AIN16-C-2 Analog Input Module
User Manual
SmartGen — make your generator smart
SmartGen Technology Co., Ltd.
No.28 Xuemei Street, Zhengzhou, Henan, China
Tel: +86-371-67988888/67981888/67992951
+86-371-67981000(overseas)
Fax: +86-371-67992952
Email: sales@smartgen.cn
Web: www.smartgen.com.cn
www.smartgen.cn
All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder.
Applications for the copyright holder’s written permission to reproduce any part of this publication should be addressed to Smartgen Technology at the address above.
Any reference to trademarked product names used within this publication is owned by their respective companies.
SmartGen Technology reserves the right to change the contents of this document without prior notice.
Table 1 – Software Version
Date | Version | Content |
2021-09-10 | 1.0 | Original release. |
2022-11-16 | 1. | Update the logo of SmartGen. |
Table 2 – Notation Clarification
Symbol | Instruction |
![]() | Highlights an essential element of a procedure to ensure correctness. |
![]() | Indicates a procedure or practice, which, if not strictly observed, could result in damage or destruction of equipment. |
![]() | Indicates a procedure or practice, which could result in injury to personnel or loss of life if not followed correctly. |
OVERVIEW
AIN16-C-2 Analog Input Module is a module which has 16 channels of 4mA-20mA sensor input and 3 channels of speed sensor input. The 4mA-20mA data and speed data are transmitted to the master controller for processing via RS485 port. Different alarm threshold values can be set for each sensor via master controller.
PERFORMANCE AND CHARACTERISTICS
- With 32-bit ARM based SCM, high integration of hardware and more reliable;
- Must be used with master controller together;
- RS485 communication baud rate can be set as 9600bps or 19200bps via dial switch;
- Module address can be set as 1 or 2 via dial switch;
- Wide power supply range DC(18~35)V, suitable to different battery voltage environment;
- 35mm guide rail mounting type;
- Modular design, pluggable terminal, compact structure and easy installation.
TECHNICAL PARAMETERS
Table 3 – Technical Parameters
Item | Content |
Working Voltage Range | DC18.0V-35.0V |
Power Consumption | <0.5W |
Input Sensor Type | (4-20)mA Current Type |
Measurement Accuracy | Class 0.5 |
RS485 Communication Parameter | Baud rate: 9600bps, Stop bit: 2-bit, Data bit: 8-bit, Parity bit: no parity |
Case Dimension | 161.6mm x 89.7mm x 60.7mm |
Rail Dimension | 35mm |
Working Temperature | (-25—+70)°C |
Working Humidity | (20—’93)%RH |
Storage Temperature | (-30—+80)°C |
Weight | 0.33kg |
CONNECTION
Fig.1 – AIN16-C-2 Panel Drawing
Table 4 – Terminal Connection
No. | Function | Cable Size | Description |
1 | B- | 1.0mm2 | DC power supply negative input. |
2 | B+ | 1.0mm2 | DC power supply positive input. |
3 | NC | No Contact. | |
4 | 1200 Terminal Matched Resistance | 0.5mm2 | Short connect Terminal 4 and Terminal 5 if the matched resistance is required. |
5 | A(+) | 0.5mm2 | The RS485 port for communication with master controller. |
6 | B(-) | ||
7 | MP1(-) | 0.5mm2 | Connect with speed sensor (shielded wire is recommended). Speed sensor input (-), B- has been connected in the controller. |
8 | MP1(+) | 0.5mm2 | |
9 | MP2(-) | 0.5mm2 | Connect with speed sensor (shielded wire is recommended). Speed sensor input (-), B- has been connected in the controller. |
10 | MP2(+) | 0.5mm2 | |
11 | MP3(-) | 0.5mm2 | Connect with speed sensor (shielded wire is recommended). Speed sensor input (-), B- has been connected in the controller. |
12 | MP3(+) | 0.5mm2 | |
13 | AIN16(mA) | 0.5mm2 | (4-20)mA analog input. |
SYMPTOMS | POSSIBLE CAUSES | COMMENTS |
• Noisy Pump | – Seized pump. – No water in the network. – Obstruction in water supply. | – If the water has particles suspended in it or is too hard, you should install a water softener filter. |
• Slow dispensing, burnt coffee. | – Incorrect calibration of the pump. Pump with reduced draught | – Check the pump pressure with a gauge. |
• Slow dispensing. • Burnt and cold coffee. • Dark cream with a tendency to be porous. • Continuous coffee dispensing suddenly stops and the ‘no water indicator blinks. • One-coffee and two-coffee lights blinking. | – Grinding point too fine. – Low pump pressure. – Injector filter dirty, partially obstructed. – Low water level in reservoir – Volume counter does not work correctly. – Coffee is excessively fine or there is no water. | – If they are blinking and to know whether it is due to the coffee, or due to a lack of water or due to the volume counter, take out the filter holder and press the button. If the blinking continues and water has come out, it may be due to the volume counter. |
• Electronic machines: One-coffee, two-coffee keys and LED level indicator blinking. • Semi-automatic machines: Boiler Water Level indicator is blinking. | – Boiler Water Level alarm has been activated. | – Check that the main water valve is open or that there is water in the internal tank (according to version). The warning will disappear once the machine is turned off and tumed on again. |
No. | Function | Cable Size | Description |
41 | AIN11(Com(B+)) | 0.5mm2 | B+ voltage output (provide power supply for pressure transmitter). |
42 | AIN11(mA) | (4-20)mA analog input. | |
43 | AIN12(Com(B+)) | 0.5mm2 | B+ voltage output (provide power supply for pressure transmitter). |
44 | AIN12(mA) | (4-20)mA analog input. | |
SWITCH | Address selection: It is module 1 when the switch 1 is connected to terminal 12 while module 2 when connect to ON terminal. Baud rate selection: It is 9600bps when the switch 2 is connected to terminal 12 while 19200bps when connect to ON terminal. | ||
POWER | Power supply and communication normal indicator; It is flashing when the communication is abnormal, it is always illuminated when communication is normal. | ||
LINK | System upgrade port; modify the default parameters. |
TYPICAL APPLICATION
CASE DIMENSIONS
TROUBLE SHOOTING
Problem | Possible Solution |
Controller no response power | Check starting batteries; Check controller connection wirings; |
RS485 communication failure | Check if RS485 wires are connected correctly; Check if 1200 resistance is connected; Check if the baud rate and stop-bit of master controller are correct. |
Documents / Resources
![]() | SmartGen AIN16-C-2 Analog Input Module [pdf] User Manual AIN16-C-2, Analog Input Module, AIN16-C-2 Analog Input Module, Input Module, Module |