SmartGen ATA600 Dual Power Switch Adaptor
All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder.
Applications for the copyright holder’s written permission to reproduce any part of this publication should be addressed to Smartgen Technology at the address above. Any reference to trademarked product names used within this publication is owned by their respective companies.
SmartGen Technology reserves the right to change the contents of this document without prior notice.
Table 1 Software Version
Date | Version | Note |
2019-12-30 | 1.0 | Original Release |
2021-02-25 | 1.1 | Add illustration for optional terminals. |
2022-04-19 | 1.2 | Update the logo of SmartGen. |
OVERVIEW
ATA600 Dual Power Switch Adapter is a kind of adapter which makes convenience for connection between HAT600/HAT600N/HAT600P/HAT700 dual power ATS controller and smart breaker, reducing a lot of field wiring work for users, not only labor saving, time saving but also reliable.
PERFORMANCE AND CHARACTERISTICS
- Suitable for 3Ph 4W AC system;
- Two integrated 400V/50Hz/10A circuits of air breaker, which are individually used to connect two circuits of AC power;
- All-in-one integrated adaptor, which can simultaneously connect S1 breaker, and S2 breaker;
- Suitable for HAT600/HAT600N/HAT600P/HAT700 dual power ATS controller;
- Cold rolled plate closure;
- With screw installation method, adapter is fixed by 4 screws.
SPECIFICATION
Table 2 Performance Parameters
Item |
Description |
Rated Working Voltage | AC 400V 50/60Hz |
Max Working Current | 10A |
Air Breaker | 400V~ 50Hz 10A |
Case Dimensions | 144.4mmx252mmx75.3mm |
Working Temperature | (-25~+70)°C |
Working Humidity | (20~93)%RH |
Storage Temperature | (-30~+80)°C |
Insulation Strength | Apply AC1.5kV voltage between high voltage terminal and low voltage terminal and the leakage current is not more than 3mA within 1min. |
Weight | 1.6kg |
PANEL DESCRIPTION
PANEL ILLUSTRATION
Panel illustration is as Fig. 1.
- Two circuits of air breaker, connect separately with S1/S2 AC power.
- Connector M1, M2, M3 need to connect to the side of
- HAT600/HAT600N/HAT600P/HAT700 controller.
- Connector S1-A, S1-B need to connect to the side of S1 breaker.
- Connector S2-A, S2-B need to connect to the side of S2 breaker.
Fig. 1 Panel Instruction
CONNECTOR ILLUSTRATION
The pin numbers of connector terminals are as Fig. 2.
Fig. 2 Pin Numbers of Connector Terminals
Terminal Wirings of connector is as Table 3
Table 3 Connector Wiring Illustration
Connector No. | Pin No. | Wire No. | Wire Harness No. | Connector No. | Pin No. | Wire No. | Wire Harness No. |
M1 | 1 | M-15 | WH600-M-20-RM | S1-A | 1 | Q1-28 | WH600-Q1-30-RM |
2 | M-14 | 2 | Q1-2 | ||||
3 | M-13 | 3 | Q1-27 | ||||
4 | M-16 | 4 | Q1-33 | ||||
5 | NC | 5 | Q1-30 | ||||
6 | M-12 | 6 | Q1-36 | ||||
7 | M-17 | 7 | Q1-24 | ||||
8 | M-18 | 8 | Q1-35 | ||||
9 | M-11 | 9 | Q1-29 | ||||
M2 | 1 | M-4 | 10 | Q1-32 | |||
2 | M-28 | 11 | Q1-1 | ||||
3 | M-5 | 12 | Q1-25 | ||||
4 | M-8 | S1-B | 1 | NC | |||
5 | M-1 | 2 | Q1-4 | ||||
6 | M-9 | 3 | Q1-23 | ||||
7 | M-6 | 4 | NC | ||||
8 | M-27 | 5 | Q1-22 | ||||
9 | M-3 | 6 | Q1-5 | ||||
10 | M-10 | ||||||
11 | M-29 |
12 | NC | ||||||
13 | M-7 | ||||||
14 | M-2 | ||||||
15 | M-30 | ||||||
M3 |
1 | M-21 | |||||
2 | M-22 | ||||||
3 | NC | ||||||
4 | M-24 | ||||||
5 | M-19 | ||||||
6 | NC |
NOTE: Connector S2-A and S2-B connected wire number starts with Q2; Others are the same with S1-A, S1-B, connected with WH600-Q2-30-RM. For example: P1 wire number of connector S2-A is Q2-28.
Wire number definition:
APPLICATION DIAGRAM
Fig. 3 Application Diagram
ACCESSORY ILLUSTRATION
The connected wire harness and terminals matched with terminal block of this product are optional; Users can make clarification at ordering, note the harness requirements and breaker type. See Table 4 for details.
Table 4 Optional Accessory Description
Category |
Note |
Optional Wire Harness |
There are three in total, one of them will be connected to the controller side and the other two will be connected to the circuit breaker side. The length of the wire harness (unit: m) and the model of the circuit breaker should be indicated when choosing. |
Optional Terminals | Include the matching terminals and connector terminals. |
CASE DIMENSIONS
This adapter is designed by screw installation method, and is fixed by four screws at installation. Unit: mm
Fig. 4 Case Dimensions and Panel Cutout
Customer Support
No.28 Jinsuo Road, Zhengzhou, Henan Province, China
Tel: +86-371-67988888/67981888/67992951
+86-371-67981000(overseas)
Fax: +86-371-67992952
Email: sales@smartgen.cn
Web: www.smartgen.com.cn
www.smartgen.cn
Documents / Resources
![]() |
SmartGen ATA600 Dual Power Switch Adaptor [pdf] User Manual ATA600 Dual Power Switch Adaptor, ATA600, ATA600 Switch Adaptor, Dual Power Switch Adaptor, Power Switch Adaptor, Dual Power Switch, Adaptor, ATA600 Adaptor |