SmartGen SGMA800-3200A Series Dual Power Automatic Transfer Switch

SmartGen-SGMA800-3200A-Series-Dual-Power-Automatic-Transfer-Switch-product

FAQ

  • Q: What is the rated voltage of the SGMA800-3200A Series Dual Power Automatic Transfer Switch?
    • A: The rated voltage of the switch is AC400V.
  • Q: In which industries can the SGMA800-3200A Series Dual Power ATS be used?
    • A: The switch can be used in various industries such as high-rise buildings, medical facilities, post and telecommunications, coal mines, ships, rail traffic, military, and fire facilities.

OVERVIEW

SGMA800~3200A series dual power ATS applies to the system which requires AC400V 50/60Hz below, rated working current 800A~3200A. Its structure is motor driven type, and there are three positions for the switch: normal (Ⅰ), spare (Ⅱ) and off (0). It can be used in the occasions where power failure is not allowed, such as high-rise buildings, medical heath, post and telecommunications, coal mine and ships, rail traffic, military and fire facilities.

This series products comply with the standard of GB GB/T 14048.11 ”Low-voltage switchgear and controlgear — part 6-1: Multiple function equipment —-Transfer switching equipment”.

STRUCTURE AND CHARACTERISTICS

SGMA800~3200A series dual power ATS adopts two-in and one-out structure, with electric key lock and mechanical padlock. Electric key lock: control the internal power supply of the switch, when the electric lock is open, the switch acts the automatic and remote operations; when the electric lock is closed, the switch only acts the manual operation. Mechanical padlock: during maintenance, pulling up the mechanical padlock to cut off the internal power supply of the switch, so the electric and manual operations of the switch will be disabled, which ensures the personal safety.

OVERALL DIMENSIONS AND CATEGORY

INSTRUCTION

SGMA800~3200A series dual power ATS can be divided into two types according to their shell frames: SGMA-1600A/4P, SGMA-3200A/4P, three-pole and four-pole switches can be provided by each type, which are suitable for both genset control and ATS control.

The rated current sequence of the switch includes: 800A, 1000A, 1600A, 2000A, 2500A, 3200A. The shapes of the switches are as follows:

Table 2 The Shapes of Switches

SmartGen-SGMA800-3200A-Series-Dual-Power-Automatic-Transfer-Switch-fig-1

SGMA800A-1600A OVERALL DIMENSIONS AND TECHNICAL DATA

SmartGen-SGMA800-3200A-Series-Dual-Power-Automatic-Transfer-Switch-fig-2

Table 3 SGMA800A-1600A Overall Dimensions

 

Model (SGMA)

Dimensions

(mm)

ATS Installation (mm) Terminals (mm)
A A1 B B1 C E G J K L M N P R S S1 T U V φX Y Y1 Y2
 

800A/3P

 

785

 

520

 

352

 

250

 

390

 

326

 

360

 

496

 

220

 

11

 

115

 

84

 

120

 

60

 

64

 

88

 

8

 

250

 

56.5

 

13

 

109

 

254

 

254

800A/4P 1080 635 352 250 390 326 540 610 220 11 115 84 120 60 64 88 8 250 60.5 13 109 254 254
1000A/3P 785 520 352 250 390 326 360 496 220 11 115 84 120 60 64 88 8 250 56.5 13 109 254 254
1000A/4P 1080 635 352 250 390 326 540 610 220 11 115 84 120 60 64 88 8 250 60.5 13 109 254 254
1250A/3P 785 520 368 250 390 326 360 496 220 11 115 84 120 80 68 100 8 250 56.5 13 109 254 254
1250A/4P 1080 635 368 250 390 326 540 610 220 11 115 84 120 80 68 100 8 250 60.5 13 109 254 254
1600A/3P 785 520 376 250 390 326 360 496 220 11 115 84 120 80 68 108 10 250 56.5 13 110 255 255
1600A/4P 1080 635 376 250 390 326 540 610 220 11 115 84 120 80 68 108 10 250 60.5 13 110 255 255

Table 4 SGMA800A-1600A Technical Parameter

Model SGMA-800A/XP SGMA-1000A/XP SGMA-1250A/XP SGMA-1600A/XP
Poles(P) 3P, 4P 3P, 4P 3P, 4P 3P, 4P
Rated Current 800A 1000A 1250A 1600A
Rated

Working Volt.

AC400V
Motor

Working Volt.

AC220V (175-277)V
Rated Insul. Volt.

Main Circuit

AC800V
Rated Impulse

Volt. Main Circuit

8 kV
Category AC-33iB
Short-time Withstand

Current

 

32 kA/60ms

Rated SC Ability 67.5 kA
Transfer Time

I-II or II-I

1.2s 1.8s
Mechanical Life 3000 times
Electrical Life 500 times
Weight (4P) 36kg 36kg 37kg 38.6kg

SGMA2000A-3200A OVERALL DIMENSIONS AND TECHNICAL DATA

SmartGen-SGMA800-3200A-Series-Dual-Power-Automatic-Transfer-Switch-fig-3

Table 5 SGMA2000A-3200A Overall Dimensions

Model (SGMA) Dimensions(mm) Switch Mounting (mm) Terminals (mm)
A A1 B G J R S T V Y1 Y2
2000A/3P 785 537 423 360 496 80 81 10 56 113 121
2000A/4P 1080 651 423 540 610 80 81 10 60 113 121
2500A/3P 785 537 433 360 496 80 81 15 56 118 116
2500A/4P 1080 651 433 540 610 80 81 15 60 118 116
3200A/3P 785 537 443 360 496 80 81 20 56 123 111
3200A/4P 1080 651 443 540 610 80 81 20 60 123 111

Table 6 SGMA2000A-3200A Technical Parameter

Model SGMA-2000A/XP SGMA-2500A/XP SGMA-3200A/XP
Poles(P) 3P, 4P 3P, 4P 3P, 4P
Rated Current 2000A 2500A 3200A
Rated

Working Volt.

AC400V
Motor

Working Volt.

AC220V (175-277)V
Rated Insul. Volt.

Main Circuit

AC800V
Rated Impulse

Volt. Main Circuit

8 kV
Category AC-33iB
Short-time

Withstand Current

32 kA/60ms
Rated SC Ability 67.5kA
Transfer Time

I-II or II-I

1.8s 2.4s
Mechanical Life 3000 times
Electrical Life 500 times
Weight (4P) 55kg 61kg 67kg

WIRINGS

SmartGen-SGMA800-3200A-Series-Dual-Power-Automatic-Transfer-Switch-fig-4

Table 7 Terminals and Descriptions

No. Function Remark
 

 

 

 

Power Terminal

 

101

 

AC220V Power L Output

101 106 are only used as signal to control power supply. 101, 106 cannot be used to mix connected with any

external circuit.

102 I# L-phase LW Input I# control power AC220V
103 I# N-phase NW Input
104 II# L-phase LW Input II# control power AC220V
105 II# N-phase NW Input
 

106

 

AC220V Power N Output

101 106 are only used as signal to control power supply. 101, 106 cannot be used to mix connected with any

external circuit.

 

 

 

 

Control Terminal

 

 

 

201

 

 

 

Auto      mode     via      short connection with 206

The automatic mode is controlled by ATS, the normal power is preferred.

Normal power is on, spare power is on, ATS I# is power- on.

Normal power is off, spare power is on, ATS II# is power-on.

Normal power is on, ATS I# is power-on.

202 COM Closed/Open control common port.
203 I# Normal Power Closed Close I# by connection with 202.
204 Open Open by connection with 202.
205 II# Spare Power Closed Close II# by connection with 202.
 

 

 

206

 

 

 

Auto      mode     via      short connection with 201

The automatic mode is controlled by ATS, the normal power is preferred.

Normal power is on, spare power is on, ATS I# is power- on.

Normal power is off, spare power is on, ATS II# is power-on.

Normal power is on, ATS I# is power-on.

 

 

 

 

 

Indication Terminal

 

301

 

Gen Start Signal Output (NO)

When detecting I# normal power is power-off, closed with

306. (Start/Stop delay cannot be set, start immediately and stop for 5s delay).

302 Closed/Open          Indication

COM

 

 

Externally connect to AC220V power indicator to display the closed/open status.

303 I# Closed Indication
304 Open Indication
305 II# Closed Indication
 

306

 

Gen Start Signal Output (NO)

When detecting I# normal power is power-off, closed with

301. (Start/Stop delay cannot be set, start immediately and stop for 5s delay).

 

 

 

Position Auxiliary Terminal

401 NC
402 I# Closed Output (Volts free) I# closed volts free feedback output, then 402, 403 are

closed.

403 I# Closed Output (Volts free)
404 II#    Closed    Output   (Volts

free)

 

II# closed volts free feedback output, then 404, 405 are closed .

405 II#    Closed    Output   (Volts

free)

406 NC /
 

 

 

 

 

Key & Padlock Auxiliary Terminal

501 NC /
 

502

Remote        Control/Manual Status     Indication    Output

(Volts free)

 

When the key is in Manual position, 502, 503 are closed. When the key is in Remote position, 502, 503 are disconnected.

 

503

Remote        Control/Manual Status     Indication    Output

(Volts free)

504 Padlock    Indication  Output

(Volts free)

When the padlock is pulled up, 504 505 are closed (cut off the internal power of ATS, the ATS cannot act electric and manual operations, then the maintenance is available.

When  the  padlock  is  pulled  down,  504  505  are

disconnected.

 

505

 

Padlock    Indication Output ((Volts free)

506 NC /

Table 8 Wiring Description

SmartGen-SGMA800-3200A-Series-Dual-Power-Automatic-Transfer-Switch-fig-5 SmartGen-SGMA800-3200A-Series-Dual-Power-Automatic-Transfer-Switch-fig-6

WORKING CONDITION

Table 9 Working Condition

Item Requirements
Working Temperature (-25~+70)ºC
Working Humidity (20~90)%RH
Installation Height ≤2000m
Pollution Degree 3-level

WIRING CONNECTION DIAGRAM

GENSET CONTROLLER APPLICATION DIAGRAM

SmartGen-SGMA800-3200A-Series-Dual-Power-Automatic-Transfer-Switch-fig-7

ATS CONTROLLER APPLICATION DIAGRAM

SmartGen-SGMA800-3200A-Series-Dual-Power-Automatic-Transfer-Switch-fig-8

INSTALLATION AND DEBUGGING

The installation and debugging of ATS should be carried out by professionals and person who knows the switchgear, the related protections and preventive measures must be considered during operating. The wirings of main circuit must be in a way that the leads are not subjected to any pressure or force. Before installation and debugging, firstly check if the switch is damaged or has any harmful effects, meanwhile, check for loose wires may be caused in transportation; clean up the dirt, especially the dirt on the surface of insulation parts, which may be caused by package materials during transportation or storage.

When connecting the primary circuit, pay attention to the phase sequence of the two power supplies that should be consistent, while connecting the secondary circuit, it should be strictly in accordance with the wiring diagram listed on the user manual, at the same time, notice that the voltage level of power supply; switch must be well grounded during installation. Considering in personal safety and the quickness of transferring, the handle is only used for debugging, users should not use the handle to operate with load. During debugging, firstly use handle to operate, then perform the electrical operation by manual button if there is nothing abnormal, finally go to the formal running.

ORDERING MODEL

SmartGen-SGMA800-3200A-Series-Dual-Power-Automatic-Transfer-Switch-fig-9

Table 10 Packing List

No. Item                        Qty.
4P      3P
1 ATS 1
2 Installation Instructions 1
3 Operating Handle 1
4 Electrical Key 2
5 Nut M12  

 

 

48

 

 

 

36

6 Spring Washer M12
7 Flat Washer M12
 

8

800A-1600A Outer Hexagonal Flat Brain/12*40 4.8
2000A Outer Hexagonal Flat Brain/12*45 4.8
2500A Outer Hexagonal Flat Brain/12*45 4.8
3000A Outer Hexagonal Flat Brain/12*60 4.8

CONTACT

SmartGen Registered trademark

All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder.
SmartGen reserves the right to change the contents of this document without prior notice.

Table 1 Software Version

Date Version Content
2024-03-07 1.0 Original release.

Documents / Resources

SmartGen SGMA800-3200A Series Dual Power Automatic Transfer Switch [pdf] User Manual
SGMA800-3200A Series, SGMA800-3200A Series Dual Power Automatic Transfer Switch, Dual Power Automatic Transfer Switch, Power Automatic Transfer Switch, Automatic Transfer Switch, Transfer Switch, Switch

References

Leave a comment

Your email address will not be published. Required fields are marked *