PHILIPS PDRAS Room Automation System Installation Guide
PHILIPS PDRAS Room Automation System

Installation Instructions

Devices must be installed by a qualified electrician in accordance with all national and local electrical and construction codes and regulations.

ASSEMBLY INSTRUCTION

ASSEMBLY INSTRUCTION
ASSEMBLY INSTRUCTION

PRODUCT DIMENSION

PRODUCT DIMENSION

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION
INSTALLATION INSTRUCTION
INSTALLATION INSTRUCTION

Supply input

Supply input
SAFETY ICON Supply input must be protected with external 120V/15A circuit breaker
Supply input
Supply input
Supply input

Output Ratings/Channel (CH)

Load Type CH1-CH5
General Use
 General Use 16 A, 277 V
Incandescent Incandescent
Standard Ballast
 Standard Ballast
Electronic Ballast
 Electronic Ballast
M Motor 16 FLA (1 HP), 120 V 14.5 FLA (2 1 /2 HP), 240 V 14.1 FLA (3 HP), 277 V
Pilot Duty
 Pilot Duty 6 A, 120 V 3 A, 240 V 2.6 A, 277 V

Control Channel Ratings

Control Channel Ratings
DALI Addressable and Broadcast ≤ 10/CH Guaranteed 20 mA Maximum 250 mA Insulation: basic ≤ 50
DSI ≤ 10/CH ≤ 50
1-10 V Sink 10 mA Source 10 mA Driver dependent

Output Ratings/Group
CH-CH ≤ 300 V (UL)/400 V (CE) DDBC516FR ≤ 80 A

Single-room system

SAFETY ICON Only one ultrasonic sensor per room

SAFETY ICON Sensor placement depends on local architecture

Single-room system

SAFETY ICON Outputs configured for 1-10 V control

Dual-room system

SAFETY ICON Only one ultrasonic sensor per room
SAFETY ICON Sensor placement depends on local architecture

Dual-room system

SAFETY ICON Outputs configured for 1-10 V control

DIAGRAM

SAFETY ICON Outputs configured for 1-10 V control

CABLE PORT

Antumbra

Antumbra

Sensor

CAT5e / CAT6

Single-room

Dual-room

System Manager

Move fuse wire

Move fuse wire

Frequency Notice Federal Communications Commission (FCC) Compliance Notice: Radio Frequency Notice –
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Consult the dealer or an experienced radio/TV technician for help. Any modifications not approved by the manufacturer of this device could void the user’s authority to operate this device

Frequency Notice This Class B digital apparatus complies with Canadian ICES-003: CAN ICES-3(B)/NMB-3(B). Cet appareil numerique de la classe B est conforme a la norme NMB003 du Canada: CAN ICES-3(B)/NMB-3(B).

Frequency Notice Suitable for plenum install per NEC 300.22(C)(3).

© 2022 Signify Holding. All rights reserved. Specifications are subject to change without notice. No representation or warranty as to the accuracy or completeness of the information included herein is given and any liability for any action in reliance thereon is disclaimed. Philips and the Philips Shield Emblem are registered trademarks of Koninklijke Philips N.V. All other trademarks are owned by Signify Holding or their respective www.dynalite.com

Documents / Resources

PHILIPS PDRAS Room Automation System [pdf] Installation Guide
PDRAS Room Automation System, PDRAS, PDRAS Automation System, Room Automation System, Automation System

References

Leave a comment

Your email address will not be published. Required fields are marked *