)
= 22ºC. This is the setpoint that will actually be requested to unit.
This formula will be applied as soon as the Control_ Setpoint Temperature and Control_ Ambient Temperature objects are written at least once from the KNX installation. After that, they are kept always consistent.
Note that this formula will always drive the AC indoor unit demand in the right direction, regardless of the operation mode (Heat, Cool or Auto).
4.5 Control Mode configuration All the parameters in this section are related with the Mode properties and communication objects.
4.5.1 Enable use of Control Mode objects (for Control and Status)
This parameter shows/hides the Control_ Control Mode and Status_ Control Mode communication objects which lets you change the indoor unit control: No Central, LIFO (Last Input First Output), Central Controller and Lock Central Controller.
- If set to “no” the objects will not be shown.
- If set to “yes” the Control_ and Status_ Control Mode objects for No Central, LIFO (Last Input First Output), Central Controller, Lock Central Controller will appear.
4.5.1 Initial state of Control Mode
This parameter sets the initial value for the Control Mode: No Central, LIFO (Last Input First Output), Central Controller, Lock Central Controller or Do not initialize.
- If set to “Apply same initial state to all Indoor Units”, the parameter option selected will apply to all indoor units.
- If set to “Initial state for each Indoor Unit might differ”, you will be able to set this parameter for each Indoor Unit individually.
4.6 Addressing of Indoor Units In this section you will be able to set the AC addressing for each AC unit present in the installation.
- Modbus GW address of ACxx refers to the addres of the Communication Addapters.
- IDU index (in Modbus GW) of ACxx refers to the AC system address of the Indoor Unit.
4.7 LicenseUse this section to introduce the migration code in case you need to update your box from another version different from the factory default one.
Error Codes
Error Code in KNX Object | Error in Remote Controller | Category | Error Name |
1 | 1 | Indoor Unit | Indoor ambient temp.sensor TA (Tas) failure |
2 | 2 | Indoor gas pipe temp. sensor TC1 failure | |
3 | 3 | Indoor liquid pipe temp. sensor TC2 failure | |
4 | 4 | Dual heat source sensor TW failure | |
5 | 5 | Indoor EEPROM failure | |
6 | 6 | Communication between indoor and outdoor failure | |
7 | 7 | Communication between indoor and wired controller failure | |
8 | 8 | Indoor float switch failure | |
9 | 9 | Indoor address repeated failure | |
10 | 10 | Reserved | |
11 | 11 | Reserved | |
12 | 12 | No 50 Hz zero passage signal | |
13 | 13 | Coil sensor TC3 failure | |
14 | 14 | DC motor failure | |
15 | 15 | Indoor ambient temp.sensor TA (Taf) failure | |
16 | 16 | – | |
17 | 17 | Outoor Unit | – |
18 | 18 | – | |
19 | 19 | – | |
20 | 20 | Defrosting temp. sensor Tdef1 failure Defrosting temp. sensor Tdef2 failure | |
21 | 21 | Ambient temp. sensor Ta failure | |
22 |
22 |
Suction temp. sensor Ts1 failure Suction temp. sensor Ts2 failure Suction temp. sensor Tsacc failure Suction temp. sensor Tsuc failure |
23 | 23 | Outdoor Unit | Discharging temp. sensor Tdi failure Discharging temp. sensor Td1 failure Discharging temp. sensor Td2 failure |
24 | 24 | Oil temp. sensor Toilp failure Oil temp. sensor Toil failure | |
25 | 25 | Inlet temp. of heat exchanger Toci1 failure Inlet temp. of heat exchanger Toci2 failure indoor communication failure Reduce the number of indoor units failure Increase the number of indoor units failure |
|
26 | 26 | ||
27 | 27 | Oil temp. too high protection (Toil) Oil temp. too high protection (Toi2) | |
28 | 28 | High pressure sensor Pd1 failure High pressure sensor Pd2 failure | |
29 | 29 | Low pressure sensor Ps failure | |
30 | 30 | High pressure switch HPSi failure High pressure switch HPS1 failure High pressure switch HPS2 failure | |
31 | 31 | Liquid pipe pressure Pl failure | |
32 | 32 | Outlet temp. of subcooler Tsco failure
Liquid pipe SC temp. of subcooler Tliqsc failure |
|
33 | 33 | EEPROM (AT24C04) failure | |
34 | 34 | Discharging temp. too high protection (Tdi) Discharging temp. too high protection (Td1) Discharging temp. too high protection (Td2) | |
35 | 35 | 4-way valve reversing failure 4-way valve reversing failure | |
36 | 36 | Oil temp. too low protection (Toil) Oil temp. too low protection (Toi2) Lack of phase of 3N power supply or wrong phase sequence |
|
37 | 37 | ||
38 | 38 | High pressure sensor Pd too low protection | |
39 | 39 | Low pressure sensor Ps too low protection Compression ratio too high protection Compression 1 ratio too low protection Compression 2 ratio too low protection | |
40 | 40 | High pressure sensor Pd1 too high protection High pressure sensor Pd2 too high protection | |
41 | 41 | Water temp. Twi too low protection Water temp. Twi too high protection | |
42 | 42 | Frost protection of water system Water system out of water freeze protection Water flow of Water system is too small to protect |
|
43 | 43 | Discharging temp. sensor Tdi too low protection Discharging temp. sensor Td1 too low protection Discharging temp. sensor Td2 too low protection | |
44 | 44 | Low pressure sensor PS too high protection | |
45 | 45 | Communication among outdoors failure | |
46 | 46 | Communication with inverter board 1 failure Communication with inverter board 2failure | |
47 | 47 | – | |
48 | 48 | Unloading valve SV1 failure | |
49 | 49 | – |
50 | 50 | Outdoor Unit | |
51 | 51 | – | |
52 | 52 | – | |
53 | 53 | Current detector CT1 failure | |
54 | 54 | Communication with Thermal storage module failure | |
55 | 55 | Thermal storage module LEV failure | |
56 | 56 | Thermal storage module too hot failure | |
57 | 57 | Communication between Thermal storage module and host computer | |
58 | 58 | Thermal storage module Tc1 temp. sensor failure | |
59 | 59 | Thermal storage module Tc2 temp. sensor failure | |
60 | 60 | Reserved | |
61 | 61 | Reserved | |
62 | 62 | Reserved | |
63 | 63 | Thermal storage module DIP setting failure | |
64 | 64 | CT1 over current CT2 over current | |
65 | 65 | – | |
66 | 66 | – | |
67 | 67 | Communication with motor driving board failure | |
68 | 68 | – | |
69 | 69 | – | |
70 | 70 | – | |
71 | 71 | Left DC motor blocked Right DC motor blocked | |
72 | 72 | Left DC motor reversed Right DC motor reversed | |
73 | 73 | Left DC motor current too high Right DC motor current too high | |
74 | 74 | – | |
75 | 75 | No pressure drop between high pressure and low one Pressure too low between high pressure and low one | |
76 | 76 | Incorrect outdoor address or capacity setting | |
77 | 77 | Oil equalization protection among outdoors | |
78 | 78 | Lack of refrigerant in cooling Lack of refrigerant in heating | |
79 | 79 | Incorrect wiring | |
80 | 80 | Indoor and outdoor do not match | |
81 | 81 | Model temp. too high protection | |
82 | 82 | Compressor current protection | |
83 | 83 | Wrong model selection | |
84 | 84 | – | |
85 | 85 | – | |
86 | 86 | – | |
87 | 87 | – | |
88 | 88 | – | |
89 | 89 | – | |
90 | 90 | – | |
91 | 91 | – | |
92 | 92 | – | |
93 | 93 | – | |
94 | 94 | – | |
95 | 95 | – | |
96 | 96 | – |
97 | 97 | Outdoor Unit | – |
98 | 98 | – | |
99 | 99 | Program self-test failure | |
100 | 100 | DC motor driving board IPM alarm | |
101 | 101 | DC motor driving board detecting out of control | |
102 | 102 | DC motor driving board EEPROM faulty | |
103 | 103 | DC motor driving board over current or current detector damaged | |
104 | 104 | Voltage too low protection of DC motor driving board | |
105 | 105 | Voltage too high protection of DC motor driving board | |
106 | 106 | DC motor driving board blocked | |
107 | 107 | Protection of motor rate over Limitation | |
108 | 108 | – | |
109 | 109 | – | |
110 | 110 | model 1 Over current model 2 Over current | |
111 | 111 | Compressor 1 out of control Compressor 2 out of control | |
112 | 112 | Radiator of model 1 temp. too high Radiator of model 2 temp. too high | |
113 | 113 | model 1 overload | |
model 2 overload | |||
114 | 114 | Voltage too low of model 1 Voltage too low of model 2 | |
115 | 115 | Voltage too high of model 1 Voltage too high of model 2 | |
116 | 116 | Communication abnormal with model 1 Communication abnormal with model 2 | |
117 | 117 | Model 1 Over current (software) Model 1 Over current (software) | |
118 | 118 | Model 1 startup failure Model 2 startup failure | |
119 | 119 | Current Detecting Circuit Abnormal of transducer 1 Current Detecting Circuit Abnormal of transducer 2 | |
120 | 120 | Power supply of transducer 1 abnormal Power supply of transducer 2 abnormal | |
121 | 121 | Power supply of inverter board 1 is abnormal Power supply of inverter board 2 is abnormal | |
122 | 122 | Radiator temp. sensor of transducer 1 abnormal Radiator temp. sensor of transducer 2 abnormal | |
123 | 123 | – | |
124 | 124 | – | |
125 | 125 | Compressor 1 frequency not match Compressor 2 frequency not match | |
126 | 126 | – | |
127 | 127 | MCU reset abnormal | |
128 | 128 | MCU Program needs to be upgraded | |
0 | N/A | KNX interface | No error |
65535 (-1) | N/A | KNX interface | Indoor Units not ready for communication |
65436 (-100) | N/A | KNX interface | License Error / indoor unit not supported by current license |
65336 (-200) | N/A | KNX interface | Overconsumption error in EXY bus |
In case you detect an error code not listed, contact your nearest technical support service for more information on the error meaning.
Appendix A – Communication Objects Table
SECTION | OBJECT NUMBER | NAME | LENGTH | DATAPOINT TYPE | FLAGS | |||||
DPT_NAME | DPT_ID | R | W | T | U | FUNCTION | ||||
On/Off | 1 | Control_ On/Off | 1 bit | DPT_Switch | 1.001 | W | T | 0 – Off; 1-On | ||
Mode | 2 | Control_ Operating Mode | 1 byte | DPT_HVACMode | 20.102 | W | T | 0 – Auto; 1 – Com; 2 – Stan; 3 – Eco; 4 – Pro |
||
3 | Control_ Mode | 1 byte | DPT_ HVACControl | 20.105 | W | T | 0 – Auto; 1 – Heat; 3 – Cool; 9 – Fan; 14 – Dry |
|||
4 | Control_ Mode Cool/Heat | 1 bit | DPT_Cool/Heat | 1.1 | W | T | 0 – Cool; 1 – Heat | |||
5 | Control_ Mode Auto | 1 byte | DPT_Scaling | 5.001 | W | T | 1 – Auto | |||
6 | Control_ Mode Heat | 1 byte | DPT_Scaling | 5.001 | W | T | 1 – Heat | |||
7 | Control_ Mode Cool | 1 bit | DPT_Bool | 1.002 | W | T | 1 – Cool | |||
8 | Control_ Mode Fan | 1 bit | DPT_Bool | 1.002 | W | T | 1 – Dry | |||
9 | Control_ Mode Dry | 1 bit | DPT_Bool | 1.002 | W | T | 1 – Fan | |||
10 | Control_ Mode +/- | 1 bit | DPT_Step | 1.007 | W | 0 – Decrease; 1 – Increase | ||||
Control_ Mode +/- | 1 bit | DPT_UpDown | 1.008 | W | 0 – Up; 1 – Down | |||||
Fan Speed | 11 | Control_ Fan Speed / 3 Speeds | 1 byte | DPT_Scaling | 5.001 | W | T | 0%-49% – Speed 1; 50%-83% – Speed 2;84%-100% Speed 3 |
||
Control_ Fan Speed / 3 Speeds | 1 byte | DPT_Enumerated | 5.01 | W | T | 1 – Speed 1; 2 – Speed 2; 3 Speed 3 |
||||
12 | Control_ Fan Speed Man/Auto | 1 bit | DPT_Bool | 1.002 | W | T | 0 – Manual; 1 – Auto | |||
13 | Control_ Fan Speed 1 | 1 bit | DPT_Bool | 1.002 | W | T | 1 – Fan Speed 1 | |||
14 | Control_ Fan Speed 2 | 1 bit | DPT_Bool | 1.002 | W | T | 1 – Fan Speed 2 | |||
15 | Control_ Fan Speed 3 | 1 bit | DPT_Bool | 1.002 | W | T | 1 – Fan Speed 3 |
Fan Speed | 16 | Control_ Fan Speed +/- | 1 bit | DPT_Step | 1.007 | W | T | 0 – Decrease; 1 – Increase | ||
Control_ Fan Speed +/- | 1 bit | DPT_UpDown | 1.008 | W | T | 0 – Up; 1 – Down | ||||
Temperature | 17 | Control_ Setpoint Temperature | 2 byte | DPT_Value_Temp | 9.001 | W | T | 17ºC to 30ºC | ||
18 | Control_ Setpoint Temp +/- Control_ Setpoint Temp +/- |
1 bit 1 bit |
DPT_Step DPT_UpDown |
1.007 1.008 |
W W |
0 – Decrease; 1 – Increase 0 – Up; 1 – Down |
||||
19 | Control_ Ambient Temperature | 2 byte | DPT_Value_Temp | 9.001 | W | T | ºC value in EIS5 format | |||
Control Mode | 20 | Control_ Control Mode No Central | 1 bit | DPT_Bool | 1.002 | W | T | 1 – No Central Controller | ||
21 | Control_ Control Mode LIFO | 1 bit | DPT_Bool | 1.002 | W | T | 1 – Last Input First Output (LIFO) | |||
22 | Control_ Control Mode Central | 1 bit | DPT_Bool | 1.002 | W | T | 1 – Central Controller | |||
23 | Control_ Control Mode Lock | 1 bit | DPT_Bool | 1.002 | W | T | 1 – Lock Central Controller | |||
On/Off | 24 | Status_ On/Off | 1 bit | DPT_Switch | 1.001 | R | T | 0 – Off; 1-On | ||
Mode | 25 | Status_ Operating Mode | 1 byte | DPT_HVACMode | 20.102 | R | T | 0 – Auto; 1 – Com; 2 – Stan; 3 – Eco; 4 – Pro |
||
26 | Status_ Mode | 1 byte | DPT_ nHVACContrMode | 20.105 | R | T | 0 – Auto; 1 – Heat; 3 – Cool; 9 – Fan; 14 – Dry |
|||
27 | Status_ Mode Cool/Heat | 1 bit | DPT_Heat/Cool | 1.1 | R | T | 0 – Cool; 1 – Heat | |||
28 | Status_ Mode Auto | 1 bit | DPT_Bool | 1.002 | R | T | 1 – Auto | |||
29 | Status_ Mode Heat | 1 bit | DPT_Bool | 1.002 | R | T | 1 – Hea | |||
30 | Status_ Mode Cool | 1 bit | DPT_Bool | 1.002 | R | T | 1 – Cool | |||
31 | Status_ Mode Fan | 1 bit | DPT_Bool | 1.002 | R | T | 1 – Fan | |||
32 | Status_ Mode Dry | 1 bit | DPT_Bool | 1.002 | R | T | 1 – Dry | |||
33 | Status_ Mode Text | 14 byte | DPT_ String_8859_1 | 16.001 | R | T | ASCII String |
Fan Speed | 34 | Status_ Fan Speed / 3 Speeds | 1 byte | DPT_Scaling | 5.001 | R | T | 33% – Speed 1; 67% – Speed 2; 100% – Speed 3 |
||
Status_ Fan Speed / 3 Speeds | 1 byte | DPT_Enumerated | 5.01 | R | T | 1 – Speed 1; 2 -Speed 2; 3- Speed 3 |
||||
35 | Status_ Fan Speed Man/Auto | 1 bit | DPT_Bool | 1.002 | R | T | 0 – Manual; 1 – Auto |
|||
36 | Status_ Fan Speed 1 | 1 bit | DPT_Bool | 1.002 | R | T | 1 – Speed 1 | |||
37 | Status_ Fan Speed 2 | 1 bit | DPT_Bool | 1.002 | R | T | 1 – Speed 2 | |||
38 | Status_ Fan Speed 3 | 1 bit | DPT_Bool | 1.002 | R | T | 1 – Speed 3 | |||
39 | Status_ Fan Speed Text | 14 byte | DPT_ String_8859_1 | 16.001 | R | T | ASCII String | |||
Temperature | 40 | Status_ AC Setpoint Temp | 2 byte | DPT_Value_Temp | 9.001 | R | T | 16ºC to 32ºC | ||
41 | Status_ AC Ambient Ref Temp | 2 byte | DPT_Value_Temp | 9.001 | R | T | ºC value in EIS5 format | |||
Error | 42 | Status_ Error/ Alarm | 1 bit | DTP_Alarm | 1.005 | R | T | 0 – No Alarm; 1 – Alarm | ||
43 | Status_ Error Code | 2 byte | Enumerated | R | T | 0 – No Error; Any other see user’s manual | ||||
44 | Status_ Error Text code | 14 byte | DPT_ String_8859_1 | 16.001 | R | T | 2 char Error; Empty – none | |||
Control Mode | 45 | Control_ Control Mode No Central | 1 bit | DPT_Bool | 1.002 | W | T | 1 – No Central Controller | ||
46 | Control_ Control Mode LIFO | 1 bit | DPT_Bool | 1.002 | W | T | 1 – Last Input First Output (LIFO) | |||
47 | Control_ Control Mode Central | 1 bit | DPT_Bool | 1.002 | W | T | 1 – Central Controller | |||
48 | Control_ Control Mode Lock | 1 bit | DPT_Bool | 1.002 | W | T | 1 – Lock Central Controller |
NOTE: This addressing corresponds to the first AC indoor unit of the configuration. Communication objects for the rest of AC units are consecutively listed .
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Documents / Resources
![]() |
Carrier XCT-7 Variable Refrigerant Flow Controls [pdf] Owner's Manual XCT-7 Variable Refrigerant Flow Controls, XCT-7, Variable Refrigerant Flow Controls, Refrigerant Flow Controls, Flow Controls |