Panel layout may vary with options. Reg. Cdn Pat. & TM Off C-Level™ Sensor US Patent No. 8,336,385; 8,567,242; 8,650,949.
The IFS simplex control panel utilizes an innovative circuit board design to control one 208/240/480 VAC three phase pump in water and sewage applications. IFS panels feature an easy-to-use touch pad on inner door for programming and system monitoring.
The panel configuration can be easily converted in the field to either a timed dose or demand dose. Available with the Essonne ® float system. The panel can utilize the C-Level™ sensor for continuous level monitoring. It senses the level in the tank and sends a signal to the panel. Pump activation levels can be adjusted by using the panel touch pad. C-Level™ CL40 sensor operating range is 3-39.9 inches (7.6-101.3 cm). C-Level™ CL100 operating range is 3-99.5 inches (7.6-252.7 cm).

TOUCH PAD FEATURES

A. Level Status indicators illuminate when floats or set points are activated; alarm will activate if a float operates out of sequence
B. HOA (Hand-Off-Automatic) buttons control pump mode with indication; Hand mode defaults to Automatic when stop level or redundant off level is reached
C. Pump Run indicator will illuminate when pumps are called to run
D. LED Display for system information including: level in inches or centimeters (C-Level™ only), mode, pumps elapsed time (ham), events (cycles), alarm counter, float error count, timed dose override counter (timed dose only), and ON/OFF times (timed dose only)
E. NEXT push button toggles display
F. UP and SET push buttons set pump ON/OFF times (timed dose only) and activation levels (C-Level™ only)

COMPONENTS

  1. Enclosure base measures 14 x 12 x 6 inches (35.56 x 30.48 x 15.24 cm); NEMA 4X (ultraviolet stabilized thermoplastic with removable mounting feet for outdoor or indoor use)
  2. Red LED beacon provides 360° visual check of alarm condition
  3. Exterior Alarm Test/Normal/Silence switch allows horn and light to be tested and horn to be silenced in an alarm condition; alarm automatically resets once alarm condition is cleared
  4. Motor protective switch provides adjustable overload, branch circuit protection and pump disconnect
  5. IEC motor contactor controls pump by switching electrical lines
  6. Multi-tap transformer (208/240/480 VAC primary) provides 120 VAC control alarm voltage or 600 VAC primary transformer
  7. Float connection terminal block
  8. Control Power indicator/fuse indicator light illuminates if control power is present in panel; alarm will activate if control fuse is blown
  9. Alarm Power indicator/fuse indicator light illuminates if alarm power is present in panel
  10. Large incoming power connection terminal block
  11. Terminal block float wiring label
  12. Ground lugs
  13. Alarm horn provides audio warning of alarm condition (83 to 85 decibel rating) (Not shown)

Note: Options, voltage, and amp range selected may change enclosure size and component layout.
Note: Schematic/Wiring Diagram and Pump Specification Label are located inside the panel.
INSTALLER FRIENDLY SERIES®THREE PHASE SIMPLEX – Demand or timed dose float controlled system for pump control and system monitoring.

IFS 5 1 W 8AC
CONTROL  PANEL MODEL TYPE ALARM PACKAGE ENCLOSURE RATING PUMP FULL LOAD AMPS FLOAT SWITCH APPLICATION OPTIONS (LISTED BELOW)
CONTROL PANEL IFS
MODEL TYPE 5 Three Phase Simplex (includes Option 8AC as standard)
ALARM PACKAGE 1 Alarm Package (includes test/normal/silence switch, fuse, red light, & horn)
ENCLOSURE RATING W Weatherproof, NEMA 4X (engineered thermoplastic)
PUMP FULL LOAD AMPS 208/240/480V 600V
001 1.0 – 1.6 FLA 005 1.0 – 1.6 FLA
101 1.6 – 2.5 FLA 105 1.6 – 2.5 FLA
201 2.5 – 4.0 FLA 205 2.5 – 4.0 FLA
301 4.0 – 6.3 FLA 305 4.0 – 6.3 FLA
401 6.0 – 10.0 FLA 405 6.0 – 10.0 FLA
511 9.0 – 14.0 FLA 515 9.0 – 14.0 FLA
611 13.0 – 18.0 FLA 615 13.0 – 18.0 FLA
621 17.0 – 23.0 FLA 625 17.0 – 23.0 FLA
701 20.0 – 25.0 FLA 705 20.0 – 25.0 FLA
FLOAT SWITCH APPLICATION H Floats – Pump Down (select Option 17 below)
E Essonne® Float Switch System (select Option 33 or 34 below)
X No Floats
C C-Level™ Sensor (select Option 24 or 29) Select Option 3E and/or 4A & 4D for high water alarm and/or redundant off floats

NOTE: Pump down applications only. Industry practices suggest that a secondary device, such as a float switch, be used for redundant activation of the high level alarm and pump shut off when using the C-Level™ sensor.

PRICING WORK SHEET

IFS Three Phase, Simplex Base Price………..
Alarm Package…………………………………………..
Enclosure Rating………………………………………
Pump Full Load Amps……………………………
Float Switch Application………………………….
Total Options………………………………………..
TOTAL LIST PRICE…………………………..

OPTIONS DESCRIPTION OPTIONS DESCRIPTION
3A Alarm Flasher 17C Sensor Float® / Internally Weighted (per Float) – Mercury
3B Manual Alarm Reset 17D Sensor Float® / Externally Weighted (per Float) – Mercury
3E High Water Alarm Float (must also select Option 17)
Only Available with Float Switch Application = C
17G SJE MilliAmpMaster™ / Pipe Clamp (per Float) – Mechanical
17H SJE MilliAmpMaster™ / Externally Weighted (per Float) – Mechanical
4A Redundant Off (must also select Option 4D if floats are required) 17J Sensor Float® / Pipe Clamp (per Float) – Mercury
4D Redundant Off Float (must also select Option 4A and Option 17) 24E C-Level™ CL40 Sensor with 4’ Vent Tube and 20’ Cord
5A Thermal Cutout/Heat Sensor Auto Reset (for pumps with thermal switch leads) 24F C-Level™ CL40 Sensor with 4’ Vent Tube and 40’ Cord
24G C-Level™ CL40 Sensor with 8’ Vent Tube and 20’ Cord
5E Seal Failure Circuit and Red Indicator (2 Wire) 24H C-Level™ CL40 Sensor with 8’ Vent Tube and 40’ Cord
6A Auxiliary Alarm Contact, Form C 24X No C-Level™ CL40 Sensor
8AC Display Board – Includes: ETM Counter, Events (Cycles) Counter, Alarm Counter (included as standard) 29A C-Level™ CL100 Sensor with 10’ Vent Tube and 20’ Cord
29B C-Level™ CL100 Sensor with 10’ Vent Tube and 40’ Cord
10E Lockable Latch – NEMA 4X 29X No C-Level™ CL100 Sensor
10G Lightning Arrestor 33D ■ Essonne® 3-Port, 25’, with 10’ Floats (3) / Pipe Clamp
10K Anti-condensation Heater 33E ■ Essonne® 3-Port, 50’, with 10’ Floats (3) / Pipe Clamp
11C Additional NEMA 1 Remote Alarm Panel (must also select Option 6A) 33G ■ Essonne® 3-Port, 25’, with 20’ Floats (3) / Pipe Clamp
11D Additional NEMA 4X Remote Alarm Panel (must also select Option 6A) 33H ■ Essonne® 3-Port, 50’, with 20’ Floats (3) / Pipe Clamp
16A 10’ Cord in Lieu of 20’ Cord (per Float) 34D ■ Essonne® 4-Port, 25’, with 10’ Floats (3) / Pipe Clamp, Sealing Plug
16B 15’ Cord in Lieu of 20’ Cord (per Float) 34E ■ Essonne® 4-Port, 50’, with 10’ Floats (3) / Pipe Clamp, Sealing Plug
16C 30’ Cord in Lieu of 20’ Cord (per Float 34G ■ Essonne® 4-Port, 25’, with 20’ Floats (3) / Pipe Clamp, Sealing Plug
16D 40’ Cord in Lieu of 20’ Cord (per Float) 34H ■ Essonne® 4-Port, 50’, with 20’ Floats (3) / Pipe Clamp, Sealing Plug

 Essonne® mechanically-activated, narrow angle float switches with quick release connections

SJE RHOMBUS LOGOwww.sjerhombus.com
email:customer.service@sjeinc.com
SEE PRICE BOOK FOR PRICING
9500055I Rev 05/21
© 2020 SJE, Inc. All Rights Reserved.
SJE Rhombus is a trademark of SJE, Inc.
www.sjerhombus.com
Toll Free 888-342-5753
SJE RHOMBUS Friendly Series IFS Three Phase Simplex Control Panel - Icon

Documents / Resources

SJE RHOMBUS Friendly Series IFS Three Phase Simplex Control Panel [pdf] Instruction Manual
Friendly Series IFS Three Phase Simplex Control Panel, IFS Three Phase Simplex Control Panel, Three Phase Simplex Control Panel, Simplex Control Panel

References

Leave a comment

Your email address will not be published. Required fields are marked *