Autonics logoDisplay Type Pressure Sensors
PSAN Series
INSTRUCTION MANUAL
TCD210185AB

PSAN Series Display Type Pressure Sensors

Thank you for choosing our Autonics product.
Read and understand the instruction manual and manual thoroughly before using the product.
For your safety, read and follow the below safety considerations before using.
For your safety, read and follow the considerations written in the instruction manual, other manuals and Autonics website.
Keep this instruction manual in a place where you can find easily.
The specifications, dimensions, etc are subject to change without notice for product improvement Some models may be discontinued without notice.
Follow Autonics website for the latest information.

Safety Considerations

  • Observe all ‘Safety Considerations’ for safe and proper operation to avoid hazards.
  • Warning icon symbol indicates caution due to special circumstances in which hazards may occur.
    Warning iconWarning Failure to follow instructions may result in serious injury or death
  1.  Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.)
    Failure to follow this instruction may result in personal injury, economic loss or fire.
  2. Do not use the unit in the place where flammable/explosive/corrosive gas, humidity, direct sunlight, radiant heat, vibration, impact, or salinity may be present.
    Failure to follow this instruction may result in explosion or fire.
  3. Install on a device panel or to a pressure port directly to use.
    Failure to follow this instruction may result in fire.
  4. Do not connect, repair, or inspect the unit while connected to a power source.
    Failure to follow this instruction may result in fire.
  5. Check ‘Connections’ before wiring.
    Failure to follow this instruction may result in fire.
  6. Do not disassemble or modify the unit.
    Failure to follow this instruction may result in fire or electric shock.

Warning icon Caution Failure to follow instructions may result in injury or product damage

  1. Use the unit within the rated specifications.
    Failure to follow this instruction may result in fire or product damage.
  2. Use a dry cloth to clean the unit, and do not use water or organic solvent.
    Failure to follow this instruction may result in fire.
  3. This product is designed to detect the pressure of noncorrosive medium. Do not use for corrosive medium.
    Failure to follow this instruction may result in product damage.
  4. Keep the product away from metal chip, dust, and wire residue which flow into the unit.
    Failure to follow this instruction may result in fire or product damage.

Cautions during Use

  • Follow instructions in ‘Cautions during Use’. Otherwise, it may cause unexpected accidents.
  • 12 – 24 VDC power supply should be insulated and limited voltage/current or Class 2, SELV power supply device.
  • Use the product, 3 sec after supplying power.
  • When using switching mode power supply, frame ground (F.G.) terminal of power supply should be grounded.
  • Wire as short as possible and keep away from high voltage lines or power lines, to prevent inductive noise.
  • This unit may be used in the following environments.
    – Indoors (in the environment condition rated in ‘Specifications’)
    – Altitude max 2,000 m
    – Pollution degree 3
    – Installation category II

Ordering Information

This is only for reference, the actual product does not support all combinations. For selecting the specified model, follow the Autonics website.

Autonics PSAN Series Display Type Pressure Sensors - icon

  1. Medium / Port fitting position
    No mark: Pneumatic type (gas) / Back
    D: Pneumatic type (gas) / Bottom
    B: Fluid type (liquid, gas) / Back
    L: Fluid type (liquid, gas) / Bottom
  2. Pressure type and Range
    Pressure Rated range
    01 Static 0.0 to 100.0 kPa
    1 0 to 1,000 kPa
    V01 Negative 0.0 to -101.3 kPa
    C01 Compound -101.3 to 100.0 kPa
  3. Wiring
    No mark: Cable type (fluid type)
    C: Connector type
  4. Control output
    No mark: NPN open collector output
    P: PNP open collector output
  5. Option input / output
    V: Voltage output
    A: Current output
    H: External input
  6. Pressure port
    Medium Port Pneumatic Fluid
    R1/8
    Rc1/8
    NPT1/8
    7/16-20UNF
    9/16-18UNF

Product Components

  • Product
  • Instruction manual
  • Unit sticker
  • Connector type: Bracket A / B, Connector wiring (PSO-C01)
  • Cable type: Bracket C

Sold Separately

  • Front cover (PSO-P01), Panel bracket (PSO-B02/B03)
  • Pneumatic type: M5 gender (PSO-Z01)

Unit Descriptions

Autonics PSAN Series Display Type Pressure Sensors - Unit Descriptions

  1. Pressure range (sticker)
  2. Display part (red)
    Run mode: Displays PV (present value), SV (setting value)
    Setting mode: Displays parameter and setting value
  3. Output indicator (OUT1: red , OUT2: green)
    Turns ON when the corresponding control output is ON.
  4.  [M] key
    Enters parameter group, selects item and returns run mode.
  5. [▼] , [▲] key
    Sets preset of output operation mode, runs the mode or changes parameter.

Connections

Color Function
Brown +V
Blue 0 V
Black OUT 1
White OUT 2
Orange Option input / output

NPN open collector output

Autonics PSAN Series Display Type Pressure Sensors - Connections

PNP open collector output

Autonics PSAN Series Display Type Pressure Sensors - Connections1

  • ①: Option voltage / current output model, ②: Option external input model
  • OCP (over current protection circuit)
  • There is no short circuit protection circuit. Do not connect directly to power or capacitive loads.
  • The control output is abnormal when the control output circuit is shorted or over current is supplied.
  • Pay attention to the input impedance of the connected device when using analog voltage output. Be sure to the voltage drop due to the resistance of the wiring when extending the wiring.

Dimensions

  • Unit: mm, For the detailed drawings, follow the Autonics website.

Pneumatic type, back port, connector type

Autonics PSAN Series Display Type Pressure Sensors - Dimensions

Pneumatic type, bottom port, connector type

Autonics PSAN Series Display Type Pressure Sensors - Dimensions1

Fluid type, bottom port, connector type

Autonics PSAN Series Display Type Pressure Sensors - Dimensions2

Fluid type, back port, cable type

Autonics PSAN Series Display Type Pressure Sensors - Dimensions3

Autonics PSAN Series Display Type Pressure Sensors - Dimensions4

Installation

One-touch fitting

Pneumatic type Fluid type
Autonics PSAN Series Display Type Pressure Sensors - Dimensions5 Autonics PSAN Series Display Type Pressure Sensors - Dimensions6

Connect the metal part with a spanner so that no large force is applied to the unit body. (tightening torque: ≤ 10 N m, it may cause malfunction.)
Bracket
Use spring washers and hexagon wrench bolts (tightening torque: ≤ 3 N m) to select and install a bracket suitable for your environment.

Connector type Cable type
• Bracket AAutonics PSAN Series Display Type Pressure Sensors - Dimensions7 • Bracket BAutonics PSAN Series Display Type Pressure Sensors - Dimensions8 • Bracket CAutonics PSAN Series Display Type Pressure Sensors - Dimensions9

Wiring

  • Do not pull the wiring with a force of more than 30 N.

Specifications

Model PSAN- □V01C□□- PSAN- □01C□□- PSAN-□1□□□- PSAN- □C01□□□-
Pressure Type Pneumatic type model: Gauge pressure  Fluid type model: Gauge pressure 01) or sealed gauge pressure 02)
Pressure Negative Static Compound
Min display unit 0.1 kPa 0.1 kPa 1 kPa 0.1 kPa
Rated pressure range 0.0 to -101.3 kPa 0.0 to 100.0 kPa 0 to 1,000 kPa -101.3 to 100.0 kPa
Display & setting pressure range 5.0 to -101.3 kPa -5.0 to 110.0 kPa -101.3 to 1,100 kPa -101.3 to 110.0 kPa
Display type 7 Segment LED, 4 ½ digit
Display accuracy -10 to 0 ℃: ≤ ±1% F.S., 0 to 50 ℃: ≤ ±0.5% F.S.
Max. pressure Rated pressure ×2 Rated pressure ×2 •  Pneumatic type: Rated pressure ×1.5
•  Fluid type: Rated pressure ×2
Rated pressure ×2
  1.  Only for static pressure, rated pressure range 100.0 kPa model
  2. The unit is sealed structure. It is based on atmospheric pressure 101.3 kPa.
Applicable medium Pneumatic type (air, non-corrosive gas) Fluid type (non-corrosive gas and fluid that do not corrode stainless steel 316L)
Connection type Connector type Cable type / connector type
Cable Ø 4 mm, 5-core, 2 m Connector type: Ø 4 mm, 5-core, 2 m Cable type: Ø 4 mm, 5-core, 3 m
Wire spec. AWG24 (0.08 mm, 40-core), insulator diameter: Ø 1 mm
Material Front case: PC Back case: (back port) PC / (bottom port) PBT+GF15%
Pressure port: Brass-nickel plated
Front case: PC Back case: PA6
Pressure port: SUS304/SUS316L
Protection structure Connector type: IP40 (IEC standard) Connector type: IP40 (IEC standard) Cable type: IP65 (IEC standard)
Approval
Unit weight (packaged) Back port: ≈ 80 g (≈ 165 g) Bottom port: ≈ 85 g (≈ 170 g) Connector type: ≈ 88 g (≈ 173 g) Cable type: ≈ 90 g (≈ 167 g)
Power supply 12 – 24 VDC (ripple P-P: ≤ 10%)
Allowable voltage range 90 to 110% of rated voltage
Current consumption ≤ 50 mA 01)
Control output NPN open collector output / PNP open collector output model
Load voltage ≤ 30 VDC
Load current ≤ 100 mA
Residual voltage NPN: ≤ 1 VDC, PNP: ≤ 2 VDC
Hysteresis According to output operation mode 02)
Repeat error ±0.2% F.S. ±min display interval
Response time 2.5, 5, 100, 500, 1000 ms
Protection circuit Output short over-current protection circuit
Insulation resistance ≥ 50 MΩ (500 VDCmegger)
Dielectric strength 1,000 VAC 50 / 60 Hz for 1 min
Vibration 1.5 mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 2 hours
Ambient temperature -10 to 50 ℃, Storage: -20 to 60 ℃ (no freezing or condensation)
Ambient humidity 30 to 80%RH, Storage: 30 to 80%RH (no freezing or condensation)
  1. Current output: ≤ 75 mA
  2.  Refer to ‘Output operation mode’. ±1digit error may occur due to pressure unit operation.
Analog output Voltage (1 5 VDCᜡ ±2% F.S) Current (DC 4 20mA ±2% F.S)
Output impedance 1 kΩ
Linearity ≤ ±1% F.S ≤ ±1% F.S
Zero-point ≤ 1 VDC ±2% F.S. ≤ DC 4 mA ±2% F.S.
Span ≤ 4 VDC±2% F.S. ≤ DC 16 mA ±2% F.S.
Resolution 1/1000 or 1/2000 (different by pressure type and display unit)
Response time 50 ms 70 ms

Minimum Display Interval

Pressure Negative Static Compound
Min display interval 0.1 kPa 0.1 kPa 1 kPa 0.1 kPa
Resolution

Display unit

1/1000 1/2000 1/1000 1/2000 1/1000 1/2000 1/1000 1/2000
MPa 0.001 0.001
kPa 0.1 0.1 1 0.1
kgf/cm2 0.001 0.001 0.01 0.001
bar 0.001 0.001 0.01 0.001
psi 0.01 0.01 0.1 0.02
mmHg 0.4 0.8
inHg 0.02 0.03
01) mmH2O 0.1 0.1

Mode Setting

Autonics PSAN Series Display Type Pressure Sensors - Setting

  1. Max. / Min. pressure value is available to check by monitoring.
    [Option external input model] Auto shift judgment level checking / setting is available when P-9 External input terminal is set as SHFT. (no input displays 0)

Parameter Setting

  • Some parameter are activated / deactivated depending on other parameters. Refer to the description.
  • The setting item name and setting value are cross-displayed on the display part.
  • It returns to RUN mode when there is no additional key input for 60 sec in each parameter group.
  • Guaranteed write life: 100,000 times
  • [M] key: Saves setting value and moves to next parameter [▼], [▲] key: Selects setting value
Parameter Display Default Setting range
P-1 Display unit Autonics PSAN Series Display Type Pressure Sensors - icon1 Autonics PSAN Series Display Type Pressure Sensors - icon11 [Negative / Compound pressure model] kPa, KGC: kgf/cm2, bar, psi, mmHg, inHg, H2O: mmH O2
Autonics PSAN Series Display Type Pressure Sensors - icon12 [Static pressure model] MPa, kPa, KGC: kgf/cm2, bar, psi
P-2 OUT operation mode Autonics PSAN Series Display Type Pressure Sensors - icon2 Autonics PSAN Series Display Type Pressure Sensors - icon13 HYS.M: Hysteresis
WIN: Window comparison output
HY-W: Hysteresis-Window comparison output AUTO: Auto sensitivity setting
F.OUT: Forced output control
P-3 Output type Autonics PSAN Series Display Type Pressure Sensors - icon3 Autonics PSAN Series Display Type Pressure Sensors - icon14 OUT1 OUT2
1O2O Normally open Normally open
1O2C Normally closed Normally open
1C2O Normally closed Normally open
1C2C Normally closed Normally closed
P-4 Response time Autonics PSAN Series Display Type Pressure Sensors - icon4 Autonics PSAN Series Display Type Pressure Sensors - icon15 2.5, 5.0, 100, 500, 1,000 ms
P-5 Voltage low limit scale Autonics PSAN Series Display Type Pressure Sensors - icon5 Autonics PSAN Series Display Type Pressure Sensors - icon16 [Option voltage output model] Min. rated pressure ≤ Low limit scale ≤ 90% of rated pressure
P-6 Voltage high limit scale Autonics PSAN Series Display Type Pressure Sensors - icon6 Autonics PSAN Series Display Type Pressure Sensors - icon17 [Option voltage output model] Low limit scale setting value + 10% of rated pressure ≤ High limit scale ≤ Max. rated pressure
P-7 Current low limit scale Autonics PSAN Series Display Type Pressure Sensors - icon7 Autonics PSAN Series Display Type Pressure Sensors - icon16 [Option current output model] Min. rated pressure ≤ Low limit scale ≤ 90% of rated pressure
P-8 Current high limit scale Autonics PSAN Series Display Type Pressure Sensors - icon8 Autonics PSAN Series Display Type Pressure Sensors - icon17 [Option current output model] Low limit scale setting value +10% of rated pressure ≤ High limit scale ≤ Max. rated pressure
P-9 External input terminal Autonics PSAN Series Display Type Pressure Sensors - icon9 Autonics PSAN Series Display Type Pressure Sensors - icon19 [Option external input model] HOLD: Hold SHFT: Auto shift
P-10 Auto shift output 01) Autonics PSAN Series Display Type Pressure Sensors - icon20 [Option external input model] OUT1, OUT2, ALL
P-11 Lock Autonics PSAN Series Display Type Pressure Sensors - icon10 Autonics PSAN Series Display Type Pressure Sensors - icon21 LOC1: Parameter, preset, zero-point adjustment setting lock / Monitoring value reset lock
LOC2: Parameter lock (available to check setting value) OFF
  1. Condition: P-9. External input terminal SHFT setting

Preset Setting

 Setting method

  • Setting name and value are cross-displayed in SV display part.
    1. Set the operation mode in P-2 OUT operation mode.
    2. Enter the preset setting mode by pressing [M] key from RUN mode.
    3. Select the setting item by [M] key and change the preset by [▼] or [▲] key.
    4. Press [M] key to save setting or no key input over 60 sec not to save setting and return to RUN mode. (except forced output control mode)

Preset setting by operation mode

Operation mode Preset Setting range
Hysteresis Autonics PSAN Series Display Type Pressure Sensors - icon37 Pressure detection level 1 Autonics PSAN Series Display Type Pressure Sensors - icon22 Min. display pressure < ST1 ≤ Max. display

pressure

Hysteresis level 1 Autonics PSAN Series Display Type Pressure Sensors - icon23 Min. display pressure ≤ HYS1 < ST1
Pressure detection level 2 Autonics PSAN Series Display Type Pressure Sensors - icon24 Min. display pressure < ST2 ≤ Max. display pressure
Hysteresis level 2 Autonics PSAN Series Display Type Pressure Sensors - icon25 Min. display pressure ≤ HYS2 < ST2
Window comparison output 01) Autonics PSAN Series Display Type Pressure Sensors - icon38 Pressure detection low limit 1 Autonics PSAN Series Display Type Pressure Sensors - icon26 Min. display pressure ≤ LO-1 ≤ Max. display pressure -(3 × Min display interval)
Pressure detection high limit 1 Autonics PSAN Series Display Type Pressure Sensors - icon27 LO-1 + (3 × Min display interval) ≤ HI-1 ≤ Max. display pressure
Pressure detection low limit 2 Autonics PSAN Series Display Type Pressure Sensors - icon28 Min. display pressure ≤ LO-2 ≤ Max. display pressure – (3 × Min display interval)
Pressure detection high limit 2 Autonics PSAN Series Display Type Pressure Sensors - icon29 LO-2 + (3 × Min display interval) ≤ HI-2 ≤ Max. display pressure
Hysteresis- Window comparison output 02) Autonics PSAN Series Display Type Pressure Sensors - icon39 Pressure detection level 1 Autonics PSAN Series Display Type Pressure Sensors - icon30 Min. display pressure < ST1 ≤ Max. display pressure
Hysteresis level 1 Autonics PSAN Series Display Type Pressure Sensors - icon31 Min. display pressure ≤ HYS1 < ST1
Pressure detection low limit Autonics PSAN Series Display Type Pressure Sensors - icon32 Min. display pressure ≤ LOW ≤ Max. display pressure – (3 × Min display interval)
Pressure detection high limit Autonics PSAN Series Display Type Pressure Sensors - icon33 Low + (3 × Min display interval) ≤ HIGH ≤

Max. display pressure

Auto sensitivity setting Autonics PSAN Series Display Type Pressure Sensors - icon40 Pressure level 1 Autonics PSAN Series Display Type Pressure Sensors - icon34 Min. display pressure ≤ ST1 ≤ Max. display pressure – 1% of rated pressure
Pressure level 2 03) Autonics PSAN Series Display Type Pressure Sensors - icon35 ST1 + 1% of rated pressure ≤ ST2 ≤ Max. display pressure
Pressure detection level Autonics PSAN Series Display Type Pressure Sensors - icon36 Auto setting SET=
•  Manual setting is possible by [▼] or [▲] key.
Forced output control 04) Autonics PSAN Series Display Type Pressure Sensors - icon41 • Manual ON/OFF for OUT1/2 is possible by
[▼] or [▲] key.
  1. Hysteresis: 1 (min display interval, fixed)
  2. ST1 = HYS1, actual hysteresis is 1 (min. display interval)
  3. When error appears, check setting conditions and set proper setting values.
  4. [Option external input model] Forced output does not support external input terminal.

■ Precaution

  • The preset value (default) of the changed operation mode is set when changing P-2 OUT operation mode setting.
  • Preset value is converted as the changed unit automatically when changing P-1 Display unit setting.
  • Preset is reset when changing P-9 External input terminal setting.

■ Default setting value

Operation mode Preset Negative Static Compound
0.1 kPa 0.1 kPa 1 kPa 0.1 kPa
Hysteresis Autonics PSAN Series Display Type Pressure Sensors - icon53 Autonics PSAN Series Display Type Pressure Sensors - icon58 -50.0 50.0 500 50.0
Autonics PSAN Series Display Type Pressure Sensors - icon59 0.0 0.0 0 -50.0
Autonics PSAN Series Display Type Pressure Sensors - icon60 -50.0 50.0 500 50.0
Autonics PSAN Series Display Type Pressure Sensors - icon62 0.0 0.0 0 -50.0
 Window comparison output Autonics PSAN Series Display Type Pressure Sensors - icon54 Autonics PSAN Series Display Type Pressure Sensors - icon61 0.0 0.0 0 -50.0
Autonics PSAN Series Display Type Pressure Sensors - icon63 -50.0 50.0 500 50.0
Autonics PSAN Series Display Type Pressure Sensors - icon64 0.0 0.0 0 -50.0
Autonics PSAN Series Display Type Pressure Sensors - icon65 -50.0 50.0 500 50.0
 Hysteresis- Window comparison output Autonics PSAN Series Display Type Pressure Sensors - icon55 Autonics PSAN Series Display Type Pressure Sensors - icon66 -50.0 50.0 500 50.0
Autonics PSAN Series Display Type Pressure Sensors - icon67 0.0 0.0 0 -50.0
Autonics PSAN Series Display Type Pressure Sensors - icon68 0.0 0.0 500 -50.0
Autonics PSAN Series Display Type Pressure Sensors - icon69 -50.0 50.0 0 50.0
Auto sensitivity setting Autonics PSAN Series Display Type Pressure Sensors - icon56 Autonics PSAN Series Display Type Pressure Sensors - icon70 0.0 0.0 0 -50.0
Autonics PSAN Series Display Type Pressure Sensors - icon71 -50.0 50.0 500 50.0
Autonics PSAN Series Display Type Pressure Sensors - icon72 -25.0 25.0 250 0.0
Forced output control Autonics PSAN Series Display Type Pressure Sensors - icon57

Output Operation Mode

Change the output operation mode to change pressure detection method.

Autonics PSAN Series Display Type Pressure Sensors - icon3

■ Hysteresis

  • Set the hysteresis for pressure detection directly.
  • Setting: Pressure detection level (ST1, ST2), Hysteresis (HYS1, HYS2)

Autonics PSAN Series Display Type Pressure Sensors - Setting1

Hysteresis – Window comparison output

  • It is available both hysteresis mode and window comparison output mode operations.
  • Setting: Pressure detection level (ST1), Hysteresis (HYS1), High limit (HIGH), Low limit (LOW)

Autonics PSAN Series Display Type Pressure Sensors - Setting2

Forced output control

  • It displays the present pressure with forcibly holding comparing output OFF regardless of setting value.
  • Manual ON/OFF for OUT1/2 is possible by [M], [▼] or [▲] key during forced output control operation.

Autonics PSAN Series Display Type Pressure Sensors - Setting5

Window comparison output

  • It detects pressure at the desired range.
  • Hysteresis is fixed as min. display interval.
  • Setting: High limit (HI1, HI2), Low limit (LO1, LO2)

Autonics PSAN Series Display Type Pressure Sensors - Setting3

Auto sensitivity setting

  • This function is to set the proper position (SET) automatically by applied pressure from two positions (ST1, ST2).  SET=
  • Hysteresis is fixed as min. display interval.

Autonics PSAN Series Display Type Pressure Sensors - Setting4

Auto shift Preset Setting

Setting method [Parameter setting]

  1. Select P-9 External input terminal: SHFT.
  2. Press the [▲] key for over 3 sec. in RUN mode to enter Max / Min monitoring / Auto shift menu.
  3. Press the [M] key to entering Auto shift setting and press the [▼] or [▲] key to change preset.
  4. When reset the set correction value, press the [▼] + [▲] keys for over 1 sec .

[External input setting]

  1. At the desired preset value pressure, maintain low level for over 1 ms of Auto shift input (orange).
  2. The pressure at this time is measured and applied after 7.5 ms and is stored in the auto shift correction value.
Operation mode Preset Default Selling range
Auto- shift Autonics PSAN Series Display Type Pressure Sensors - icon42 Auto-shift
correction
Autonics PSAN Series Display Type Pressure Sensors - icon43 Autonics PSAN Series Display Type Pressure Sensors - icon44 Min. preset setting< SH.IN < Max. preset setting
Pressure Setting range
(after correction)
Setting range
(preset range)
Negavive -101.3 to 5.0 kPa -101.3 to 101.3 kPa
Static -5.0 to 110.0 kPa -110.0 to 110.0 kPa
-50.0 to 1100 kPa -1100 to 1100 kPa
Compound -101.3 to 110.0 kPa -101.3 to 110.0 kPa

Precaution

  • Auto shift correction is reset as 0 when changing P-2 OUT operation mode and preset value.
  • Preset setting range is wider than the rated pressure with the source pressure fluctuations.
  • In case of forced output control mode or PV HHHH/LLLL, Auto shift function does not operate.

Error

Display Cause Troubleshooting
Autonics PSAN Series Display Type Pressure Sensors - icon45 When external pressure is input while adjusting zero point. Try again after removing external pressure.
Autonics PSAN Series Display Type Pressure Sensors - icon46 When overload is applied on control output Remove overload.
Autonics PSAN Series Display Type Pressure Sensors - icon47 When ‘ST1’, ‘ST2’ setting range is not met in auto sensitivity setting mode. Check setting conditions and set proper setting values.
Autonics PSAN Series Display Type Pressure Sensors - icon48 When applied pressure exceeds high-limit of display pressure range. Apply pressure within display pressure range.
Autonics PSAN Series Display Type Pressure Sensors - icon49 When applied pressure exceeds low-limit of display pressure range.
Autonics PSAN Series Display Type Pressure Sensors - icon50 Auto shift correction error. Set the corrected setting value within setting pressure range.
Autonics PSAN Series Display Type Pressure Sensors - icon51
Autonics PSAN Series Display Type Pressure Sensors - icon52

Autonics logo18, Bansong-ro 513Beon-gil, Haeundae-gu, Busan, Republic of Korea, 48002
www.autonics.com 
+82-2-2048-1577
sales@autonics.com

Documents / Resources

Autonics PSAN Series Display Type Pressure Sensors [pdf] Instruction Manual
PSAN Series Display Type Pressure Sensors, PSAN Series, Display Type Pressure Sensors, Pressure Sensors, Sensors

References

Leave a comment

Your email address will not be published. Required fields are marked *