ABB-LOGO

ABB DS203NC Residual Current Circuit Breaker

ABB-DS203NC-Residual-Current-Circuit-Breaker -PRODUCT

The complete evolution
DS203NC and ABB modular range: absolute integration

ABB is present on the market of electric installations with a range of the most complete and integrated modular DIN rail components. Circuit breakers, control and measurement solutions, devices for energy saving and many more are realized in compliance with the standards to anticipate the application needs of the customers, and are developed and constantly improved to ensure cutting-edge performance. A real “team”, in which it is also involved the family of DS203NC residual current circuit breakers with overcurrent protection. Designed to respect the concept of compatibility that permeates the entire portfolio of ABB modular products, also this line takes account of the growing plant-related constraints and demanding requirements of protection imposed worldwide by new generation installations.

In any application where the dimensions represent a potential barrier, the products of the family of DS203NC residual current circuit breakers with overcurrent protection from ABB guarantee a reliable and complete protection againstovercurrent and earth fault currents.

Characterised by a compact size, equal to a normal 4-pole MCB, the 3P+N RCBO of the line DS203NC are suitable to three-phase circuits installed in environments where space is a precious resource, such as zones for marinas and camping, switchboards for temporary environments such as yards orexhibitions, industrial sockets and power generators. The line focuses on the efficiency of installation, sharing all the functional and mounting characteristics that distinguish the modular devices of the System pro M compact® family. Thanks to this legacy, the DS203NC RCBOs offer a solution of international standing, with a wide set of certifications and the level of quality that only a global and recognized manufacturer as ABB can ensure.

The essential protection
New solutions and retrofit: the importance of versatility

In all electrical installations it is crucial to ensure, at any time and under any condition, the safety of people, facilities and related equipment. Even in applications where space is a limited resource, the quality of protection must be given and guaranteed through features effective and respectful of the standards, without penalizing aspects such as size, ease of installation and flexibility of use.

The DS203NC family of 3P+N residual current circuit breakers with overcurrent protection by ABB has been developed with the aim of meeting requirements such as the protection and safety of people, equipment or facilities, offering a compact solution in 4 modules that is at the top of its category from every point of view. Ideal for the protection of three-phase distribution circuits in commercial facilities, but also of equipment and industrial sockets, the products of the RCBO 3P+N DS203NC family of ABB have all the necessary specifications to ensure reliable and durable performance, offering space savings of 30% comparedto a standard configuration. DS203NC RCBOs are the ideal solution for new installations,ensuring space saving in switchboards, as well as in retrofitting of existing plants, by adding earth fault current protection in installations where it wasn’t foreseen, without any impact on the overall dimensions of the system and on the placing of the existing devices

ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-1

The compact reliability
DS203NC: increase safety, reduce space

Totally integrated into the modular range System pro M compact®, the DS203NC residual current circuit breakers with overcurrent protection respond to the request for protective equipment that meet the different types of circuits of the modern three phases systems, increasingly compact and sensitive. Thanks to the many types and to a width of 4 modules only, the series DS203NC (“C” stands for “Compact”) allows to reduce the used space to a third compared to a traditional 3P+N solution.

ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-2

DS203NC range combines in a single device of only four modules width the protection against overcurrents (overload and short circuit) and earth fault currents. The range, developed in accordance to product standards IEC/EN 61009-1 and IEC/EN 61009-2-1, is available in two rated breaking capacities: DS203NC L (4500 A) and DS203NC (6000 A). The extreme breaking capacity Icu according to IEC/EN 60947- 2 is 6 kA for DS203NC L and10 kA for DS203NC, making these devices performing and suitable especially in industrial applications. The range includes AC, A, APR or S versions, with sensitivity levels of 30, 100 or 300 mA and intervention curves B, C or K. The APR versions ensure high immunity to unwanted trippingsdue to transient overvoltage generated, or by capacitive filters of electronic devices like computers, printers, faxes etc.

For these versions, the surge current withstand rises to 3000 A (8/20 wave), compared to 250 A of the standard models. The compatibility with ABB CMS (Circuit Monitoring Systems) enables a consistent management of the network and a permanent monitoring of the circuit, anticipating the occurrence of faults. DS203NC has been tested in accordance to IEC 61373 standard “Railway applications – Rolling stock equipment – Shock and vibration tests” meeting the requirement of Category 1-Class B thus making DS230NC suitable for all the installations subjected to high shocks and vibrations

In addition to its compact size, further elements that distinguish the products of the range of DS203NC residual current circuit breakers with overcurrent protection are the ease of use and management. These features, combined with the quality parameters typical of the ABB brand, make these solutions ideal for applications of international scope, where they can rely on the numerous certificates of conformity issued by leading worldwide regulatory bodies.
The RCBO DS203NC can be used in three phase systems with or without neutral, with no need to add any external resistance: this gives the opportunity to enjoy a unique product code to cover different applications, simplifying logistics and management of parts in stock.

The logistical aspect is further optimized thanks to the radio frequency identification (RFid) tag that equips each unit and allows ABB both to trace the product information, as to track and verify the authenticity of the individual devices through the unique code assigned by ABB in accordance with the standards ISO/ IEC FCD 15693-3. In terms of simplification, these products also consider the needs of the installer.

The devices use the same profile as the family System pro M compact®, with which they can share the accessories via the interface module. Suitable for mounting on DIN rail thanks to the simple fixing device, the RCBOs DS203NC have terminals with two slots that allow to use different types of conductors: one housing is designed for cables up to 25 mm2, the other for busbars or cables up to 10 mm2. The devices can be supplied both from bottom and top terminals. In addition to ensuring maximum flexibility, this set of features allows to meet the different installation habits in different countries. This is further supported by the reliability and warranty of the ABB brand and a quality and compliance to standards that are tested and approved by many global bodies, including IMQ, VDE and KEMA. The framework of the features is complemented by numerous measures designed to optimize the operation, to facilitate troubleshooting and to reduce inefficiencies and downtime. Notable among them are the tripping indicator, the contact position indicator to ease the identification of causes of fault.

ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-3

The effective choice
The benefits of a product with the highest quality standards

ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-4

ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-5

DS203NC
Technical features

ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-6

ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-7

DS203NC
Overall dimensions

ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-8

DS203NC
Order code

ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-9

DS203NC L – AC type – C curve
Icn = 4500 A

Poles Rated residual current

I∆n A

Rated current

In A

Description Pack unit

pc.

Type ABB code EAN code
3P+N 0,03 6 DS203NC L C6 AC30 2CSR246040R1064 8012542353928 1
8 DS203NC L C8 AC30 2CSR246040R1084 8012542343622 1
10 DS203NC L C10 AC30 2CSR246040R1104 8012542353829 1
13 DS203NC L C13 AC30 2CSR246040R1134 8012542343523 1
16 DS203NC L C16 AC30 2CSR246040R1164 8012542353720 1
20 DS203NC L C20 AC30 2CSR246040R1204 8012542343424 1
25 DS203NC L C25 AC30 2CSR246040R1254 8012542353621 1
32 DS203NC L C32 AC30 2CSR246040R1324 8012542343325 1
0,3 6 DS203NC L C6 AC300 2CSR246040R3064 8012542343226 1
8 DS203NC L C8 AC300 2CSR246040R3084 8012542343127 1
10 DS203NC L C10 AC300 2CSR246040R3104 8012542343028 1
13 DS203NC L C13 AC300 2CSR246040R3134 8012542342922 1
16 DS203NC L C16 AC300 2CSR246040R3164 8012542776727 1
20 DS203NC L C20 AC300 2CSR246040R3204 8012542342823 1
25 DS203NC L C25 AC300 2CSR246040R3254 8012542342724 1
32 DS203NC L C32 AC300 2CSR246040R3324 8012542358428 1

ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-9DS203NC L – A type – C curve
Icn = 4500 A

Poles Rated residual current

I∆n A

Rated current

In A

Description Pack unit

pc.

Type ABB code EAN code
3P+N 0,03 6 DS203NC L C6 A30 2CSR246140R1064 8012542354628 1
8 DS203NC L C8 A30 2CSR246140R1084 8012542344322 1
10 DS203NC L C10 A30 2CSR246140R1104 8012542354529 1
13 DS203NC L C13 A30 2CSR246140R1134 8012542344223 1
16 DS203NC L C16 A30 2CSR246140R1164 8012542354420 1
20 DS203NC L C20 A30 2CSR246140R1204 8012542344124 1
25 DS203NC L C25 A30 2CSR246140R1254 8012542354321 1
32 DS203NC L C32 A30 2CSR246140R1324 8012542498025 1
0,3 6 DS203NC L C6 A300 2CSR246140R3064 8012542499220 1
8 DS203NC L C8 A300 2CSR246140R3084 8012542344025 1
10 DS203NC L C10 A300 2CSR246140R3104 8012542354222 1
13 DS203NC L C13 A300 2CSR246140R3134 8012542343929 1
16 DS203NC L C16 A300 2CSR246140R3164 8012542354123 1
20 DS203NC L C20 A300 2CSR246140R3204 8012542343820 1
25 DS203NC L C25 A300 2CSR246140R3254 8012542354024 1
32 DS203NC L C32 A300 2CSR246140R3324 8012542343721 1

DS203NC L – APR type – C curveABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-9
Icn = 4500 A

Poles Rated residual current

I∆n A

Rated current

In A

Description Pack unit

pc.

Type ABB code EAN code
3P+N 0,03 6 DS203NC L C6 APR30 2CSR246440R1064 8012542079125 1
8 DS203NC L C8 APR30 2CSR246440R1084 8012542079026 1
10 DS203NC L C10 APR30 2CSR246440R1104 8012542078920 1
13 DS203NC L C13 APR30 2CSR246440R1134 8012542078821 1
16 DS203NC L C16 APR30 2CSR246440R1164 8012542078722 1
20 DS203NC L C20 APR30 2CSR246440R1204 8012542078623 1
25 DS203NC L C25 APR30 2CSR246440R1254 8012542078524 1
32 DS203NC L C32 APR30 2CSR246440R1324 8012542078425 1

DS203NC – AC type – B curveABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-9
Icn = 6000 A

Poles Rated residual current

I∆n A

Rated current

In A

Description Pack unit

pc.

Type ABB code EAN code
3P+N 0,03 6 DS203NC B6 AC30 2CSR256040R1065 8012542077428 1
8 DS203NC B8 AC30 2CSR256040R1085 8012542077329 1
10 DS203NC B10 AC30 2CSR256040R1105 8012542077220 1
13 DS203NC B13 AC30 2CSR256040R1135 8012542077121 1
16 DS203NC B16 AC30 2CSR256040R1165 8012542077022 1
20 DS203NC B20 AC30 2CSR256040R1205 8012542076926 1
25 DS203NC B25 AC30 2CSR256040R1255 8012542790525 1
32 DS203NC B32 AC30 2CSR256040R1325 8012542076827 1
0,1 6 DS203NC B6 AC100 2CSR256040R2065 8012542076728 1
8 DS203NC B8 AC100 2CSR256040R2085 8012542076629 1
10 DS203NC B10 AC100 2CSR256040R2105 8012542076520 1
13 DS203NC B13 AC100 2CSR256040R2135 8012542076421 1
16 DS203NC B16 AC100 2CSR256040R2165 8012542076322 1
20 DS203NC B20 AC100 2CSR256040R2205 8012542076223 1
25 DS203NC B25 AC100 2CSR256040R2255 8012542076124 1
32 DS203NC B32 AC100 2CSR256040R2325 8012542076025 1
0,3 6 DS203NC B6 AC300 2CSR256040R3065 8012542353423 1
8 DS203NC B8 AC300 2CSR256040R3085 8012542353324 1
10 DS203NC B10 AC300 2CSR256040R3105 8012542266327 1
13 DS203NC B13 AC300 2CSR256040R3135 8012542266228 1
16 DS203NC B16 AC300 2CSR256040R3165 8012542266129 1
20 DS203NC B20 AC300 2CSR256040R3205 8012542266020 1
25 DS203NC B25 AC300 2CSR256040R3255 8012542265924 1
32 DS203NC B32 AC300 2CSR256040R3325 8012542790822 1

DS203NC – AC type – C curveABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-9
Icn = 6000 A

Poles Rated residual current

I∆n A

Rated current

In A

Description Pack unit

pc.

Type ABB code EAN code
3P+N 0,03 6 DS203NC C6 AC30 2CSR256040R1064 8012542265825 1
8 DS203NC C8 AC30 2CSR256040R1084 8012542353225 1
10 DS203NC C10 AC30 2CSR256040R1104 8012542518228 1
13 DS203NC C13 AC30 2CSR256040R1134 8012542186823 1
16 DS203NC C16 AC30 2CSR256040R1164 8012542352228 1
20 DS203NC C20 AC30 2CSR256040R1204 8012542186724 1
25 DS203NC C25 AC30 2CSR256040R1254 8012542352129 1
32 DS203NC C32 AC30 2CSR256040R1324 8012542263920 1
0,1 6 DS203NC C6 AC100 2CSR256040R2064 8012542263821 1
8 DS203NC C8 AC100 2CSR256040R2084 8012542263722 1
10 DS203NC C10 AC100 2CSR256040R2104 8012542263623 1
13 DS203NC C13 AC100 2CSR256040R2134 8012542263524 1
16 DS203NC C16 AC100 2CSR256040R2164 8012542518327 1
20 DS203NC C20 AC100 2CSR256040R2204 8012542263425 1
25 DS203NC C25 AC100 2CSR256040R2254 8012542186021 1
32 DS203NC C32 AC100 2CSR256040R2324 8012542352020 1
0,3 6 DS203NC C6 AC300 2CSR256040R3064 8012542185925 1
8 DS203NC C8 AC300 2CSR256040R3084 8012542185826 1
10 DS203NC C10 AC300 2CSR256040R3104 8012542185727 1
13 DS203NC C13 AC300 2CSR256040R3134 8012542185628 1
16 DS203NC C16 AC300 2CSR256040R3164 8012542185529 1
20 DS203NC C20 AC300 2CSR256040R3204 8012542185420 1
25 DS203NC C25 AC300 2CSR256040R3254 8012542517825 1
32 DS203NC C32 AC300 2CSR256040R3324 8012542180821 1

DS203NC – A type – B curveABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-9
Icn = 6000 A

Poles Rated residual current

I∆n A

Rated current

In A

Description Pack unit

pc.

Type ABB code EAN code
3P+N 0,03 6 DS203NC B6 A30 2CSR256140R1065 8012542078326 1
8 DS203NC B8 A30 2CSR256140R1085 8012542078227 1
10 DS203NC B10 A30 2CSR256140R1105 8012542078128 1
13 DS203NC B13 A30 2CSR256140R1135 8012542078029 1
16 DS203NC B16 A30 2CSR256140R1165 8012542077923 1
20 DS203NC B20 A30 2CSR256140R1205 8012542077824 1
25 DS203NC B25 A30 2CSR256140R1255 8012542077725 1
32 DS203NC B32 A30 2CSR256140R1325 8012542077626 1
0,1 6 DS203NC B6 A100 2CSR256140R2065 8012542080329 1
8 DS203NC B8 A100 2CSR256140R2085 8012542080220 1
10 DS203NC B10 A100 2CSR256140R2105 8012542080121 1
13 DS203NC B13 A100 2CSR256140R2135 8012542080022 1
16 DS203NC B16 A100 2CSR256140R2165 8012542079927 1
20 DS203NC B20 A100 2CSR256140R2205 8012542079828 1
25 DS203NC B25 A100 2CSR256140R2255 8012542079729 1
32 DS203NC B32 A100 2CSR256140R2325 8012542079620 1
0,3 6 DS203NC B6 A300 2CSR256140R3065 8012542079521 1
8 DS203NC B8 A300 2CSR256140R3085 8012542079422 1
10 DS203NC B10 A300 2CSR256140R3105 8012542079323 1
13 DS203NC B13 A300 2CSR256140R3135 8012542079224 1
16 DS203NC B16 A300 2CSR256140R3165 8012542305026 1
20 DS203NC B20 A300 2CSR256140R3205 8012542305125 1
25 DS203NC B25 A300 2CSR256140R3255 8012542400226 1
32 DS203NC B32 A300 2CSR256140R3325 8012542400028 1

DS203NC – A type – C curveABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-9
Icn = 6000 A

Poles Rated residual current

I∆n A

Rated current

In A

Description Pack unit

pc.

Type ABB code EAN code
3P+N 0,03 6 DS203NC C6 A30 2CSR256140R1064 8012542400127 1
8 DS203NC C8 A30 2CSR256140R1084 8012542058823 1
10 DS203NC C10 A30 2CSR256140R1104 8012542896524 1
13 DS203NC C13 A30 2CSR256140R1134 8012542768227 1
16 DS203NC C16 A30 2CSR256140R1164 8012542830924 1
20 DS203NC C20 A30 2CSR256140R1204 8012542839927 1
25 DS203NC C25 A30 2CSR256140R1254 8012542768524 1
32 DS203NC C32 A30 2CSR256140R1324 8012542831228 1
0,1 6 DS203NC C6 A100 2CSR256140R2064 8012542840220 1
8 DS203NC C8 A100 2CSR256140R2084 8012542896425 1
10 DS203NC C10 A100 2CSR256140R2104 8012542768128 1
13 DS203NC C13 A100 2CSR256140R2134 8012542830825 1
16 DS203NC C16 A100 2CSR256140R2164 8012542839828 1
20 DS203NC C20 A100 2CSR256140R2204 8012542896722 1
25 DS203NC C25 A100 2CSR256140R2254 8012542768425 1
32 DS203NC C32 A100 2CSR256140R2324 8012542831129 1
0,3 6 DS203NC C6 A300 2CSR256140R3064 8012542840121 1
8 DS203NC C8 A300 2CSR256140R3084 8012542830726 1
10 DS203NC C10 A300 2CSR256140R3104 8012542839729 1
13 DS203NC C13 A300 2CSR256140R3134 8012542896623 1
16 DS203NC C16 A300 2CSR256140R3164 8012542768326 1
20 DS203NC C20 A300 2CSR256140R3204 8012542831020 1
25 DS203NC C25 A300 2CSR256140R3254 8012542840022 1
32 DS203NC C32 A300 2CSR256140R3324 8012542631620 1

DS203NC – A type – K curveABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-9
Icn = 6000 A

Poles Rated residual current

I∆n A

Rated current

In A

Description Pack unit

pc.

Type ABB code EAN code
3P+N 0,03 6 DS203NC K6 A30 2CSR256140R1067 8012542376026 1
8 DS203NC K8 A30 2CSR256140R1087 8012542629726 1
10 DS203NC K10 A30 2CSR256140R1107 8012542375920 1
13 DS203NC K13 A30 2CSR256140R1137 8012542779322 1
16 DS203NC K16 A30 2CSR256140R1167 8012542769323 1
20 DS203NC K20 A30 2CSR256140R1207 8012542631521 1
25 DS203NC K25 A30 2CSR256140R1257 8012542375821 1
32 DS203NC K32 A30 2CSR256140R1327 8012542779223 1

DS203NC – APR type – C curveABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-9
Icn = 6000 A

Poles Rated residual current

I∆n A

Rated current

In A

Description Pack unit

pc.

Type ABB code EAN code
3P+N 0,03 6 DS203NC C6 APR30 2CSR256440R1064 8012542349822 1
8 DS203NC C8 APR30 2CSR256440R1084 8012542180722 1
10 DS203NC C10 APR30 2CSR256440R1104 8012542349723 1
13 DS203NC C13 APR30 2CSR256440R1134 8012542261520 1
16 DS203NC C16 APR30 2CSR256440R1164 8012542261421 1
20 DS203NC C20 APR30 2CSR256440R1204 8012542261322 1
25 DS203NC C25 APR30 2CSR256440R1254 8012542261223 1
32 DS203NC C32 APR30 2CSR256440R1324 8012542261124 1
0,1 6 DS203NC C6 APR100 2CSR256440R2064 8012542274223 1
8 DS203NC C8 APR100 2CSR256440R2084 8012542517924 1
10 DS203NC C10 APR100 2CSR256440R2104 8012542261025 1
13 DS203NC C13 APR100 2CSR256440R2134 8012542180029 1
16 DS203NC C16 APR100 2CSR256440R2164 8012542349624 1
20 DS203NC C20 APR100 2CSR256440R2204 8012542179924 1
25 DS203NC C25 APR100 2CSR256440R2254 8012542179825 1
32 DS203NC C32 APR100 2CSR256440R2324 8012542179726 1
0,3 6 DS203NC C6 APR300 2CSR256440R3064 8012542179627 1
8 DS203NC C8 APR300 2CSR256440R3084 8012542179528 1
10 DS203NC C10 APR300 2CSR256440R3104 8012542179429 1
13 DS203NC C13 APR300 2CSR256440R3134 8012542518020 1
16 DS203NC C16 APR300 2CSR256440R3164 8012542176329 1
20 DS203NC C20 APR300 2CSR256440R3204 8012542351023 1
25 DS203NC C25 APR300 2CSR256440R3254 8012542176220 1
32 DS203NC C32 APR300 2CSR256440R3324 8012542350927 1

DS203NC – A S type – C curveABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-9
Icn = 6000 A

Poles Rated residual current

I∆n A

Rated current

In A

Description Pack unit

pc.

Type ABB code EAN code
3P+N 0,1 16 DS203NC C16 A S100 2CSR256240R2164 8012542021827 1
20 DS203NC C20 A S100 2CSR256240R2204 8012542021728 1
25 DS203NC C25 A S100 2CSR256240R2254 8012542021629 1
32 DS203NC C32 A S100 2CSR256240R2324 8012542021520 1
0,3 16 DS203NC C16 A S300 2CSR256240R3164 8012542297727 1
20 DS203NC C20 A S300 2CSR256240R3204 8012542373223 1
25 DS203NC C25 A S300 2CSR256240R3254 8012542373124 1
32 DS203NC C32 A S300 2CSR256240R3324 8012542077527 1

DS203NC
Auxiliary elements and accessories

ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-10 ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-11

Accessories and integration
Fully equipped, perfectly modular

ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-12

  • SN201-IH = coupling interface / auxiliary contact
  • SN201-S = signal contact
  • S2C-H6R = auxiliary contact
  • S2C-S/H6R = signal/ auxiliary contact
  • S2C-S/H6R (H) = signal/ auxiliary contact used as auxiliary contact
  • F2C-A = shunt trip
  • S2C-UA = undervoltage release
  • S2C-OR = overvoltage release
  •  The interface has to be installed in order to accessorize DS203NC with the System pro M compact® series accessories

Technical details
Tripping characteristics

ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-13 ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-14

Technical details
Limitation of specific let-through energy I2t

ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-15 ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-16 ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-17

Technical details
Peak current Ip

ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-18 ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-19 ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-20

Technical details
Influence of adjacent devices, derating in temperature, power loss and performance in altitude

ABB-DS203NC-Residual-Current-Circuit-Breaker -FIG-21

Contact us

  • ABB SACE A division of ABB S.p.A. Line Protection Devices Viale dell’Industria, 18 20010 Vittuone (MI) – Italy
  • www.abb.com/lowvoltage
  • www.abb.com
  • The data and illustrations are not binding. We reserve the right to modify the contents of this document on the basis of technical development of the products, without prior notice. Copyright 2015 ABB. All rights reserved.

Documents / Resources

ABB DS203NC Residual Current Circuit Breaker [pdf] User Guide
DS203NC Residual Current Circuit Breaker, DS203NC, Residual Current Circuit Breaker, Current Circuit Breaker

References

Leave a comment