Smiths EXT 60 Caspian Fan Convectors Owner’s Manual
Warm air is delivered at 1.7m from the base/floor level and the heater can be installed as an exposed unit or within a recess
Caspian fan convectors are both a practical and high quality heating solution for any commercial project Incorporating the latest EC motor technology, which can result in running-cost savings as high as 70%, and with variable speed control as standard, the Caspian delivers heat quickly and quietly
It is possible to have master and slave Caspian fan convectors that integrate the entire range of EC Caspian products. Please contact either our sales team or technical team to ensure that this is correctly specified
Caspians are compatible with most types of wet central heating systems, functioning equally efficiently with conventional boilers, biomass technology or ground or air source heat pumps
The airflow can be reversed so that the warm air is discharged from the lower vent. Please contact either our sales team or technical team to ensure that the correct inlet/discharge positioning is specified
Available with Smart Control and Antibacterial paint
Product Information
Motor
EC (BMS compliant).
Finish
Casing: zinc-coated steel 1.2mm .
Polyester powder-coated: white RAL 9010.
Available to special order in any colour and with anti-microbial or antibacterial paint.
Filter
Class G2, 100% polyester, non-washable.
Installation
Suitable for two-pipe central heating systems.
Maximum installation height for high or ceiling mounting – 4m to underside.
Pipework access holes on the rear and underside.
Key operated front access panels.
Bleed valve accessible on removal of front casing.
Unit must be earthed.
Commissioning
Check water is hot enough to activate the low temperature cut-out thermostat.
Controls
See accessories table.
Specification
To specify state:
Fan Convector with EC motor, in 1.2mm zinc coated steel, 1800mm high and 595mm, 895mm, 1195mm, 1495mm or 1795mm wide.
With variable heat output controller. As Smith’s Caspian EXT 60, 90, 120, 150, 180.
Technical Data
Heat output – EC
Model Reference | Fan Speed | Control Voltage VDC | 40°C MWT | 45°C MWT | 50°C MWT | 55°C MWT | 60°C MWT | 65°C MWT | 70°C MWT | 75°C MWT | 80°C MWT | |||||||
EC 60 | Low | 3.8 | 0.85 | 1.20 | 1.55 | 1.96 | 2.37 | 2.78 | 3.19 | 3.61 | 4.02 | |||||||
Mid | 4.9 | 1.13 | 1.62 | 2.10 | 2.58 | 3.06 | 3.55 | 4.03 | 4.51 | 5.00 | ||||||||
High | 6.4 | 1.47 | 2.05 | 2.63 | 3.21 | 3.79 | 4.36 | 4.94 | 5.52 | 6.10 | ||||||||
EC 90 | Low | 3.2 | 1.98 | 2.55 | 3.11 | 3.67 | 4.24 | 4.80 | 5.37 | 5.93 | 6.50 | |||||||
Mid | 4.6 | 2.80 | 3.58 | 4.36 | 5.14 | 5.91 | 6.69 | 7.47 | 8.25 | 9.03 | ||||||||
High | 6.1 | 3.68 | 4.65 | 5.62 | 6.59 | 7.55 | 8.52 | 9.49 | 10.46 | 11.42 | ||||||||
EC 120 | Low | 3.1 | 3.03 | 3.61 | 4.19 | 4.78 | 5.36 | 5.94 | 6.53 | 7.11 | 7.69 | |||||||
Mid | 4.3 | 3.91 | 4.87 | 5.82 | 6.78 | 7.74 | 8.70 | 9.65 | 10.61 | 11.57 | ||||||||
High | 5.5 | 4.84 | 6.00 | 7.17 | 8.33 | 9.49 | 10.66 | 11.82 | 12.99 | 14.15 | ||||||||
EC 150 | Low | 2.9 | 3.59 | 4.57 | 5.55 | 6.53 | 7.51 | 8.49 | 9.47 | 10.45 | 11.44 | |||||||
Mid | 4.0 | 4.77 | 6.10 | 7.43 | 8.76 | 10.08 | 11.41 | 12.74 | 14.07 | 15.39 | ||||||||
High | 5.1 | 6.47 | 7.71 | 8.96 | 10.21 | 11.45 | 12.70 | 13.94 | 15.19 | 16.43 | ||||||||
EC 180 | Low | 2.8 | 4.69 | 5.92 | 7.15 | 8.39 | 9.62 | 10.85 | 12.08 | 13.31 | 14.55 | |||||||
Mid | 3.9 | 4.93 | 7.15 | 9.38 | 11.60 | 13.82 | 16.05 | 18.27 | 20.49 | 22.72 | ||||||||
High | 4.9 | 7.90 | 9.74 | 11.58 | 13.42 | 15.27 | 17.11 | 18.95 | 20.79 | 22.63 | ||||||||
Model Reference | Fan Speed | Air Volume (m3/h) | Air Volume (l/s) | Specific Fan Power w/ls | Power Consumption (W) | NR in typical room* | Hydraulic Resistance (KPA) | Nominal Weight (KG) | Water Capacity (L) | |||||||||
EC 60 | Low | 201.00 | 55.90 | 0.14 | 8.00 | 34.00 | 1.38 | 23.00 | 0.92 | |||||||||
Mid | 290.50 | 80.75 | 0.26 | 21.00 | 41.50 | 1.69 | ||||||||||||
High | 380.00 | 105.60 | 0.32 | 34.00 | 49.50 | 2.00 | ||||||||||||
EC 90 | Low | 297.00 | 80.75 | 0.20 | 16.00 | 34.00 | 4.70 | 36.00 | 1.50 | |||||||||
Mid | 450.50 | 124.38 | 0.34 | 42.00 | 41.50 | 5.85 | ||||||||||||
High | 604.00 | 168.00 | 0.40 | 68.00 | 49.97 | 7.00 | ||||||||||||
EC 120 | Low | 419.30 | 116.50 | 0.14 | 16.00 | 34.00 | 17.78 | 45.00 | 2.08 | |||||||||
Mid | 549.65 | 152.68 | 0.26 | 40.00 | 42.00 | 20.59 | ||||||||||||
High | 680.00 | 188.89 | 0.34 | 64.00 | 49.96 | 23.40 | ||||||||||||
EC 150 | Low | 459.80 | 127.72 | 0.17 | 22.00 | 34.70 | 22.23 | 60.00 | 2.58 | |||||||||
Mid | 598.10 | 166.14 | 0.35 | 59.00 | 41.50 | 29.46 | ||||||||||||
High | 736.40 | 205.56 | 0.47 | 96.00 | 49.38 | 36.69 | ||||||||||||
EC 180 | Low | 542.00 | 150.56 | 0.19 | 29.00 | 34.90 | 47.83 | 78.00 | 3.18 | |||||||||
Mid | 690.00 | 191.67 | 0.40 | 78.50 | 41.50 | 60.76 | ||||||||||||
High | 838.00 | 232.78 | 0.55 | 128.00 | 49.00 | 73.70 |
*a typical room is taken as a room with a volume of 173m3 and a reverberation time of 0.8 seconds at 500 Hz with one unit installed, situated against a wall or ceiling (radiating noise in a quarters here). No allowance is made for attenuation provided by ceilings, enclosures or ductwork. Outputs based upon testing at EN442: 2014 using mean water temperature and an entering air temperature of 20°C with a 10°C temperature drop between flow and return
Correction factors
Mean Water Temp °C : 45 – 80
Entering Air Temperature °C | 15 | 1.13 | 1.10 | 1.07 | 1.05 |
18 | 1.08 | 1.05 | 1.02 | 0.99 | |
20 | 1.04 | 1.00 | 0.95 | 0.89 | |
25 | 0.93 | 0.91 | 0.89 | 0.86 |
Factors are approximate data based upon a standard coil.
How to calculate Mean Water Temperature
Mean watertemperature (∆T) | Flow temperature +Return temperature |
2 |
Ordering Guide
Model | Packed Wt (kg) | Product Codes |
CASPIAN EXT 60 EC | 30 | HPCA24001 |
CASPIAN EXT 90 EC | 49 | HPCA24002 |
CASPIAN EXT 120 EC | 58 | HPCA24003 |
CASPIAN EXT 150 EC | 76 | HPCA24004 |
CASPIAN EXT 180 EC | 95 | HPCA24005 |
Mounting Options
Dimensions
Rear Outlet
Plinths | Product Codes | |||
100mm Black | 100mm White | 150mm Black | 150mm White | |
CASPIAN FF/EXT/SL/TT 60 PLINTH | HACA33077 | HACA33087 | HACA33082 | HACA33092 |
CASPIAN FF/EXT/SL/TT 90 PLINTH | HACA33078 | HACA33088 | HACA33083 | HACA33093 |
CASPIAN FF/EXT/SL/TT 120 PLINTH | HACA33079 | HACA33089 | HACA33084 | HACA33094 |
CASPIAN FF/EXT/SL/TT 150 PLINTH | HACA33080 | HACA33090 | HACA33085 | HACA33095 |
CASPIAN FF/EXT/SL/TT 180 PLINTH | HACA33081 | HACA33091 | HACA33086 | HACA33096 |
Accessories | White Steel | Black steel | ||
POWDER-COATED STEEL INLET/OUTLET GRILLE (TO SUIT FF & EXT RO 60) | HACA33048 | HACA33053 | ||
POWDER-COATED STEEL INLET/OUTLET GRILLE (TO SUIT FF & EXT RO 90) | HACA33049 | HACA33054 | ||
POWDER-COATED STEEL INLET/OUTLET GRILLE (TO SUIT FF & EXT RO 120) | HACA33050 | HACA33055 | ||
POWDER-COATED STEEL INLET/OUTLET GRILLE (TO SUIT FF & EXT RO 150) | HACA33051 | HACA33056 | ||
POWDER-COATED STEEL INLET/OUTLET GRILLE (TO SUIT FF & EXT RO 180) | HACA33052 | HACA33057 | ||
Accessories | Product Codes | |||
ADJUSTABLE STRAIGHT AIR INLET/OUTLET EXTENSION DUCT (TO SUIT EXT & FF RO 60) | HACA33043 | |||
ADJUSTABLE STRAIGHT AIR INLET/OUTLET EXTENSION DUCT (TO SUIT EXT & FF RO 90) | HACA33044 | |||
ADJUSTABLE STRAIGHT AIR INLET/OUTLET EXTENSION DUCT (TO SUIT EXT & FF RO 120) | HACA33045 | |||
ADJUSTABLE STRAIGHT AIR INLET/OUTLET EXTENSION DUCT (TO SUIT EXT & FF RO 150) | HACA33046 | |||
ADJUSTABLE STRAIGHT AIR INLET/OUTLET EXTENSION DUCT (TO SUIT EXT & FF RO 180) | HACA33047 | |||
ANODISED ALUMINIUM INLET/OUTLET GRILLE (TO SUIT FF & EXT RO 60) | HACA33058 | |||
ANODISED ALUMINIUM INLET/OUTLET GRILLE (TO SUIT FF & EXT RO 90) | HACA33059 | |||
ANODISED ALUMINIUM INLET/OUTLET GRILLE (TO SUIT FF & EXT RO 120) | HACA33060 | |||
ANODISED ALUMINIUM INLET/OUTLET GRILLE (TO SUIT FF & EXT RO 150) | HACA33061 | |||
ANODISED ALUMINIUM INLET/OUTLET GRILLE (TO SUIT FF & EXT RO 180) | HACA33062 | |||
PENCIL PROOF GRILLE INSERT (PAIR TO SUIT FF, SL & UV 60) | HACA33069 | |||
PENCIL PROOF GRILLE INSERT (PAIR TO SUIT FF, SL & UV 90) | HACA33070 | |||
PENCIL PROOF GRILLE INSERT (PAIR TO SUIT FF, SL & UV 120) | HACA33071 | |||
PENCIL PROOF GRILLE INSERT (PAIR TO SUIT FF, SL & UV 150) | HACA33072 | |||
PENCIL PROOF GRILLE INSERT (PAIR TO SUIT FF, SL & UV 180) | HACA33073 | |||
FLEXIBLE HOSES 22MM PAIR | HAGA95003 | |||
ROOM THERMOSTAT HARD WIRED | HAGA95001 | |||
ROOM THERMOSTAT TAMPER PROOF | HAGA95004 | |||
CASPIAN PROPORTIONAL HEAT OUTPUT CONTROLLER 15°-25° INTEGRAL (EC) | HACA33005 | |||
CASPIAN PROPORTIONAL HEAT OUTPUT CONTROLLER 15°-25° REMOTE SENSOR (EC) | HACA33037 | |||
CASPIAN PROPORTIONAL HEAT OUTPUT CONTROLLER 11°-21° INTEGRAL (EC) | HACA33117 | |||
CASPIAN PROPORTIONAL HEAT OUTPUT CONTROLLER 11°-21° REMOTE SENSOR (EC) | HACA33118 | |||
BLANK CONFIGURABLE PROPORTIONAL HEAT OUTPUT CONTROLLER (PROGRAMMED AT FACTORY) | HACA33126 | |||
CASPIAN ADJUSTABLE LOW TEMPERATURE CUT-OUT | HACA33001 | |||
CASPIAN EXTERNAL CONTROL HARNESS (EC) | HACA33004 | |||
CASPIAN EC LINKING KIT (MASTER/SLAVE) | HACA33068 | |||
CASPIAN REMOTE SWITCHING ON/OFF RELAY (24V AC COIL) | HACA33127 | |||
CASPIAN EC THERMOSTAT (T1) & AUTO-SPEED CONTROL (T2) C/W CIRCUIT BOARD | HACA33039 | |||
CASPIAN THERMOSTAT (T1) (EC LOW LEVEL) | HACA33002 | |||
CASPIAN EC AUTO-SPEED CONTROL (T2) C/W CIRCUIT BOARD | HACA33038 |
As part our commitment to continuous improvement Smith’s Environmental Products may change the specifications of its products without prior notification or public announcement. All descriptions, illustrations, drawings and specifications in this publication present only general particulars and shall not form part of any contract. All dimensions are in mm unless otherwise stated. Please visit our website for the most up to date information.
Issue 014 | January 2025 +44 (0) 1245 324 900 | sales@smithsep.co.uk | SmithsEP.co.uk