BITMAIN ANTRACK V1 Cooling Mining Rack
Specifications
- Model: ANTRACK V1
- Capacity: 4 units ANTMINER (S21 Hyd.)
- Maximum Load: 24 kW
Product Glance
- Hardware configuration:
- Size (Width*Height*Depth): 600*2000*1000 mm
- Net weight (w/o miner): 300 kg
- Network connection mode: RJ45 Ethernet 10/100M
- Power supply:
- AC input voltage, Volt: 380~415V AC
- AC input frequency range, Hz: 50~60
- Maximum power supply AC input current, Amp: 80
- Fan:
- Rated power, W: 106
- Noise, dBA@1m: 68
- Size (Length*Height*Thickness), mm: 280*280*80
- Pump:
- Rated power, W: 750
- Noise, dBA@1m: 55
- Size (Length*Width* Height), mm: 360*210*268
- Plate heat exchanger:
- Maximum heat exchange power, kW: 30
- Size (Length*Width* Height), mm: 305*106*64
- Diameter of water pipe connector, mm: DN25
- Environment requirements:
- Temperature Range: 15~45°C
- Water flow, L/min: 32.0~40.0
- Water pressure, bar: 3.5
- Working fluid: Deionized water/Pure water
- Liquid PH: 8.5~9.5
- Operation humidity(non-condensing), RH: 10~90%
Product Usage Instructions
Power Supply Connection
Connect the power supply to the designated AC input voltage and frequency range mentioned above.
Network Connection Setup
Use an RJ45 Ethernet cable to connect the product for network access.
Frequently Asked Questions (FAQ)
What should I do if the water conductivity is above 100 s/cm?
If the water conductivity exceeds 100 s/cm, the fluid must be replaced to prevent damage to the system.
Specification
Product Glance | Value |
Model | ANTRACK |
Version | V1 |
Capacity | 4 units ANTMINER (S21 Hyd.) |
Maximum load, kW | 24 |
Detailed Characteristics | Value |
Hardware configuration | |
Size (Width*Height*Depth), mm | 600*2000*1000 |
Net weight (w/o miner), kg | 300 |
Network connection mode | RJ45 Ethernet 10/100M |
Power supply | |
Power supply AC input voltage, Volt(1-1) | 380~415V AC |
Power supply AC input frequency range, Hz | 50~60 |
Maximum power supply AC input current, Amp(1-2) | 80 |
Fan | |
Rated power, W | 106 |
Noise, dBA@1m | 68 |
Size (Length*Height*Thickness), mm | 280*280*80 |
Pump | |
Rated power, W | 750 |
Noise, dBA@1m | 55 |
Size (Length*Width* Height), mm | 360*210*268 |
Plate heat exchanger | |
Maximum heat exchange power, kW | 30 |
Size (Length*Width* Height), mm | 305*106*64 |
Diameter of water pipe connector, mm | DN25 |
Environment requirements | |
Ambient temperature, °C | 15~45 |
Water flow, L/min | 32.0~40.0 |
Water pressure, bar | ≤3.5 |
Working fluid(1-3) | Deionized water/Pure water |
Liquid PH | 8.5~9.5 |
Storage temperature, °C | -20~70 |
Operation humidity(non-condensing), RH | 10~90% |
Notes:
- Caution: Wrong input voltage may cause server damaged.
- Three-phase AC input.
- If the water conductivity is ≥100 μs/cm, the fluid must be replaced. The water conductivity is less than 20 μs/cm when the system is running at the first time.
Documents / Resources
![]() |
BITMAIN ANTRACK V1 Cooling Mining Rack [pdf] Instructions ANTRACK V1 Cooling Mining Rack, ANTRACK V1, Cooling Mining Rack, Mining Rack, Rack |