1. Nhanganyaya
This manual provides essential information for the safe and effective installation, operation, and maintenance of the Danfoss MCI 15 Motor Controller, model 037N0039. Please read this manual thoroughly before attempting to install or operate the device. Retain this manual for future reference.
2. Safety Information
Gara uchicherechedza zvinotevera zvekuchengetedza kudzivirira kukuvara kana kukuvadzwa kwemidziyo:
- Kuisa uye kugadzirisa kunofanira kuitwa chete nevashandi vanokwanisa.
- Iva nechokwadi chekuti magetsi adzima usati waita chero waya kana kugadzirisa.
- Verify all connections are secure and correctly wired according to the provided diagrams.
- Dzivirira mudziyo kubva kuhunyoro, guruva, uye tembiricha yakanyanya.
- Do not operate the controller if it appears damaged.
3. Chigadzirwa Pamusoroview
The Danfoss MCI 15 Motor Controller is designed for controlling motor speed and soft starting applications. It features robust construction with an integrated heat sink for efficient thermal management.




4. Zvinotsanangurwa
Key technical specifications for the Danfoss MCI 15 Motor Controller:
| Parameter | Value |
|---|---|
| Model Number | MCI 15 (037N0039) |
| Yakatemerwa ikozvino (kureva) | Max 15 A AC 53a |
| Kudzora Voltage (Uc) | 24-480 V AC/DC |
| Kushanda Voltage (Ue) | 380-480V 50/60Hz |
| Insulation Voltage (Ui) | 660V |
| Impulse Withstand Voltage (Uimp) | 4 kV |
| Product Dimensions | 5 x 5 x 2 inches |
| Item Weight | 1.35 makirogiramu |
| Material | Copper (heat sink) |
| Max Fuse | 50 A gL/gG |
| Overload Relay Trip Class | 10 |
| HP Rating (400-480V) | 10 HP |


5. Setup uye Kuiswa
5.1 Kuiswa
The Danfoss MCI 15 Motor Controller is designed for panel mounting. Ensure adequate ventilation around the heat sink to prevent overheating. Use appropriate fasteners through the mounting brackets shown in Figure 3.4.
5.2 Wiring
Refer to the wiring diagram on the device label (Figure 4.1) for correct connections. Ensure all wiring adheres to local electrical codes and safety standards.
- Power Input (L1, L2, L3): Connect the three-phase power supply to terminals 1/L1, 3/L2, and 5/L3.
- Motor Output (T1, T2, T3): Connect the motor leads to terminals 2/T1, 4/T2, and 6/T3.
- Control Input (A1, A2): Batanidza control voltage to terminals A1 and A2.
- Use recommended wire sizes (e.g., 0.75-6mm² or 18-10AWG for power, 0.5-1.5mm² or 20-16AWG for control) and tighten terminals to the specified torque (e.g., 0.5Nm or 4.4lb-in for M3 screws).
5.3 Zvirongwa zvekutanga
Before initial operation, adjust the potentiometers on the front panel (Figure 3.2) to desired settings:
- Ramp Up Time: Adjust the 'up' potentiometer to set the motor acceleration time (0-10 seconds).
- Ramp Down Time: Adjust the 'down' potentiometer to set the motor deceleration time (0-10 seconds).
- Kutanga Kutanga: Adjust this potentiometer to provide an initial torque boost for starting loads.
- Initial Torque: Adjust this potentiometer to set the initial torque level during startup.
6. Operating Instructions
Once installed and configured, the Danfoss MCI 15 Motor Controller operates by applying a controlled voltageramp to the motor, providing a soft start and stop. The motor will accelerate to full speed over the set ramp-up time and decelerate over the set ramp- nguva yekuzorora.
- Shandisa control voltage to terminals A1 and A2 to initiate motor operation.
- Remove control voltage to initiate motor stop (soft stop).
- Monitor motor performance and adjust ramp times and torque settings as needed for optimal operation.
7. Kuchengeta
Regular maintenance ensures the longevity and reliable operation of the motor controller.
- Kuchenesa: Periodically clean the exterior of the controller, especially the heat sink fins, to ensure proper heat dissipation. Use a dry, soft cloth. Do not use solvents or abrasive cleaners.
- Kuongorora: Regularly inspect wiring connections for tightness and signs of wear or damage. Check for any discoloration or unusual odors, which may indicate overheating.
- Environment: Ita shuwa kuti nzvimbo yekushanda inoramba iri mukati metembiricha yakatarwa uye humidity range.
8. Kugadzirisa matambudziko
If the motor controller does not operate as expected, consider the following basic troubleshooting steps:
- No Motor Start: Verify power supply to the controller and motor. Check control signal to A1/A2. Ensure all wiring is correct and secure.
- Motor overheating: Check for proper ventilation around the heat sink. Ensure the motor is not overloaded. Verify motor parameters are correctly set.
- Incorrect Ramp Nguva: Re-adjust the 'up' and 'down' potentiometers on the front panel.
- Unexpected Stops: Check for power fluctuations or intermittent control signals. Inspect for any fault indicators if available on the device or system.
For complex issues, contact Danfoss technical support.
9. Warranty uye Tsigiro
For information regarding product warranty, technical support, or service, please refer to the official Danfoss website or contact your local Danfoss representative. Ensure you have the model number (MCI 15) and serial number (if applicable, visible on the rear label, Figure 7.1) available when contacting support.