4010 Fire Alarm Control Panel
Product Information
Specifications
- Product Name: 4010 Fire Alarm Front Panel
- Model Number: 574-052 Rev. E
- Country of Origin: United States of America
- Listing Categories: UL 864, Factory Mutual Approved, Local
Approvals - California State Fire Marshal Approval: Yes, CSFM Listing No.
7170-0026:226
Product Usage Instructions
Installation
1. Carefully unpack the product and inspect for any shipping
damage.
2. Follow the installation manual provided with the product for
proper installation guidelines.
3. Ensure proper electrical connections and power off when
making any internal adjustments.
Operation
1. Familiarize yourself with the operating manual for the Fire
Alarm Control Panel (FACP).
2. Follow the instructions provided to ensure proper system
operation.
Programming
1. Refer to the programming manual for detailed instructions on
programming the panel.
2. Perform system reacceptance testing as per NFPA72-1996,
Chapter 7 after any software changes.
FAQ
Q: What should I do if I notice shipping damage on my Simplex
product?
A: Immediately file a claim with the carrier and notify Simplex
about the damage.
Q: How can I ensure proper system operation after software
changes?
A: Perform system reacceptance testing as per NFPA72-1996
guidelines, testing all affected components and a portion of
unaffected initiating devices.
4010 Fire Alarm Front Panel Installing, Operating, and
Programming Instructions
574-052 Rev. E
This page intentionally blank
Copyright and Trademarks
Copyright © Simplex Time Recorder Co., 2000. All rights reserved.
Printed in the United States of America.
Information in this document is subject to change without notice. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written consent of Simplex Time Recorder Company.
Walk TestTM is protected by US Patent No. 4,725,818. MAPNET addressable communications is protected by US Patent No.4,796,025. IDNetTM is patent pending. TrueAlarm® Analog Detection is protected by US Patent No. 5,155,468. TrueAlarm® Detector Base is protected by US Patent No. 5,173, 683.
Cautions and Warnings
SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES – To ensure proper system operation, this product must be tested in accordance with NFPA72-1996, Chapter 7 after any programming operation or change in sitespecific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
READ AND SAVE THESE INSTRUCTIONS. Follow the instructions in the installation, operating and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. Fire Alarm Control Panel (FACP) operation and reliability depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify Simplex.
ELECTRICAL HAZARD – Disconnect electrical power when making any internal adjustments or repairs. Servicing should be performed by qualified Simplex Representatives.
RADIO FREQUENCY ENERGY – This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area may cause interference in which case the user at his own expense will be required to take whatever measures may be required to correct the interference.
i
This page intentionally blank. ii
Codes and Standards
The 4010 is listed for the following listing categories.
UL 864 Listings for Type of System:
· UL 864 Power-Limited Fire Alarm Control Unit
· Local (formerly NFPA 72A) Requires the sounding of an alarm via listed notification appliance(s)
· Auxiliary (formerly NFPA 72B) Requires 4010-9809 City Circuit Module
· Remote Station – protected premise (formerly NFPA 72C) Requires 4010-9809 City Circuit Module or the 4010-9810 or -9816 DACT
· Proprietary – protected premise (formerly NFPA 72D) Requires 4010-9817 (with 4010-9818 or 4010-9819) or 4010-9821 Network Interface Modules
· Central Station – protected premise (formerly NFPA 71) Requires 4010-9810 or -9816 DACT
· Suppression Releasing Service Requires 4010-9814 Suppression Kit
UL 864 Listings for Type of Service:
· Automatic, Manual, Waterflow, and Sprinkler Supervisory
UL 864 Listings for Type of Signaling:
· Coded, Non-Coded, March-Time and DACT Requires the 4010-9810 or -9816 DACT
Factory Mutual Approved:
· Same as UL above
Local Approvals:
· CSFM* · MEA · City of Chicago (pending)
*This product has been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing No. 7170-0026:226 for allowable values and/or conditions for use concerning material presented in this document.
iii
Codes and Standards (continued)
About this Manual
The installer should be familiar with the relevant codes listed below as well as any other applicable local codes and standards, when installing a fire alarm system.
· NFPA 72 National Fire Alarm Code · NFPA 11 Standard for Low-Expansion Foam and Combined Agent
Systems · NFPA 11A Standard for Medium- and High-Expansion Foam Systems · NFPA 12 Standard on Carbon Dioxide Extinguishing Systems · NFPA 12A Standard on Halon 1301 Fire Extinguishing Systems · NFPA 13 Standard for the Installation of Sprinkler Systems · NFPA 14 Standard for the Installation of Standpipe and Hose Systems · NFPA 15 Standard for Water Spray Fixed Systems for Fire Protection · NFPA 16 Standard for the Installation of Deluge Foam-Water Sprinkler
and Foam-Water Spray Systems · NFPA 16A Standard for the Installation of Closed-Head Foam-Water
Sprinkler Systems · NFPA 17 Standard for Dry Chemical Extinguishing Systems · NFPA 17A Standard for Wet Chemical Extinguishing Systems · NFPA 25 Standard for Inspection, Testing, and Maintenance of
Water-Based Fire Protection Systems · NFPA 70 National Electrical Code · NFPA 80 Standard for Fire Doors and Fire Windows · NFPA 90A Standard for the Installation of Air Conditioning and
Ventilation Systems · NFPA 90B Standard for the Installation of Warm Air Heating and Air
Conditioning Systems · NFPA 92A Recommended Practice for Smoke-Control Systems · NFPA 92B Guide for Smoke Management Systems in Malls, Atria, and
Large Areas · NFPA 101 Life Safety Code · NFPA 170 Standard for Fire Safety Symbols · NFPA 231C Standard for Rack Storage of Materials · NFPA 1221 Standard on the Installation, Maintenance, and Use of Public
Fire Service Communication Systems
The following conventions are used in this publication to identify special names or text.
· When a membrane panel key (located below the display) is referenced in this manual, it is normally shown between left and right arrows. Examples are <ALARM SILENCE> and <SYSTEM RESET>.
· Text enclosed in quotation marks indicates the title of a chapter or section of the manual, such as “About this Manual.”
· Bulleted lists, such as this one, provide you with information. They are also used to indicate alternatives in numbered procedural steps.
· Numbered lists indicate procedures with steps that you must carry out sequentially.
iv
Table of Contents
Chapter 1. 4010 FACP Overview
Introduction………………………………………………………………………………….. 1-1 In this Chapter………………………………………………………………………………. 1-1
Related Documentation……………………………………………………………………… 1-2
Base System Module…………………………………………………………………………. 1-3 Overview……………………………………………………………………………………… 1-3 SFI/O…………………………………………………………………………………………… 1-3 Power Supply Base System………………………………………………………….. 1-4 Default Settings…………………………………………………………………………….. 1-4 Environmental Specifications …………………………………………………………. 1-4
Optional System Modules ………………………………………………………………….. 1-5 Overview……………………………………………………………………………………… 1-5 Optional Modules with Dedicated Hardware Slots …………………………….. 1-5 Optional Modules for Expansion Slots …………………………………………….. 1-6 Remote Optional Modules ……………………………………………………………… 1-7 Other Compatible Equipment………………………………………………………….. 1-8
User Interface…………………………………………………………………………………… 1-9 Overview……………………………………………………………………………………… 1-9 Operator Key Definitions……………………………………………………………….. 1-9 Menu Navigation Key Definitions …………………………………………………. 1-10
Passcodes, Access Levels, and Logging In and Out……………………………… 1-12 Overview……………………………………………………………………………………. 1-12 Passcodes and Access Levels………………………………………………………… 1-12 Logging In and Out ……………………………………………………………………… 1-13
Menu Structure……………………………………………………………………………….. 1-14
Chapter 2. Back Box Installation
Overview……………………………………………………………………………………… 2-1 In this Chapter………………………………………………………………………………. 2-1
Before You Begin …………………………………………………………………………….. 2-2 Unpacking the System……………………………………………………………………. 2-2 Installation Guidelines …………………………………………………………………… 2-2 Standards and Codes ……………………………………………………………………… 2-2
Remove Chassis and Cut Conduit Openings…………………………………………. 2-3 Overview……………………………………………………………………………………… 2-3 Step 1. Remove the Chassis …………………………………………………………… 2-3 Step 2. Cut Conduit Entrances ……………………………………………………….. 2-3
Mount the Backbox…………………………………………………………………………… 2-4 Surface Mounting the Back Box ……………………………………………………… 2-4 Semi-Flush Mounting the Back Box ………………………………………………… 2-4
Re-install the Chassis ………………………………………………………………………… 2-5 Procedure …………………………………………………………………………………….. 2-5
v
Chapter 3. Wiring
Overview……………………………………………………………………………………… 3-1 In this Chapter………………………………………………………………………………. 3-1
Overview…………………………………………………………………………………………. 3-2 Power Limited Versus Non-Power Limited Systems ………………………….. 3-2 Locations of Terminal Connections …………………………………………………. 3-3
NAC Wiring…………………………………………………………………………………….. 3-4 Overview……………………………………………………………………………………… 3-4 Terminal Connections ……………………………………………………………………. 3-4
IDNet Wiring …………………………………………………………………………………… 3-5 Overview……………………………………………………………………………………… 3-5 Terminal Connections ……………………………………………………………………. 3-5
AC Power and Battery Wiring ……………………………………………………………. 3-6 AC Power…………………………………………………………………………………….. 3-6 Installing and Connecting Batteries …………………………………………………. 3-7
Auxiliary Relays……………………………………………………………………………….. 3-9 Auxiliary Relays……………………………………………………………………………. 3-9
System Power-Up and Checkout……………………………………………………….. 3-10 Connect AC & Battery Power ……………………………………………………….. 3-10 Power-Up and Checkout ………………………………………………………………. 3-10 Acceptance Test ………………………………………………………………………….. 3-12
Periodic Testing and Maintenance …………………………………………………….. 3-13 Overview……………………………………………………………………………………. 3-13 Battery Testing Information ………………………………………………………….. 3-13
Chapter 4. Quick CFIG
Overview……………………………………………………………………………………… 4-1 Cautions and Warnings ………………………………………………………………….. 4-1 In this Chapter………………………………………………………………………………. 4-1
Reconfigure ALL Hardware……………………………………………………………….. 4-2 Overview……………………………………………………………………………………… 4-2 Procedure …………………………………………………………………………………….. 4-2
Auto Detect NEW Hardware ……………………………………………………………… 4-3 Overview……………………………………………………………………………………… 4-3 Procedure …………………………………………………………………………………….. 4-3
Restore Factory CFIG ……………………………………………………………………….. 4-4 Overview……………………………………………………………………………………… 4-4 Procedure …………………………………………………………………………………….. 4-4
Accept Default Settings for System Options…………………………………………. 4-5 Procedure …………………………………………………………………………………….. 4-5
Edit Settings for System Options ………………………………………………………… 4-6 Overview……………………………………………………………………………………… 4-6 Procedure …………………………………………………………………………………….. 4-6
Save CFIG Option…………………………………………………………………………….. 4-8 Overview……………………………………………………………………………………… 4-8
vi
Chapter 5. Configuring Cards
Overview……………………………………………………………………………………… 5-1 In this Chapter………………………………………………………………………………. 5-1
Card Addresses ………………………………………………………………………………… 5-2 Card Addresses …………………………………………………………………………….. 5-2
Adding, Deleting, or Modifying 4010 Cards ………………………………………… 5-3 Overview……………………………………………………………………………………… 5-3 Adding a Card ………………………………………………………………………………. 5-3 Deleting a Card …………………………………………………………………………….. 5-4 Modifying a Card ………………………………………………………………………….. 5-5
Chapter 6. Configuring Points
Overview……………………………………………………………………………………… 6-1 In this Chapter………………………………………………………………………………. 6-1
Configure Points Menu ……………………………………………………………………… 6-2 Configuring Points Menu ……………………………………………………………….. 6-2
Configuring TrueAlarm Points……………………………………………………………. 6-3 Overview……………………………………………………………………………………… 6-3 Add IDNet Point …………………………………………………………………………… 6-3 Edit TrueAlarm Point…………………………………………………………………….. 6-3 Delete TrueAlarm Point …………………………………………………………………. 6-4
Configuring ZAM/IAM/RIAM Points …………………………………………………. 6-6 Overview……………………………………………………………………………………… 6-6 Adding ZAM/IAM/RIAM Point ……………………………………………………… 6-6 Editing a ZAM/IAM/RIAM Point……………………………………………………. 6-6 Deleting ZAM/IAM/RIAM IDNet Point…………………………………………… 6-8
Configuring Relay and NAC Points …………………………………………………….. 6-9 Overview……………………………………………………………………………………… 6-9 Procedure …………………………………………………………………………………….. 6-9
Configuring Digital and Analog Pseudo Points …………………………………… 6-11 Overview……………………………………………………………………………………. 6-11 Configuring Digital Pseudo Points…………………………………………………. 6-11 Configuring Analog Pseudo Points ………………………………………………… 6-12
Configuring 24-Point I/O Points ……………………………………………………….. 6-14 Overview……………………………………………………………………………………. 6-14 Configuring 24-Point Input Points …………………………………………………. 6-14 Configuring 24-Point Output Points……………………………………………….. 6-16
Configuring List Points ……………………………………………………………………. 6-18 Overview……………………………………………………………………………………. 6-18 Configure a List ………………………………………………………………………….. 6-18 Add a Point to a List ……………………………………………………………………. 6-19 Delete a Point from a List …………………………………………………………….. 6-19 Delete ALL Points from a List ………………………………………………………. 6-20
Configuring User-Defined SW/LED………………………………………………….. 6-21 Overview……………………………………………………………………………………. 6-21 Configure a User-Defined Switch or LED ………………………………………. 6-21 Edit a Mode of a User-Defined SW/LED ……………………………………….. 6-22
vii
Chapter 7. System Options
Overview……………………………………………………………………………………… 7-1 In this Chapter………………………………………………………………………………. 7-1
System Options Menu ……………………………………………………………………….. 7-2 Introduction………………………………………………………………………………….. 7-2
Time/Date Format…………………………………………………………………………….. 7-3 Overview……………………………………………………………………………………… 7-3 Setting the Time Format…………………………………………………………………. 7-3
Active Status Reminder……………………………………………………………………… 7-4 Overview……………………………………………………………………………………… 7-4 Setting the Active Status Reminder………………………………………………….. 7-4
Silence/Reset Inhibit …………………………………………………………………………. 7-5 Overview……………………………………………………………………………………… 7-5 Setting the Silence/Reset Inhibit ……………………………………………………… 7-5
Alarm Cut-Out Timer………………………………………………………………………… 7-6 Overview……………………………………………………………………………………… 7-6 Setting the Alarm Cut-Out Timer…………………………………………………….. 7-6
Door Drop on Alarm…………………………………………………………………………. 7-7 Overview……………………………………………………………………………………… 7-7 Setting the Door Drop on Alarm Timer ……………………………………………. 7-7
Door Drop on AC Loss ……………………………………………………………………… 7-8 Overview……………………………………………………………………………………… 7-8 Setting the Door Drop on AC Loss Timer ………………………………………… 7-8
Audible and Visible NAC Operation …………………………………………………… 7-9 Overview……………………………………………………………………………………… 7-9 Setting the Audible or Visual NAC Operation…………………………………… 7-9
QuickAlert Horn Operation ……………………………………………………………… 7-10 Introduction………………………………………………………………………………… 7-10 Setting the QuickAlert Horn Option ………………………………………………. 7-10
Depleted Battery Cut-Out ………………………………………………………………… 7-11 Overview……………………………………………………………………………………. 7-11 Setting the Depleted Battery Cut-Out …………………………………………….. 7-11
Stagger Start AHUs…………………………………………………………………………. 7-12 Overview……………………………………………………………………………………. 7-12 Setting the Stagger Start AHU Delay Timer ……………………………………. 7-12
Enable City Circuit………………………………………………………………………….. 7-13 Overview……………………………………………………………………………………. 7-13 Setting the Enable City Circuit Option……………………………………………. 7-13
Expansion Power ……………………………………………………………………………. 7-14 Overview……………………………………………………………………………………. 7-14 Setting the Expansion Power Option………………………………………………. 7-14
Single-Station…………………………………………………………………………………. 7-15 Overview……………………………………………………………………………………. 7-15 Enabling Single-Station ……………………………………………………………….. 7-15
viii
Suppression Release………………………………………………………………………… 7-16 Overview……………………………………………………………………………………. 7-16 Example …………………………………………………………………………………….. 7-16 Step 1. Turn ON Suppression Release …………………………………………… 7-17 Step 2. Assign Suppression Monitor Point Types to Suppression Release Monitor Points…………………………………………………….. 7-17 Step 3. Create Suppression Release Monitor Lists…………………………… 7-17 Step 4. Assign Point Types to Suppression Outputs ………………………… 7-18 Step 5. Create Suppression Release Output Lists…………………………….. 7-18
Chapter 8. Custom Control
Introduction………………………………………………………………………………….. 8-1 In this Chapter………………………………………………………………………………. 8-1
Overview…………………………………………………………………………………………. 8-2 Introduction………………………………………………………………………………….. 8-2
SMPL Opcodes and Operators……………………………………………………………. 8-3 Input Opcodes ………………………………………………………………………………. 8-3 Input and Relational Operators ……………………………………………………….. 8-4 Output Opcodes ……………………………………………………………………………. 8-5
Custom Control Equation…………………………………………………………………… 8-6 Custom Control Example ……………………………………………………………….. 8-6
Custom Control Programming ……………………………………………………………. 8-7 To Start Custom Control Programming ……………………………………………. 8-7 Custom Control Menu Navigation …………………………………………………… 8-8 Equation Level ……………………………………………………………………………… 8-9 Custom Control Level ……………………………………………………………………. 8-9 Equations …………………………………………………………………………………… 8-10 Input Side (IF)…………………………………………………………………………….. 8-10 Field 1 ……………………………………………………………………………………….. 8-10 Field 2 ……………………………………………………………………………………….. 8-15 Fields 3 & 4………………………………………………………………………………… 8-16 Output Side (THEN) ……………………………………………………………………. 8-24
Application-Specific Examples…………………………………………………………. 8-26 Introduction………………………………………………………………………………… 8-26 Day Night Programming Example …………………………………………………. 8-26 TrueAlarm Heat Utility Monitoring Example ………………………………….. 8-26 City Circuit Alarm-Output Programming Example…………………………… 8-26 AHJ City Circuit Reset Operation Example…………………………………….. 8-27
Chapter 9. Saving a CFIG
Introduction………………………………………………………………………………….. 9-1 In this Chapter………………………………………………………………………………. 9-1
Viewing CFIG Properties…………………………………………………………………… 9-2 Introduction………………………………………………………………………………….. 9-2 Procedure …………………………………………………………………………………….. 9-2
Continue, Restore CFIG, and Save CFIG …………………………………………….. 9-3 Continue………………………………………………………………………………………. 9-3 Restore CFIG ……………………………………………………………………………….. 9-3 Save CFIG……………………………………………………………………………………. 9-3
ix
Chapter 10. Diagnostics and Troubleshooting
Overview……………………………………………………………………………………. 10-1 Before Calling Tech Support ………………………………………………………… 10-1
Diagnostics…………………………………………………………………………………….. 10-2 Overview……………………………………………………………………………………. 10-2 Running Diagnostics ……………………………………………………………………. 10-2 Diagnostic Options………………………………………………………………………. 10-3 N2 Comm Diagnostics …………………………………………………………………. 10-3 IDNet Diagnostics……………………………………………………………………….. 10-3 IDNet Earth Fault Search Diagnostics ……………………………………………. 10-4 Network Diagnostics……………………………………………………………………. 10-4
Walk Test………………………………………………………………………………………. 10-6 Overview……………………………………………………………………………………. 10-6 Using Walk Test …………………………………………………………………………. 10-6
TrueTest………………………………………………………………………………………… 10-8 Overview……………………………………………………………………………………. 10-8 Using TrueTest …………………………………………………………………………… 10-9
Crash Codes …………………………………………………………………………………. 10-10
Chapter 11. Operation
Overview……………………………………………………………………………………. 11-1 In this Chapter…………………………………………………………………………….. 11-1
Handling Abnormal Conditions ………………………………………………………… 11-2 Normal Operation ……………………………………………………………………….. 11-2 Abnormal Conditions …………………………………………………………………… 11-2 Acknowledging an Alarm, Trouble, or Supervisory Condition…………… 11-3 Silencing Alarms…………………………………………………………………………. 11-3 Resetting the System ……………………………………………………………………. 11-4
Viewing and Clearing Historical Logs ……………………………………………….. 11-5 Overview……………………………………………………………………………………. 11-5 Using the Historical Logs……………………………………………………………… 11-6
Viewing and Controlling Points………………………………………………………… 11-7 Overview……………………………………………………………………………………. 11-7 Controlling/Viewing Points…………………………………………………………… 11-7 How to Disable/Enable Points ………………………………………………………. 11-9 How to Disable Points in Alarm ……………………………………………………. 11-9
Editing Custom Labels…………………………………………………………………… 11-10 How to Edit a Custom Label ……………………………………………………….. 11-10
User Control Functions ………………………………………………………………….. 11-12 Overview………………………………………………………………………………….. 11-12 Using the Function Options…………………………………………………………. 11-12
Setting the Time and Date………………………………………………………………. 11-14
x
Appendix A. Device and Point Types
Overview…………………………………………………………………………………….. A-1 In this Chapter……………………………………………………………………………… A-1
Hardware Device Types……………………………………………………………………. A-2 Overview…………………………………………………………………………………….. A-2 TrueAlarm Hardware Device Types ……………………………………………….. A-2 TrueAlarm Levels and Sensitivities ………………………………………………… A-3 Monitor Hardware Device Types……………………………………………………. A-3 4009A Hardware Device Types ……………………………………………………… A-4
Software Point Types ……………………………………………………………………….. A-5 Monitor Point Types …………………………………………………………………….. A-5 Signal Point Types ……………………………………………………………………….. A-6 Relay Point Types ………………………………………………………………………… A-7 QuickAlert Point Types ………………………………………………………………… A-8
Appendix B. Hardware and Pseudo Points
Overview…………………………………………………………………………………….. B-1 In this Chapter……………………………………………………………………………… B-1
Hardware Points………………………………………………………………………………. B-2 Introduction…………………………………………………………………………………. B-2 General Card Status Point Information ……………………………………………. B-2 Master Controller Card …………………………………………………………………. B-2 Master Controller Card Status Points………………………………………………. B-2 Master Controller Points ……………………………………………………………….. B-2 NAC Card …………………………………………………………………………………… B-3 NAC Card Status Points………………………………………………………………… B-3 NAC Card Points …………………………………………………………………………. B-4 Power Supply Card ………………………………………………………………………. B-5 Power Supply Card Status Points……………………………………………………. B-5 Power Supply Points …………………………………………………………………….. B-5 IDNet Card………………………………………………………………………………….. B-6 IDNet Card Status Points ………………………………………………………………. B-6 IDNet Points ……………………………………………………………………………….. B-7 RS232/Modem Card …………………………………………………………………….. B-8 RS232/Modem Card Status Points………………………………………………….. B-8 RS232/Modem Points …………………………………………………………………… B-8 DACT Card…………………………………………………………………………………. B-9 DACT Card Status Points ……………………………………………………………… B-9 SDACT Points …………………………………………………………………………….. B-9 Network Card…………………………………………………………………………….. B-10 Network Card Status Points …………………………………………………………. B-10 Network Points…………………………………………………………………………… B-10 24I/O Card ………………………………………………………………………………… B-11 24I/O Card Status Points……………………………………………………………… B-11 24I/O Points ………………………………………………………………………………. B-12 LCD Card………………………………………………………………………………….. B-12 LCD Card Status Points ………………………………………………………………. B-12 LCD Points ……………………………………………………………………………….. B-13
Pseudo Points………………………………………………………………………………… B-14 Introduction……………………………………………………………………………….. B-14 Digital Pseudo Points………………………………………………………………….. B-14 4010 System Digital Pseudos……………………………………………………….. B-15
xi
4010 User Digital Pseudos…………………………………………………………… B-17 Analog Pseudo Points …………………………………………………………………. B-18 4010 System Analog Pseudos ………………………………………………………. B-18 4010 User Analog Pseudos ………………………………………………………….. B-18 List Pseudo Points………………………………………………………………………. B-19 4010 System Lists ………………………………………………………………………. B-19 4010 User Lists ………………………………………………………………………….. B-20
Appendix C. Glossary of Terms
Overview………………………………………………………………………………………C-1 Glossary ……………………………………………………………………………………….C-1
Index ……………………………………………………………………. IN-1
xii
Overview
Introduction In this Chapter
Chapter 1 4010 FACP Overview
The 4010 is a single-channel, addressable, modular Fire Alarm Control Panel (FACP) that monitors and controls up to 250 IDNet addressable devices. The Standard Function Input/Output (SFI/O) card, power supply, and cabinet provide a complete fire alarm control panel for most applications. Optional modules mount to the chassis to provide additional inputs and outputs, network communication, and additional power. Additionally, the 4010 can automatically control supplementary equipment such as fire doors and fans during an alarm condition using its auxiliary relay outputs.
The 4010 provides audible and visible indications during trouble, supervisory, or alarm (fire) conditions. Should any of these conditions occur, the system activates the applicable notification appliance(s), LEDs, and the panel tone-alert. The indications continue until someone appropriately acknowledges the condition.
This publication describes how to install, configure, operate, program, and test the Simplex 4010 Fire Alarm Control Panel (FACP).
This chapter discusses the following topics:
Topic Related Documentation Base System Module Optional System Modules User Interface Passcodes, Access Levels, and Logging In and Out Menu Structure
See Page # 1-2 1-3 1-5 1-9 1-12 1-14
1-1
Related Documentation
The following table lists publications that provide specific information concerning field wiring, replacement parts, optional modules, and application information.
Publication Title
4010-9806 Class A Module – Installation Instructions 4010-9809 City Circuit Card – Installation Instructions 4010 Fire Alarm Expansion Power Supplies Installation Instructions 4010 Fire Alarm RS232 Interface and Service Modem Cards Installation Instructions 4010-9820 Battery Meter Module – Installation Instructions 4010-9814 Suppression Kit – Installation Instructions 4010 Fire Alarm DACT Modules – Installation Instructions 4010 Fire Alarm 4120 Network Interface Cards Installation Instructions 4010 Fire Alarm – Parts List 4098 Detectors, Sensors, and Bases – Application Manual 4010 Fire Alarm – Field Wiring Diagrams
Part Number 574-055 574-056 574-057
574-058
574-165 574-166 574-167 574-168
574-424 574-709 842-058
1-2
Overview
Base System Module
Overview SFI/O
The 4010 Base System includes the SFI/O card, power supply, and cabinet.
The SFI/O contains all connections for optional modules as well as N2 annunciator communication, IDNet, NAC, Auxiliary Power, Auxiliary Relay, PC Programmer (service port), and expansion power connections.
The User Interface provides a 2×40 LCD screen, LEDs, operational and programming keys, all of which are visible with the cabinet door closed. See “User Interface,” later in this chapter for additional information about the user interface.
TB1
TB2
TB3 TB4
TB5 TB6 P13 P14
TB7 TB8
Figure 1-1. 4010 SFI/O with User Interface Continued on next page
1-3
Base System Module, Continued
Power Supply Base System
Base System:
· 120VAC +10% / -15%, 60Hz or 220/240VAC +10% / -15%, 50/60Hz · 24VDC (unregulated) 4A alarm power · 24VDC, 1/2 Amp auxiliary power · Battery Charger for 25Ah Batteries, 24-hour recharge at 120VAC (for larger
battery capacity, use the 4081-9301, -9302, -9303, or -9304 External Battery Cabinet w/Charger)
Note: The 4010 back box can accommodate up to 25Ah batteries.
Default Settings
All switches and potentiometers are set at the factory before shipping. Although the settings should be accurate, you can change the settings on the following components as indicated.
· LCD Adjustment (R143) If necessary, use a small flat head screwdriver, turn the R143 Potentiometer located below TB1 to adjust the contrast on the LCD for the 4010.
· Baud Rate Setting (SW2) – Baud rate settings for the 4010 communications are shown in Table 1-1 below. If you receive a communications trouble at the panel, verify that SW2 is set correctly.
Table 1-1. SW2 Switch Settings
Baud Rate
OFF LINE 9,600 19,200 19,200
SW2-1
ON OFF ON OFF
SW2-2
ON ON OFF OFF
Important: You must set all cards to the same baud rate in order for the 4010 to operate properly. If you have a 4010 with a Network or DACT card, you must set the SW2 dip switch to the 9600 baud rate. It is recommended that you use the 19,200 option when uploading/downloading information to a PC.
Environmental Specifications
Temperature: The 4010 operates normally with ambient temperatures from 32° F to 120° F (0°C to 49°C), inclusive.
Humidity: The 4010 operates normally under non-condensing humidity conditions up to 85% relative humidity @ 86° F (30°C).
1-4
Overview
Optional System Modules
Overview
Optional Modules with Dedicated Hardware Slots
The following is a list of optional modules for the 4010. Refer to the individual instructions that accompany each module for more information. Those instructions and their part numbers are listed in the “Related Documentation” section of this chapter. Refer to the label inside the door of the 4010 for the placement of optional modules.
Note:
Certain modules are mutually exclusive. For example: · One DACT or One City Circuit Card is allowed. · One 4120 Network Card or One DACT is allowed. · One Dual RS232 Card or One RS232/Modem is allowed. · One Battery Meter Module or One 24VDC Extender Terminal
Block.
The 4010 has five dedicated mounting locations to support the following modules.
4010-9806 Class A Adapter Card for NACs
The four NACs found on the SFI/O board are Class B (Style Y). To support Class A (Style Z) you must install an adapter card that mounts to the SFI/O board. Each adapter card supports two NACs.
4010-9809 City Circuit Card
The city circuit card connects to the SFI/O with a ribbon harness to provide ULlisted connections to either Remote Station (reverse polarity) or Public Service Fire Communications Center (local energy) receiving units (selectable). The card has two circuits — Circuit 1 reports only alarm events and Circuit 2 can be configured to report Trouble events or Trouble and Supervisory events. In the event of a CPU failure, a city card configured for a Trouble Output sends a trouble to the city circuit. The card is mounted to the right of the SFI/O at the top of the chassis.
Newer versions of the 4010 FACP (Version 2.01 or later) provide the ability to reset the City Circuit in the following situation.
· If the device(s) in alarm is physically removed. · No other devices are in an alarm state. · System Reset is performed.
Enabling City Circuit reset is done via Custom Control. Refer to “ApplicationSpecific Examples” at the end of Chapter 8 for specific information. Be sure to consult the AHJ before enabling the City Circuit Reset option.
Continued on next page
1-5
Optional System Modules, Continued
Optional Modules with Dedicated Hardware Slots (continued)
Optional Modules for Expansion Slots
4010-9813 Expansion Power Supply
When more than 4A of Notification or AUX power is required, an expansion power supply may be added. The expansion power supply provides filtered 24VDC, 4A power for Notification and Auxiliary use. The expansion power supply is mounted to the right of the SFI/O at the bottom of the chassis.
4010-9814 Suppression Kit
The 4010-9814 suppression kit consists of an expansion power supply designed to provide regulated 24VDC power for suppression circuits and a suppression system appliqué that is applied to the outside of the FACP. The suppression kit mounts in the same hardware slot as the expansion power supply.
4010-9820 Battery Meter Module
The 4010-9820 Battery Meter Module provides an indication of the charge/discharge state of the FACP’s batteries (internal or external). The module also provides a constant reading of the current and voltage of the monitored batteries. This module mounts to the right of the city module.
The 4010 has a maximum of two expansion slots available to support the following cards.
4010-9810 and -9816 DACT Cards. Two versions of the DACT are offered:
4010-9810 Event Reporting DACT – Five categories of status changes are supported with this card. The Central Station is notified of Alarm, Trouble, Supervisory or Waterflow status changes. AC Fail trouble is delayed for 6 to 12 hours before reporting to the Central Station. In the event of a CPU failure, the card sends a “CPU Trouble” message to the Central Station.
4010-9816 Per Point Reporting DACT – Specific information is available about which point in the system experiences a status change. The report sent to the Central Station includes the specific point address along with the point status. The DACT supervises the system CPU via N2 communication. In the event of a CPU failure, the DACT sends a “CPU Trouble” message to the Central Station.
Continued on next page
1-6
Overview
Optional System Modules, Continued
Optional Modules for Expansion Slots (continued)
Remote Optional Modules
4010-9811 Dual RS232 Card
The Dual RS232 Card is connected to the N2 communication lines. The 4010 can vector messages to RS232 ports by category. The RS232 ports may be configured as follows:
· Two serial printers (80 or 40 column). · One serial printer and one CRT/Keyboard (command line interface).
The RS232 ports on the option card are electrically isolated from earth, allowing connection of an AC powered printer or CRT/keyboard.
Note: Only the 80-column printer can be used to print 4010 system reports.
4010-9812 RS232/Service Modem Card
This card is similar to the above dual RS232 card except that one port is a dedicated Service Modem port (command line interface). The second port may be programmed for use with a serial printer or left unused. Event vectoring by category is supported on the modem and RS232 ports.
4010-9817, -9818, -9819, and -9821 4120 Network Cards
A 4120 Network card can be added to the 4010. This card communicates with the system CPU via N2 communication. The 4010 system can be a node on a 4120 Network, however it has limited functionality. Points on the 4010 may be declared as Public. No points on other nodes may be declared as External to the 4010. Set Host and Remote Download functions are fully supported.
The following optional modules mount remotely from the 4010 FACP.
4606-9101 LCD Remote Annunciator
The 4606 LCD annunciator for the 4010 provides remote area annunciation of the 4010 panel’s status. Pass-key protected, the user interface provides a 2×40 LCD screen, indicating LEDs, and operator membrane keys.
4605-8401 24-Point I/O
The 24-Point I/O Card for the 4010 is capable of using any combination of 24 inputs or outputs to control LEDs, lamps, and relays, and to monitor contact closure inputs. The outputs can be ON continuous or flashed, at a slow or fast rate. Inputs may be unsupervised, supervised for opens, supervised for open and shorts, depending upon how the switch is wired externally.
Continued on next page
1-7
Optional System Modules, Continued
Other Compatible Equipment
The 4010 is compatible with the equipment listed below provided all equipment meets the applicable agency listings for the intended use.
· 4003 Voice Control Panel (VCP). Since the 4010 does not contain hardwired monitor points, the alarm/trouble output from the 4003 is connected to a Zone Adapter Module (ZAM). One of the NACs on the 4010 can be used to activate the 4003.
· 4009A and 4009R IDNet NAC Extender. · The 4010 is compatible with the following 4098 smoke/heat sensors and
bases:
PID 4098-9710 4098-9713 4098-9714 4098-9717 4098-9733 4098-9789, -9791 thru -9793
Description
Quickconnect, TrueAlarm, Photo Smoke Sensor
Quickconnect, TrueAlarm, Photo Smoke Sensor with sounder.
TrueAlarm, Photo Smoke Sensor (requires separate base)
TrueAlarm, Ion Smoke Sensor (requires separate base)
TrueAlarm Heat Sensor (requires separate base)
Sensor Bases
· Power supplies that are power-limited and listed for fire-protective signaling use can be used with the 4010 when wired according to power-limited guidelines.
· The 4010 is compatible with the 4120 network. In order to use the 4010 as a node on the network, you must have
– 4100 master software must be Rev. 8.01 or higher and GCC/NPU must be Rev. 2.03 or higher.
– 4120 network firmware must be Rev. 3.01 or greater. (Rev. 3.02.99 or later is recommended.)
– 4010 network firmware must be Rev. 3.03.99 or later.
1-8
Overview
User Interface
Overview
The user interface of the 4010 system consists of control keys, LEDs, a 2-line by 40-character backlit LCD, and a tone-alert mounted in the control panel. The purposes of the Operator and Menu keys are listed below.
LCD
LEDs Operator
Keys
Menu Navigation Keys
12:02:15pm
*S*SYYSSTTEEMM IISSNONORRMMAALL**
10:09:33am
Wed 27-Aug-97 Thur 04-Jul-96
FIRE ALARM
SYSTEM
SYSTEM
SUPERVISORY TROUBLE
ALARM SILENCED
AC POWER
User Programmed
ALARM ACK
SUPV ACK
TROUBLE ACK
ALARM SILENCE
SYSTEM RESET
User Programmed User Programmed
Menu
Function
Disable Enable
Exit Clear
Enter
Previous
Next
Operator Key Definitions
ALARM ACK
SUPV ACK
TROUBLE ACK
Figure 1-2. 4010 Operator Interface, Showing High-Level Status Screen
The following information defines the operator (rectangular) keys on the 4010 panel.
Alarm Acknowledge <ALARM ACK> The <ALARM ACK> key is used to acknowledge any unacknowledged fire alarms in the system and to scroll through the alarms in the active Alarm List.
Supervisory Acknowledge <SUPV ACK> The <SUPV ACK> key is used to acknowledge any unacknowledged supervisories in the system and to scroll through the supervisory conditions in the active Supervisory List.
Trouble Acknowledge <TROUBLE ACK> The <TROUBLE ACK> key is used to acknowledge any unacknowledged troubles in the system and to scroll through the troubles in the active Trouble List.
Continued on next page
1-9
User Interface, Continued
Operator Key Definitions (continued)
ALARM SILENCE
SYSTEM RESET
Menu Navigation Key Definitions
Menu
Function
Disable Enable
Exit Clear
Alarm Silence <ALARM SILENCE> The <ALARM SILENCE> key is used to silence any silenceable output types (generally all non-visible notification appliances).
System Reset <SYSTEM RESET> The <SYSTEM RESET> key allows you to reset all alarm notification appliances and controls, remove alarms from the Alarm List, silence all silenceable outputs, reset detectors, and return the system to a normal state (provided that no alarms are present). The display will indicate that a reset is in progress and whether or not a reset completes successfully.
The following information defines the menu navigation (round) keys on the 4010 panel. These keys perform access level dependent functions defined in the “Passcodes, Access Levels, and Logging In and Out” section of this chapter.
Menu <Menu> The <Menu> key always brings you to the top of the main menu structure unless you are in Programming or Quick-CFIG menus (see the Menu Structure at the back of this chapter).
Function <Function> The Function Menu is displayed when the <Function> key is pressed at the High-Level Status screen. Use the < Previous> and < Next> keys to scroll through the functions list. The function key provides access to commonly used control and display “functions,” and is also used for list editing.
Disable/Enable <Disable/Enable> The <Disable/Enable> key allows the operator to quickly disable or enable any point that is currently displayed (passcode protected). A confirmation screen is displayed requesting <Enter> be pressed before performing the actual enable or disable.
Exit/Clear <Exit/Clear> The <Exit/Clear> key is used to back out of menus or displays to get to the toplevel menu structure (refer to the “Menu Structure” at the end of this chapter). Where possible, the <Exit/Clear> key will back out one level at a time. There are cases, however, that the <Exit/Clear> key will return the operator directly to the top level.
Continued on next page
1-10
Overview
User Interface, Continued
Menu Navigation Key Definitions (continued)
Enter
Previous
Next
þ
Enter <Enter> The <Enter> key is used to confirm selections. When pressed, this key provides additional information about the point shown on the display. In a programming screen, pressing <Enter> indicates that the information on the display is correct and can be entered. The <Enter> key is used in various other places within the menu structure, always for this same type of operation.
Right <> and Left Arrow <> The <> and <> arrows are used in screens with multiple choices. The keys advance the focus (square brackets [ ] ) from field-to-field.
Previous < Previous> and Next < Next> The < Previous> and < Next> keys allow you to move from screen-to-screen within any displayable object having multiple screens. This would include scrolling through an historical log, the point database, a list of points, or other similar activities. The < Next> key selects the next display screen in sequence, and the < Previous> key selects the previous screen. These keys are also used to view additional information about abnormal points or in viewing Historical Logs.
1-11
Passcodes, Access Levels, and Logging In and Out
Overview
Certain operator functions of the 4010 are passcode protected at different levels. This section describes logging in and out at specific access levels.
Passcodes and Access Levels
All operations in the 4010 are protected at a preset level with designated passcodes to access these operations. The table below shows the basic operations and menu choices for specific access levels. The default passcodes are listed for Levels 2 through 4. Refer to the Menu Structure later in this chapter for a complete quick-reference of the main 4010 FACP menus.
Table 1-2. Access Levels and Operations
ACCESS LEVEL 1
2 Passcode = 2000
3 Passcode = 3000
4 Passcode = 4000
OPERATIONS
Ack
Silence
System Reset
All Level 1 Operations, plus: Set Time/Date Point Control Enable/Disable Points
All Level 1 & 2 Operations, plus: Clear Logs Clear Verification Tallies Programming
– Edit/Clear Point Label – Restore/Save CFIG
TrueTest Walk Test Reports
All Level 1,2, & 3 Operations, plus: Quick CFIG Run Diagnostics Upload/Download Programming
· Edit Cards · Edit SMPL Program · System Options Restart Panel · Warm Start · Cold Start
Continued on next page
1-12
Overview
Passcodes, Access Levels, and Logging In and Out, Continued
Logging In and Out
To execute any of the functions protected at Level 2 or above, you must Login to the 4010 FACP using a passcode. After completing a task at a certain access level you should then Logout to return the access level to Level 1. When logged in at Level 2 or above and you do not press any front panel keys for more than ten minutes, the 4010 defaults to access level 1.
All passcodes consist of a four-digit number. Logging in at a Level 4 causes a Service Mode trouble. Note that this trouble can only be cleared by restarting the panel.
To Login, perform Steps 1 through 7 on a 4010 that is at the High-Level Status screen (refer to Figure 1-2 for an example of this screen). When moving from one digit to the next, an asterisk () appears in the place of an entered number for security purposes. See Table 1-2 in the previous section for the default passcodes.
1. Obtain the appropriate passcode information for the appropriate level. 2. Press <MENU>. 3. Press and hold < NEXT> until [Login/Logout] is displayed, and then press
<ENTER>. 4. Press and hold < NEXT> until [Login] is displayed, and then press
<ENTER>. 5. Press < NEXT> to scroll through the numbers on the display until the
appropriate number is displayed. 6. Press the right arrow < > to move the focus brackets [ ] to the next digit in
the passcode. Repeat Steps 5 & 6 until all numbers are entered. 7. When the passcode is correct, press <ENTER> to Login.
A **Login Accepted** screen indicating your current access level is displayed briefly upon a successful Login attempt. If you did not enter the appropriate Login passcode, a **Login is Invalid** screen appears.
To Logout, perform Steps 1 through 4 above except for Step 4 where you need to wait until [Logout] is displayed.
1-13
Menu Structure
1-14
Overview In this Chapter
Chapter 2 Back Box Installation
This chapter contains instructions and guidelines for installing the 4010 FACP backbox.
This chapter discusses the following topics:
Topic Before You Begin Remove Chassis and Cut Conduit Openings Mount the Backbox Re-install the Chassis
See Page # 2-2 2-3 2-4 2-5
Back Box Installation
2-1
Before You Begin
Unpacking the System Installation Guidelines
Standards and Codes
Unpack the 4010 using the following information:
· Carefully unpack the system and inspect for shipping damage. · Select a location for the control panel in a clean, dry, vibration-free area
with moderate temperature (see the “Environmental Specifications” section in Chapter 1).
Before installing the 4010, read the following guidelines:
· Install the FACP in a readily accessible area with sufficient room to easily install and maintain the control panel.
· Locate the top of the cabinet approximately five feet above the floor with the door hinge on the left-hand side.
· Count the number of conductors needed for all devices and cut the appropriate knockouts. Pay careful attention to the routing for PowerLimited and Non-Power Limited wiring. You must maintain a 1/4-inch separation between these two types of wiring. All terminal connections are Power-Limited except those to the AC power, Battery, and City Circuit, and contacts when switching Non-Power Limited sources.
· Review the precautions and warnings at the front of this publication. · All wiring must comply with the National and/or Local codes for fire alarm
systems. All wiring must test free of grounds. · Leave sufficient room for batteries in the bottom of the back box (see the
label inside the 4010 back box for more information). · Enclosure must be level and plumb when installed.
When installing the 4010, you should be familiar with the following standards:
· NEC Article 300 Wiring Methods · NEC Article 760 Fire Protective Signaling Systems · Applicable Local and State Building Codes · Requirements of the Local Authority Having Jurisdiction (AHJ)
2-2
Back Box Installation
Remove Chassis and Cut Conduit Openings
Overview
The 4010 ships from the factory completely assembled in the back box, or as a single piece electronics assembly that is shipped separately from the back box, retainer, and door. The system electronics (SFI/O and power supply) are mounted to a steel chassis. Refer to the 526-407 label inside the back box for additional information.
Step 1. Remove the Chassis
Prior to installation you must remove the chassis containing the 4010 SFI/O and power supply from the back box. Use the following steps to remove the chassis.
1. Remove the door grounding wire from the back box. Remove the door from the hinges and set it aside.
2. Remove the metal retainer by gently lifting and pulling the bottom of the retainer out from the back box. Then, being careful not to drop the retainer, slide the top of the retainer out from under the lip of the top of the back box.
3. Remove the AC wiring Quick-Disconnect connector from the chassis by firmly squeezing the release tabs and pulling it free. The Quick-Disconnect connector is located directly below the chassis. Dress the wires so that they do not interfere with back box installation.
4. Loosen or remove the four mounting screws holding the chassis to the back box.
5. Lift the chassis out of the back box and store in a clean, dry, safe area for reinstallation later.
Step 2. Cut Conduit Entrances
Determine the amount and proper location of conduit/service entrances. Make all appropriate entrances into back box (see Figure 2-1).
Caution:
Power-Limited and Non-Power-Limited wiring must enter through separate conduit/service entrances. AC power entrance into back box is recommended at the bottom right side of the back box.
If a Bus Bar is required to terminate wire shields, see Figure 2-1 for proper mounting location. Entrances for shielded wire must be located within two inches of the bus bar. Maximum intrusion into box for conduit is 1/2-inch.
TYPICAL CONDUIT LOCATION
BUS BAR MOUNTING STUDS
2″ MAX IF USING BUS BAR
TOP VIEW
Figure 2-1. Conduit and Bus Bar Mounting Locations.
2-3
Mount the Backbox
Surface Mounting the Back Box
Semi-Flush Mounting the Back Box
1. Using the pre-cut holes in the back of the box as a guide, mark off where you want to mount the back box (see the “Before You Begin” section of this chapter).
2. Using mounting hardware capable of supporting a fully loaded 4010 (approximately 50 lbs.), screw two screws into the wall where the top two teardrop holes of the back box are to be located. Tighten the screws leaving about a 1/8-inch gap from the seated position.
3. Carefully lift the back box and place the two teardrop holes over the mounting screws.
4. Screw two mounting screws into the two bottom back box holes and tighten all screws.
1. Remove the mounting knockouts from both sides of the back box. See Figure 2-2 for their location.
2. Make the appropriate opening in the wall or wall board to accommodate the back box. Dimensions of the backbox are 22″ (55.8 cm) W x 18 (45.7 cm) H x 6 ¼ (15.8 cm) D.
3. Frame the opening to accommodate the back box. Fit the back box into the opening. Use wall stud guides to ensure free movement of the door.
4. Using mounting hardware capable of supporting a fully loaded 4010, screw or nail back box to the studs.
DOOR
6 1/4″ 5 3/8″
FRONT OF STUD FOR 1/2″ WALLBOARD
FRONT OF STUD FOR 5/8″ WALLBOARD
WALL STUD GUIDES (1/2″ WALL BD)
WALL STUD GUIDES (5/8″ WALL BD)
KNOCKOUT SCREW/NAIL HOLES (FOR SEMI
FLUSH MOUNT.)
SIDE VIEW
Figure 2-2. Wall Stud Guides Continued on next page
2-4
Back Box Installation
Re-install the Chassis
Procedure
Use the following steps to re-install the 4010 chassis containing the SFI/O and power supply into the back box.
1. Insert two mounting screws into the top two mounting holes for the chassis. Tighten the screws leaving a 1/8-inch gap from the seated position.
Caution: When mounting the chassis, pay careful attention to any wiring inside the back box. Do not crimp any wiring behind the chassis when mounting.
2. Carefully hang the chassis on the two top mounting screws using the top teardrop holes on the chassis.
3. Insert two mounting screws into the bottom two teardrop chassis mounting holes and tighten all screws.
4. Re-hang the door on the back box hinges and re-attach the door grounding wire to the back box.
5. You can re-install the retainer now before wiring or later after wiring is complete. Re-install the retainer by guiding the top lip of the retainer under the top lip of the back box and carefully sliding the bottom of the retainer into place.
WARNING: DO NOT APPLY POWER TO THE 4010 AT THIS TIME! DO NOT connect the quick-disconnect AC connector to the chassis. Refer to the “Power-Up and Checkout” section of this publication for more information.
2-5
This is blank
Overview In this Chapter
Chapter 3 Wiring
This chapter contains instructions and guidelines for wiring the 4010 FACP.
This chapter describes how to wire the base 4010 FACP. Use the information in this chapter, the 526-407 and 526-408 labels located on the inside door of the FACP, and the 842-058 Field Wiring Diagram to wire the base panel.
Refer to the publications listed in Chapter 1 to wire all optional modules.
This chapter discusses the following topics:
Topic Overview NAC Wiring IDNet Wiring AC Power and Battery Wiring Auxiliary Relays System Power Up and Checkout Periodic Testing and Maintenance
See Page # 3-2 3-4 3-5 3-6 3-9 3-10 3-13
Wiring
3-1
Overview
Power Limited Versus NonPower Limited Systems
The 4010 system can be wired as either a Power Limited or Non-Power Limited system. Adhere to the following guidelines and consult the NEC for specifics.
· When installing the 4010 as a Power Limited system, you must observe the following guidelines:
– Maintain ¼ inch of space between Power Limited wiring and AC Power or Battery wiring.
– Run AC Power wiring in a separate conduit that enters the back box in the upper or lower right corner.
– Route AC Power, battery wiring, city circuit connections, and non-
Power Limited Relay wiring only through the shaded areas shown in Figure 3-1. Do not route Power Limited wiring through the shaded areas shown in the figure.
· The 4010 FACP can be reclassified as a non-Power Limited system when installed in accordance with the latest version of NEC 760. In this case, all references to Power Limited must be removed from the panel’s labels.
18″
DISCARD AFTER SHIPPING
22″ 8 1/2″
14.5″
BATTERY AREA
NO CONDUIT ENTRY OR WIRING IN THIS AREA
FRONT VIEW
AC POWER HARNESS
AC TERMINAL BLOCK
SHADED AREA IS FOR NON-POWER LIMITED WIRING ONLY
Figure 3-1. Location of Non-Power Limited Wiring Area
3-2
Overview, Continued
Locations of Terminal Connections
Figure 3-2 shows the location of all terminal connections for the system components. Refer to the appropriate section later in this chapter for specific information on wiring a component.
4010-9806 Class A Module (565-789)
4010-9806 Class A Module (565-789)
Pot for LCD Adjustment
4010-9809 City Module
4010-9820 Battery Meter
Module
WARNING: PTCs MUST NOT TOUCH EACH OTHER OR ANY OTHER METAL SURFACE!
Figure 3-2. Base Panel Wiring
4010-9813 Expansion Power Supply (565-792)
or 4010-9814 Supression Power Supply (565-793)
Wiring
3-3
NAC Wiring
Overview
Terminal Connections
The 4010 provides four NACs for notification appliances such as horns and strobes. These NACs are standard Class B (Style Y). Optional Class A (Style Z) operation can be achieved using an adapter. Refer to the 4010-9806 Class A Module – Installation Instructions, Part No. 574-055 for information on the Class A NAC adapter.
The NACs supervise for short or open circuit troubles. In the event of a short, the NAC does not energize. Each NAC is rated at 2A. Up to 4A of NAC power is available from the base unit. If more power is needed, NAC 3 and NAC 4 can be connected to an expansion power supply.
An auxiliary (AUX) power connection (rated at 1/2A, 24VDC) is provided at TB5 located to the left of the auxiliary (AUX) relay terminal blocks at the bottom center of the SFI/O. Current drawn from TB5 must be deducted from the 4A total NAC power.
Each NAC can be configured as “On until Silence” or “On until Reset” and can be coded or non-coded (refer to “Chapter 6 – Configuring Points” for more information). The 4010 can disconnect each NAC individually to aid in locating earth faults.
The NAC’s wiring connects to TB1 and TB2 as shown in Figure 3-3. These terminal blocks are barrier strip type that can accommodate 12-18 AWG wires. TB1 and TB2 are located in the upper left corner of the SFI/O. Refer to the 842058 wiring diagram for Alarm Current, Wiring Distance, and Line Resistance values.
TB1-1: NAC 1 + Alarm TB1-2: NAC 1 – Alarm TB1-3: NAC 2 + Alarm TB1-4: NAC 2 – Alarm
TB2-1: NAC 3 + Alarm TB2-2: NAC 3 – Alarm TB2-3: NAC 4 + Alarm TB2-4: NAC 4 – Alarm
NAC 1
NAC 2
NAC 3
NAC 4
Alm+ Alm- Alm+ AlmTB1
1
2
3
4
Alm+ Alm- Alm+ AlmTB2
1
2
3
4
Figure 3-3. NAC Wiring 3-4
IDNet Wiring
Overview
Terminal Connections
The 4010 uses addressable IDNet devices (smoke and heat detectors/sensors and pull stations, 4009 IDNet NAC Extender, etc.). The 4010 supports 250 devices on a single pair of wires on a single channel.
The IDNet channel supports Style 4 and 6 as part of the base system. Refer to the 4010 Field Wiring Diagram (842-058) for all wiring information.
IDNet communication also supports the detection of duplicate devices. IDNet detects if two devices are set to the same address. This function is activated from the front panel (see IDNet Diagnostics in the Diagnostic/Troubleshooting section of this publication).
Use the information below to wire the IDNet communication lines (14-18 AWG) to TB4 located in the upper right corner of the SFI/O.
· To connect Class A wiring, wire the “B” terminals (TB4-1 and -2) to each device in succession without T-taps (observe polarity). At the last device in the loop, return the B+ wire to the A+ terminal (TB4-4) and the B- wire to the A- terminal (TB4-5).
· To connect Class B wiring, jumper B+ to A+ and B- to A- using 14-18 AWG insulated wire (T-taps are allowed). Connect B+ to all devices (positive connection) and connect B- to all devices (negative connection).
IDNet Comms
A- A+ SHLD B- B+
TB4
6
5
4
3
2
1
Figure 3-4. IDNet Connections
Wiring
3-5
AC Power and Battery Wiring
AC Power
When the 4010 FACP is installed as a Power-Limited system, AC power lines must be run in a separate conduit, and should enter the back box in the lower right corner. Use the shaded area of Figure 3-5 only for routing of AC power wiring. All wiring must be neatly dressed within the back box. Use the wiring guides inside the back box when possible.
· The FACP requires connection to a separate dedicated AC fire alarm circuit, which must be labeled “Fire Alarm.”
· The AC power circuit must connect to the line side of the main power feed of the protected premises.
· No other equipment can be powered from the fire alarm circuit. · The AC power circuit wiring must run continuously, without any disconnect
devices, from the power source to the FACP. · Over-current protection for this circuit must comply with Article 760 of the
National Electric Code as well as local codes. · Use 12AWG wire with 600-volt insulation for this circuit.
1. Match incoming Neutral and Hot wires
to their corresponding wires leading
from the terminal block located in the
lower right corner of the back box to
the Quick-Disconnect harness and
screw into place. 2. The safety ground wire from the AC
WIRE GUIDES
source must be connected to the
ground stud located below the terminal
block. Do the following to connect the
ground wire to the stud:
a) Run the ground wire to the stud and cut it, leaving a little slack for adjustment.
b) Crimp a spade terminal (Part No. 474-144 or -015) onto the ground wire.
c) Place a lock washer on the stud, followed by the terminal and then another lock washer.
d) Securely fashion a nut (Part No. 322-128) onto the stud.
14.5″
BATTERY AREA NO CONDUIT ENTRY OR WIRING IN THIS AREA
AC POWER HARNESS
AC TERMINAL BLOCK
Figure 3-5. AC Power Wiring
SHADED AREA IS FOR NON-POWER LIMITED WIRING ONLY
Continued on next page
3-6
AC Power and Battery Wiring, Continued
Installing and Connecting Batteries
The base 4010 FACP accommodates (and charges) up to 25 Ah capacity batteries. The following is a list of compatible batteries.
· 2081-9272, 6.2 Ah · 2081-9274, 10 Ah · 2081-9275, 18 Ah · 2081-9288, 12.7 Ah · 2081-9287, 25 Ah
Install the batteries in the area shown on the label located in the bottom of the back box. Use the following steps, Part No. 733-945 battery harness (733-903 for Canadian systems), and Figure 3-6 to connect the batteries to TB8 located in the lower left corner of the SFI/O.
Domestic systems should use the following procedure.
1. Using the short white wire crimped at both ends, jumper one positive (+) terminal of one battery to the negative (-) terminal of the other battery.
2. Take the non-crimped end of the red wire from the harness and connect this to the + side of TB8. Connect the Fast-on connector on the other end of the Red wire to the Positive terminal of one of the batteries.
3. Take the non-crimped end of the black wire from the harness and connect this to the – side of TB8. Connect the Fast-on connector on the other end of the Black wire to the Negative terminal of one of the batteries.
TB8
Wiring
– BATTERY +
Figure 3-6. Battery Connections Domestic System
Canadian systems should use Figure 3-7 as an installation guide. WARNING: DO NOT APPLY BATTERY POWER TO THE 4010 AT
THIS TIME! DO NOT connect crimped ends of the red and black wires to the battery. Refer to the “Power-Up and Checkout” section of this publication for more information.
Continued on next page
3-7
AC Power and Battery Wiring, Continued
Installing and Connecting Batteries (continued)
CANADIAN LOW BATTERY MODULE P4
SF I/O BD 565-738
RED
6 4 2
BTRY
TB8
BATTERY HARNESS 733-903
BLK
RELAY 5 3 1
RED
RED
BATTERY
BATTERY
Figure 3-7. Canadian Battery Wiring
WARNING: DO NOT APPLY BATTERY POWER TO THE 4010 AT THIS TIME! DO NOT connect crimped ends of the red and black wires to the battery. Refer to the “Power-Up and Checkout” section of this publication for more information.
3-8
Auxiliary Relays
Auxiliary Relays
The 4010 provides two auxiliary (AUX) relay circuit connections; one at TB6 and the other at TB7. Each circuit provides one form “C” contact (normally open or normally closed) rated at 2A (24VDC), or 0.5A (120 VAC) with optional 120 Volt auxiliary relay kit.
The default operation for AUX1 is an Alarm Relay and AUX2 is a Trouble Relay. The AUX relay circuits can also be programmed for other desired operations using the front panel (see “Chapter 6 – Configuring Points”).
Use Figure 3-8 to wire the AUX relay circuits. TB6 and TB7 are located at the bottom of the SFI/O near the center.
When power for the AUX relay contacts is from TB5 (AUX Power), 4010-9813, or 4010-9814 expansion power supplies, the circuit is power-limited. When power for the AUX relay contacts IS NOT from the sources listed above, use an in-line fuse (Part No. 208-165). If power source is non-power-limited, wiring must be routed through the non-power-limited spaces shown in Figure 3-1 and “power-limited” markings must be obliterated.
TB6
TB7
NO
C
NC
NC
C
NO
Bottom of the SFI/O
AUX1
AUX2
Figure 3-8. AUX Relay Connections
Wiring
3-9
System Power-Up and Checkout
Connect AC & Battery Power
Use the following steps to apply AC and battery power to the 4010 FACP.
1. Re-connect the AC power harness removed in previous steps 2. Connect the crimped ends of the 733-945 battery harness (733-903 for
Canadian systems) to the batteries. Observe polarity (red to +, black to -) when connecting batteries.
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes, and can destroy fabrics. Replace any leaking or damaged battery. If contact is made with sulfuric acid, immediately flush skin or eyes with water for 15 minutes and seek immediate medical attention.
Power-Up and Checkout
Caution: Notify fire, central station, and/or building personnel before testing the system.
Power-Up
After applying power to the system, use the following list to check the 4010 for proper operation.
· Check that the green AC Power LED is ON. · Check that all yellow and red LEDs are OFF. · Use the Lamp Test procedure in “Chapter 11 – Operation” of this
publication to verify that all 4010 LEDs and LCD segments work properly.
On power-up, the 4010 performs the following:
· Displays revision of boot-loader software · Self Test – CPU Hardware Checkout · Linkscan – Checking for a Programmer Unit Connection · Memory Scan – Checking for Incorrect Application · Start up – 4010 FACP Startup
Start up
Figure 3-9. 4010 Start Up Screen Continued on next page
3-10
System Power-Up and Checkout, Continued
Power-Up and Checkout (continued)
If the 4010 passes its start up self-test, the FACP starts and the system is normal, the High-Level Status screen shown in Figure 3-10 displays. If troubles exist in the system, Figure 3-11 displays after pressing <ACK>.
Note: The High-Level Status screen is the first screen shown on a 4010 whether in a normal or a trouble/supervisory/fire alarm state before any keys are pressed.
SYSTEM IS NORMAL
10:09:33am
Wed 27-Aug-97
Figure 3-10. System Normal (High Level Status) Screen
Custom Label Point Type
FIRE=0
SUPERVISORY=0
[TrueAlarm]Add
FIRST FLOOR EAST WING ROOM 12
Smoke Detector
Trouble
TROUBLE=3 1/130
1/3
First of Three Troubles
Device Condition
Figure 3-11. System Trouble Screen
Note: If the self-test fails, the 4010 displays the error code and waits 45 seconds before attempting a restart. Refer to Chapter 10 for a list of error codes.
Checkout
Caution: Before proceeding with the acceptance test procedures, do the following:
· Notify the fire department and the central alarm receiving station if transmitting alarm conditions.
· Notify building personnel of the test so that alarm sounding devices are disregarded during the test session.
· When necessary, disable activation of alarm notification appliances and speakers to prevent their sounding.
Continued on next page
Wiring
3-11
System Power-Up and Checkout, Continued
Acceptance Test
When finished with the original installation and all modifications, conduct a complete operational test on the entire installation to verify compliance with applicable NFPA standards. Testing should be conducted by a Simplex-trained technical representative in the presence of a representative of the Authority Having Jurisdiction, and the customer’s representative. Follow the procedures outlined in Chapter 7 “Inspection, Testing, and Maintenance” of NFPA Standard 72-1996 and the following steps.
1. Activate an initiating device (smoke, pull, etc.) and check that all active notification appliances (strobes, horns, etc.) function. Reset the alarm initiating device, the FACP, and any other associated equipment. Repeat this step for each initiating device.
2. Remove AC power, activate an initiating device, and check that active notification appliances sound, and alarm indicators illuminate. Measure the battery voltage with notification appliances active. Replace any battery with a voltage of less than 24VDC and reapply AC power.
Note:
Step 2 requires fully charged batteries. If batteries are new or discharged due to a recent power outage, allow the batteries to charge for 48 hours before testing. Refer to “Periodic Testing and Maintenance” section for more information on testing batteries.
3. Reapply AC power and check that all yellow and red LEDs are OFF and the green AC Power LED is ON.
Caution: Notify fire, central station, and/or building personnel when you finish testing the system.
3-12
Periodic Testing and Maintenance
Overview Battery Testing Information
Periodic testing and maintenance of the FACP, all initiating and notification devices, and any other associated equipment is essential to ensure proper and reliable operation. Test and maintain the FACP according to the schedules and procedures outlined in the following publications:
· NFPA Standard 72-1996, Chapter 7, “Inspection, Testing, and Maintenance.”
· Installation Instructions for the peripheral devices installed in your system. Correct any trouble condition or malfunction immediately.
Periodic testing and maintenance of the system batteries must be done to ensure proper and reliable back-up operation. Test and maintain the system batteries using the following information.
All sealed lead-acid batteries in fire alarm service should be tested annually. Replace all sealed lead-acid batteries that have been in service for four or more years.
It is recommended that a battery tester made specifically for checking sealed lead-acid batteries be used. Such a tester is available under Service Part No. 553-602.
If a battery tester is unavailable, the “voltage response test” described in the following information can be used to detect batteries with very low capacity or shorted cells.
Caution:
A defective battery charger circuit can cause battery failure. Check the condition of the battery charger when either a battery tester or a voltage response test reveals weakened batteries.
Voltage Response Test
1. Disconnect battery from system. 2. Connect a digital voltmeter across the battery. 3. Connect the appropriate sized resistor(s) (see Table 3-1) across the battery’s
terminals for the listed test time.
Caution: Resistors will get hot during test! Use 12AWG wire for battery-to-resistor hookup.
4. Record the end voltage reading. 5. Treat the battery as described in Table 3-2.
Continued on next page
Wiring
3-13
Periodic Testing and Maintenance, Continued
Battery Testing Information (continued)
Table 3-1. Battery Testing
Voltage Amp Hr
Resistor (Ohms)
12
6.2
6.0
12
8
4.5
12
10
4.0
12
18
2.0
12
25
1.5
12
33
1.0
6*
50
1.0
12
110
1.0
*Test 2 batteries in series for 12V
Watts Part No. and Description Test Time
50
380-031
2 Seconds
50
380-031 (adj to 4.5 Ohm) 2 Seconds
50
380-031 (adj to 4 Ohm)
2 Seconds
100 380-031 (3 in parallel)
2 Seconds
100 382-090 (2 in parallel)
2 Seconds
150 382-090 (3 in parallel)
2 Seconds
150 382-090 (3 in parallel)
4 Seconds
150 382-090 (3 in parallel)
4 Seconds
Table 3-2. Battery Readings and Instructions
If end voltage reading of battery is: 11.8V or more 11.7V to 11.0V 10.9V or less
*Retest battery after charging
Instructions Put in Service Charge Battery* Discard Battery
Discard battery after four or more years of service. Dispose of according to manufacturer’s guidelines.
3-14
Chapter 4 Quick CFIG
Overview Cautions and Warnings In this Chapter
The Quick CFIG option provides you with the ability to quickly and automatically program the components and features of the 4010. Quick CFIG is especially useful for programming basic system components following a new installation, and for adding components to an existing installation.
Quick CFIG functions include the following:
· Reconfigure All Hardware · Autodetect all new hardware added since CFIG was last saved · Restore the Factory CFIG · Accept default settings for system options · Edit settings of system options
Be alert to the following when using Quick CFIG:
· WARNING: The 4010 System will NOT continue to operate as a Fire Alarm System during the programming of Quick CFIG operations.
· Quick CFIG performs an IDNet duplicate address search, and terminates if duplicate addresses are found.
· Using the Quick CFIG options changes the 4010 configuration. When changing the configuration, information could be lost.
· Quick CFIG is not allowed if a DACT or Network card is installed. Use Quick CFIG first, and then program the DACT or network card.
· Class A Adapters are not automatically detected by Quick CFIG. Refer to Chapter 6 for information on programming a Class A NAC.
· QuickAlert functions are not accessible through Quick CFIG. You must manually program the appropriate NACs with the QuickAlert point type to enable QuickAlert operation. Refer to Chapter 6 for information on manually programming a NAC’s point type.
· Quick CFIG automatically configures the hardware device type for a 4009 (4009A, R4009A, 4009A8, R4009A8). All 4009 NACs are set for Class B operation and assigned a point type of SSIGNAL.
This chapter discusses the following topics:
Topic Reconfigure All Hardware Auto Detect New Hardware Restore Factory CFIG Accept Default Settings for System Options Edit Settings for System Options
See Page # 4-2 4-3 4-4 4-5 4-6
4-1
Programming
Reconfigure ALL Hardware
Overview Procedure
This option starts the 4010 with a new configuration. If a configuration already exists and this option is selected, it clears the current configuration and adds all currently connected devices to the CFIG.
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [Quick CFIG] is displayed and
then press <ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm Operation mode.
Please Wait . . . Fire Alarm Operation Suspended
3. Press <ENTER> to continue with the Quick-CFIG option. 4. Press <NEXT> or <PREVIOUS> until <RECONFIGURE ALL
HARDWARE> is displayed and then press <ENTER>. A warning appears, indicating that this will delete the current configuration.
WARNING <Enter> to Continue WARNING This will DELETE current configuration
5. Press <ENTER> to continue. Another warning appears, indicating that you need to press <ENTER> to confirm the deletion.
WARNING <Enter> to Continue WARNING Press <Enter> to confirm deletion
A message appears indicating that Quick CFIG is reconfiguring the hardware. This message is followed by another, which indicates that Quick CFIG is scanning for IDNET devices. The Reconfigure ALL Hardware function is complete when a message similar to the following appears.
** Automatic Hardware Detection Completed ** Total IDNet Devices Added: 128
Refer to “Save CFIG Option” at the end of this chapter for information on saving the CFIG once you have reconfigured the hardware.
4-2
Auto Detect NEW Hardware
Overview Procedure
This option adds new hardware that is not currently in the CFIG. All existing hardware and programming remains the same.
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [Quick CFIG] is displayed and
then press <ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm Operation mode.
Please Wait . . . Fire Alarm Operation Suspended
3. Press <ENTER> to continue with the Quick-CFIG option. 4. Press <NEXT> or <PREVIOUS> until <AUTO DETECT NEW
HARDWARE> is displayed and then press <ENTER>. A warning appears, indicating that this will change the current configuration.
WARNING <Enter> to Continue WARNING This will CHANGE current configuration
5. Press <ENTER> to continue. Another warning appears, indicating that you need to press <ENTER> to confirm the hardware detection operation.
WARNING <Enter> to Continue WARNING Press <Enter> to confirm Detect NEW
A message appears indicating that Quick CFIG is reconfiguring the hardware. This message is followed by another, which indicates that Quick CFIG is scanning for IDNET devices. The Auto Detect NEW Hardware function is complete when a message similar to the following appears.
** Automatic Hardware Detection Completed ** Total IDNet Devices Added: 128
Refer to “Save CFIG Option” at the end of this chapter for information on saving the CFIG once you have reconfigured the hardware.
Programming
4-3
Restore Factory CFIG
Overview Procedure
This option restores the 4010 to its original (factory default) CFIG. All pseudo points (Analog and Digital) are cleared, Custom Control is erased, etc.
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [Quick CFIG] is displayed and
then press <ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm Operation mode.
Please Wait . . . Fire Alarm Operation Suspended
3. Press <ENTER> to continue with the Quick-CFIG option. 4. Press <NEXT> or <PREVIOUS> until <RESTORE FACTORY
CONFIG.> is displayed and then press <ENTER>. A warning appears, indicating that this will delete the current configuration.
WARNING <Enter> to Continue WARNING This will DELETE current configuration
5. Press <ENTER> to continue. The following message appears, indicating that the system is restoring the factory default configuration.
** Restoring Factory Default Panel **
This message is followed by a series of internal test messages. The High-Level Status screen appears when the operation is complete.
4-4
Accept Default Settings for System Options
Procedure
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [Quick CFIG] is displayed and
then press <ENTER>. A warning appears, indicating that the that the 4010 is no longer in the Fire Alarm Operation mode.
Please Wait . . . Fire Alarm Operation Suspended
3. Press <ENTER> to continue with the Quick-CFIG option. 4. Press <NEXT> or <PREVIOUS> until <ACCEPT DEFAULT
OPTIONS> is displayed and then press <ENTER>. A warning appears, indicating that this operation may change current settings.
WARNING <Enter> to Continue WARNING This may CHANGE current setting
5. Press <ENTER> to continue. The following message appears, indicating that the system is restoring the default settings for system options.
** Default Settings Restored **
Programming
4-5
Edit Settings for System Options
Overview
Once this action is selected from the Quick CFIG menu, you can set these options by scrolling through the choices shown in Table 4-1 and selecting the appropriate settings for each. For timer options, selecting “0”initiates the action immediately.
Procedure
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [Quick CFIG] is displayed and
then press <ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm Operation mode.
Please Wait . . . Fire Alarm Operation Suspended
3. Press <ENTER> to continue with the Quick-CFIG option. 4. Press <NEXT> or <PREVIOUS> until <EDIT SYSTEM OPTIONS> is
displayed and then press <ENTER>. 5. Use the <NEXT> and <PREVIOUS> keys to scroll through the system
options. Edit each of the system options as necessary, using the information in Table 4-1. Refer to Chapter 7 for specific information on system options.
Table 4-1. System Options and Available Settings
System Option Time/Date Format Active Status Reminder
Alarm Silence/Reset Inhibit Alarm Cut-out Timer Door Drop on Alarm Door Drop on AC Power Loss Audible NAC Operation
Settings
Choose 12 or 24-Hour Format
Choose: · On/Off; default Off · Set Reminder Interval (1-12 Hours); default = 8 · Signal Duration (0-60 Secs.) 0=ON til clear default = 5
Choose a timer range from 0 – 60 Mins; default = 0
Choose a timer range from 0 – 60 Mins; default = 0
Choose a timer range from 0 – 60 Secs; default = 0
Choose a timer range from 0 – 60 Mins; default = 0
Choose: · Audible NACs: Steady · Audible NACs: Slow March · Audible NACs: Fast March · Audible NACs: Temporal (default)
Continued on next page
4-6
Edit Settings for System Options, Continued
Procedure (continued)
Table 4-1. System Options and Available Settings (continued)
System Option
Settings
Visual NAC Operation
Choose: · Visual NACs: Steady · Visual NACs: Slow March · Visual NACs: Fast March · Visual NACs: Temporal · Visual NACs: Synchronous (default)
QuickAlert NAC Horn Operation
Choose:
· Temporal (default) · Steady · Slow March
Depleted Battery Cutout
Choose ON or OFF; default = OFF. Note: Set Depleted Battery Cutout to ON for suppression release systems.
Stagger Start AHU
Choose a timer range from 0 – 60 Secs; default = 30
Enable City Circuit
Choose ON or OFF; default = OFF
Expansion Power
Choose ON or OFF; default = OFF
Suppression Release (refer to “Chapter 7 – System Options” for more information)
Choose: · ON or OFF (default = OFF) · Dual Detector (default = OFF) · Detector Delay (default = 60) · Manual Delay (default = 30)
Edit Passcodes*
Change Passcode Designations
Logical Zone Labels*
Apply Zone Labels
*Available under Quick-CFIG System Options Menu Only.
Programming
4-7
Save CFIG Option
Overview
Depending on whether or not you will be doing additional programming (such as changing hardware and point types, etc.), you may want to save the CFIG following the Quick CFIG operation.
The Save CFIG option saves all information to the 4010 configuration after or during programming. Choose this option if you wish to save all of your edits and modifications you made during your programming session to the 4010 configuration. You can Save CFIG by choosing the menu option or pressing Exit/Clear to back out of Programming mode and then choosing the Save CFIG option from the 4010 prompts.
When exiting the programming mode, your 4010 re-boots and becomes operational as a fire alarm system.
4-8
Overview In this Chapter
Chapter 5 Configuring Cards
The 4010 allows you to manually configure each option card in the system. This chapter describes how to add, delete, or modify optional cards in the 4010 FACP.
Note: The system must be powered down before cards are added to the system.
This chapter discusses the following topics:
Topic Card Addresses Adding, Deleting, or Modifying 4010 Cards
See Page # 5-2 5-3
Programming
5-1
Card Addresses
Card Addresses
All card addresses (whether hardware or logical cards) are shown in Table 5-1. Table 5-1. 4010 Card Addresses
Card Address 0 1 2 3 4
5 – 7 8
9 – 14 15 – 16
17 18 19 20 21 22 23
Reserved Cards CPU Board NAC/Relay circuits Power Supply IDNet Channel Dual RS232 or Service Modem Unused 4120 Network or DACT cards N2 Slaves (24-Point I/O or LCD Annunciator) Unused 4009 IDNet NAC Extender System Digital Pseudo Points User Digital Pseudo Points System Analog Pseudo Points User Analog Pseudo Points System List Pseudo Points User List Pseudo Points
5-2
Adding, Deleting, or Modifying 4010 Cards
Overview Adding a Card
This section describes how to add, delete, or modify cards in a 4010 FACP. Be aware of the following configuration rules when adding, deleting, or modifying cards. · Cards 1 through 3 and 17 through 23 cannot be deleted. · Certain cards are mutually exclusive. For example:
– One 4120 Network Card or One DACT is allowed. – One Dual RS232 Card or One RS232/Modem is allowed.
· The City Circuit card and Expansion Power Supply are enabled via the System Options menu. Refer to Chapter 7 for information on doing this.
· The DACT and Network cards are programmed and added to the 4010 FACP via the 4010 PC Programming tool.
Use the following steps to add a card to the 4010 FACP.
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm Operation mode.
Please Wait . . . Fire Alarm Operation Suspended
3. Press <ENTER> to continue. 4. Press <NEXT> or <PREVIOUS> until <CONFIGURE CARDS> is
displayed and then press <ENTER>. 5. Press <NEXT> or <PREVIOUS> until <ADD 4010 CARD> is displayed. 6. Press <NEXT> or <PREVIOUS> to scroll through the choices listed
below. · RS232 Card (Card Address 4) · Modem Card (Card Address 4) · 24IO Card (Card Address 9 through 14) · LCD (Card Address 9 through 14)
7. Once the desired card is displayed, press Enter. The RS232 and Modem cards are automatically set to card address 4. Follow the prompts to confirm this action.
Continued on next page
Programming
5-3
Adding, Deleting, or Modifying 4010 Cards, Continued
Adding a Card (continued) Deleting a Card
8. When first adding a 24-Point I/O or LCD Annuciator cards to the 4010, you must choose an available address of 9 through 14. (The system automatically picks the next available address.) When selecting 24IO or LCD and then pressing Enter, the following figure appears.
Card=[09] Card Type=LCD Card
9. Press <NEXT> or <PREVIOUS> to scroll through the available addresses, select the appropriate address for your card, and then press Enter. Follow the prompts to confirm this action.
Use the following steps to delete a card from the 4010 FACP.
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm Operation mode.
Please Wait . . . Fire Alarm Operation Suspended
3. Press <ENTER> to continue. 4. Press <NEXT> or <PREVIOUS> until <CONFIGURE CARDS> is
displayed and then press <ENTER>.
Caution: Deleting 4010 Cards also deletes any modes and SMPL (Custom Control) programming associated with that card.
5. After selecting Delete a 4010 Card as your option under the Configure Cards menu, press <NEXT> or <PREVIOUS> to scroll through the cards configured in the 4010 FACP.
6. When the card you wish to delete is displayed, press Enter. 7. Follow the prompts to confirm this action.
Continued on next page
5-4
Adding, Deleting, or Modifying 4010 Cards, Continued
Modifying a Card
Use the following steps to Modify a card in the 4010 FACP. The only cards you can modify from this menu are the Dual RS232, Modem/RS232, and LCD Annunciator cards.
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm Operation mode.
Please Wait . . . Fire Alarm Operation Suspended
3. Press <ENTER> to continue. 4. Press <NEXT> or <PREVIOUS> until <CONFIGURE CARDS> is
displayed and then press <ENTER>. 5. Press <NEXT> or <PREVIOUS> until <MODIFY A 4010 CARD> is
displayed. 6. Press <NEXT> or <PREVIOUS> to scroll through the cards configured in
the 4010 FACP. 7. When the card you wish to modify is displayed, press Enter. The available
modifications you can make per card are shown in Table 5-2. The 4010 prompts you on which keys to press to execute different options.
Continued on next page
Programming
5-5
Adding, Deleting, or Modifying 4010 Cards, Continued
Modifying a Card (continued)
Table 5-2. Modification Options for 4010 Cards
4010 Card RS232 Card Port A and Port B
Modem Card Port A and Port B
LCD Card
Modifications
Device: PRT40U (unsupervised 40-Column printer) PRT40S (supervised 40-Column printer PRT80U (unsupervised 80-Column printer) PRT80S (supervised 80-Column printer) UNUSED COMMAND (For use with a CRT on Port B Only)
Baud Rates: 1200, 2400, 4800, 9600, 19200, 38400
Parity: NONE, EVEN, ODD
Note: To print 4010 reports, you must have an 80-column printer.
Device: PRT40U (unsupervised 40-Column printer) PRT40S (supervised 40-Column printer PRT80U (unsupervised 80-Column printer) PRT80S (supervised 80-Column printer) UNUSED COMMAND (For use with a CRT on Port B Only)
Baud Rates: 1200, 2400, 4800, 9600, 19200, 38400
Parity: NONE, EVEN, ODD
Enter selects ALL events to report to the LCD, Default Key Operation, and Default Overrides.
Pressing Next allows you to choose Yes or No for the following:
EVENTS: Fire, Supervisory, Trouble, Reset/Silence, Test, CCE Print Events
KEY OPERATION: Fire Ack, Supv Ack, Trouble Ack, System Reset, Alarm Silence
OVERRIDE ON ALARM: Fire Ack, Supv Ack, Trouble Ack, System Reset, Alarm Silence
5-6
Overview In this Chapter
Chapter 6 Configuring Points
The 4010 allows you to manually program each point in the system. This chapter describes how to add, delete, edit, etc., points in the 4010 FACP. The following information assumes you have all cards properly installed. If your cards are not installed properly or need modification, refer to “Chapter 5 Configuring Cards.”
This chapter discusses the following topics:
Topic Overview Configure Points Menu Configuring TrueAlarm Points Configuring ZAM/IAM/RIAM Points Configuring Relay and NAC Points Configuring Digital and Analog Pseudo Points Configuring 24-Point I/O Points Configuring List Points Configuring User-Defined SW/LED Points
See Page #
6-1 6-2 6-3 6-6 6-9 6-11 6-14 6-18 6-21
Programming
6-1
Configure Points Menu
Configuring Points Menu
All options for configuring 4010 points are located in the Configure Points menu. Figure 6-1 shows the structure of this menu.
Programming Menus
Save CFIG Configure Configure
Points
Cards
· TrueAlarm · ZAMs/IAMs/RIAMs · Relay · NACs · Digital Pseudos · Analog Pseudos · 24-I/O Outputs · 24-I/O Inputs · Lists · User Defined SW/LED
Figure 6-1. Configure Points Menu
6-2
Configuring TrueAlarm Points
Overview Add IDNet Point
Edit TrueAlarm Point
This section describes how to Add an IDNet Point, Edit a TrueAlarm Point, and Delete a TrueAlarm Point.
Use the following steps to Add an IDNet point to the 4010 FACP.
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm Operation mode.
Please Wait . . . Fire Alarm Operation Suspended
3. Press <ENTER> to continue. 4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is
displayed and then press <ENTER>. 5. Press <NEXT> or <PREVIOUS> to scroll through your choices until
<TRUEALARM> is displayed and then press <ENTER>. 6. Use <NEXT> or <PREVIOUS> to scroll through your choices until <Add
IDNet Point> is displayed and then press Enter. 7. The first unused point in the system (for example, M1-1) is displayed. Press
<NEXT> or <PREVIOUS> to scroll through your list of unused points until the desired point is displayed and then press Enter. 8. Follow the prompts to confirm this action.
Note: If there are 250 devices present in the 4010 (maximum allowed), the system informs you that the IDNet channel is full and does not allow you to add any more points.
Use the following steps to Edit a TrueAlarm point in the 4010 FACP.
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm Operation mode.
Please Wait . . . Fire Alarm Operation Suspended
3. Press <ENTER> to continue. 4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is
displayed and then press <ENTER>. 5. Press <NEXT> or <PREVIOUS> to scroll through your choices until
<TRUEALARM> is displayed and then press <ENTER>.
Continued on next page
6-3
Programming
Configuring TrueAlarm Points, Continued
Edit TrueAlarm Point (continued)
Delete TrueAlarm Point
6. Use <NEXT> or <PREVIOUS> to scroll through your choices until <Edit IDNet Point> is displayed and then press Enter.
7. Press <NEXT> or <PREVIOUS> to scroll through your list of TrueAlarm points until the desired point is displayed and then press Enter.
8. Press <NEXT> or <PREVIOUS> to scroll through your list of choices until the desired option is displayed and then press Enter. Your choices are shown in Table 6-1.
Table 6-1. TrueAlarm Configuration Choices
Function
Description
Edit Device Type (See Note 1)
Changes the Hardware Device Type of the Point
Edit Point Type
Changes the Software Point Type of the Point
(See Notes 1 and 2)
Edit Point Label (See Note 2)
Changes the 40-Character Label of the Point
Clear Point Label (See Note 2)
Blanks the 40-Character Label of the Point
Edit Mode (See Note 1)
Changes the Mode of Operation for the Point
Notes:
1. For a complete list of your choices for these edit functions, refer to “Appendix A. Device and Point Types.”
2. To complete these functions, refer to their appropriate section in this publication.
Use the following steps to delete a TrueAlarm point from the 4010 FACP.
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm Operation mode.
Please Wait . . . Fire Alarm Operation Suspended
3. Press <ENTER> to continue.
Continued on next page
6-4
Configuring TrueAlarm Points, Continued
Delete TrueAlarm Point (continued)
4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is displayed and then press <ENTER>.
5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <TRUEALARM> is displayed and then press <ENTER>.
6. Use <NEXT> or <PREVIOUS> to scroll through your choices until <DELETE IDNet POINT> is displayed and then press Enter.
7. Press <NEXT> or <PREVIOUS> to scroll through your list of IDNet points until the desired point is displayed and then press Enter.
8. Follow the prompts to confirm this action.
Caution: Any Custom Control equations and LED/Switch Modes referencing the deleted point are also deleted.
Programming
6-5
Configuring ZAM/IAM/RIAM Points
Overview
This section describes how to Add, Edit, and Delete an ZAM/IAM/RIAM point.
Adding ZAM/IAM/RIAM Point
Use the following steps to add a ZAM/IAM/RIAM point to the 4010 FACP.
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm Operation mode.
Please Wait . . . Fire Alarm Operation Suspended
3. Press <ENTER> to continue. 4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is
displayed and then press <ENTER>. 5. Press <NEXT> or <PREVIOUS> to scroll through your choices until
<ZAMs/IAMs/RIAMs> is displayed and then press <ENTER>. 6. Use <NEXT> or <PREVIOUS> to scroll through your choices until <Add
IDNet Point> is displayed and then press Enter.
7. The first unused point in the system (for example, M1-1) is displayed. Press <NEXT> or <PREVIOUS> to scroll through your list of unused points until the desired point is displayed and then press Enter.
8. Follow the prompts to confirm this action.
Note: If there are 250 devices present in the 4010 (maximum allowed), the system informs you that the IDNet channel is full and does not allow you to add any more points.
Editing a ZAM/IAM/RIAM Point
Use the following steps to edit a ZAM/IAM/RIAM point in the 4010 FACP.
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm Operation mode.
Please Wait . . . Fire Alarm Operation Suspended
3. Press <ENTER> to continue. 4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is
displayed and then press <ENTER>. 5. Press <NEXT> or <PREVIOUS> to scroll through your choices until
<ZAMs/IAMs/RIAMs> is displayed and then press <ENTER>.
Continued on next page
6-6
Configuring ZAM/IAM/RIAM Points, Continued
Editing a ZAM/IAM/RIAM Point (continued)
6. Use <NEXT> or <PREVIOUS> to scroll through your choices until <Edit IDNet Point> is displayed and then press Enter.
7. Press <NEXT> or <PREVIOUS> to scroll through your list of ZAM/IAM/RIAM points until the desired point is displayed and then press Enter.
8. Press <NEXT> or <PREVIOUS> to scroll through your list of choices until the desired option is displayed and then press Enter. Your choices are shown in Table 6-2.
Table 6-2. ZAM/IAM/RIAM Configuration Choices
Function
Description
Edit Device Type Changes the Hardware Device Type of the Point (See Notes 2 and 3)
Edit Point Type
Changes the Software Point Type of the Point
(See Notes 2 and 3)
Edit Point Label (See Note 3)
Changes the 40-Character Label of the Point
Clear Point Label (See Note 3)
Blanks the 40-Character Label of the Point
Edit Mode (See Note 1)
Changes the Mode of Operation for the Point
Notes:
1. This function not allowed for ZAM/IAM/RIAM points. 2. For a complete list of your choices for these edit functions, refer
to “Appendix A. Device and Point Types.” 3. To complete these functions, refer to their appropriate section
in this publication.
Continued on next page
Programming
6-7
Configuring ZAM/IAM/RIAM Points, Continued
Deleting ZAM/IAM/RIAM IDNet Point
Use the following steps to delete a ZAM/IAM/RIAM point from the 4010 FACP.
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm Operation mode.
Please Wait . . . Fire Alarm Operation Suspended
3. Press <ENTER> to continue. 4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is
displayed and then press <ENTER>. 5. Press <NEXT> or <PREVIOUS> to scroll through your choices until
<ZAMs/IAMs/RIAMs> is displayed and then press <ENTER>.
6. Use <NEXT> or <PREVIOUS> to scroll through your choices until <DELETE IDNet POINT> is displayed and then press Enter.
7. Press <NEXT> or <PREVIOUS> to scroll through your list of IDNet points until the desired point is displayed and then press Enter.
8. Follow the prompts to confirm this action.
Caution: Any Custom Control equations and LED/Switch Modes referencing the deleted point are also deleted.
6-8
Configuring Relay and NAC Points
Overview Procedure
This section describes how to configure a Relay, NAC, or User-Defined SW/LED point. The following assumes that you have chosen Relay, NAC, or User-Defined SW/LED as your option after entering the Configure Points menu.
Use the following steps to configure a Relay or NAC point in the 4010 FACP.
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm Operation mode.
Please Wait . . . Fire Alarm Operation Suspended
3. Press <ENTER> to continue. 4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is
displayed and then press <ENTER>. 5. Press <NEXT> or <PREVIOUS> to scroll through your choices until
<RELAY> or <NAC> is displayed and then press <ENTER>. 6. Use <NEXT> or <PREVIOUS> to scroll through your NAC or RELAY
points until the desired point is displayed and then press Enter. 7. Press <NEXT> or <PREVIOUS> to scroll through your list of choices until
the desired option is displayed and then press Enter. Your choices are shown in Table 6-3.
Continued on next page
Programming
6-9
Configuring Relay and NAC Points, Continued
Procedure (continued)
Table 6-3. Relay and NAC Point Configuration Choices
Function
Description
Edit Device Type (See Note 2)
Changes the Hardware Device Type of the Point
Edit Point Type
Changes the Software Point Type of the Point
(See Notes 2 and 3)
Edit Point Label (See Note 3)
Changes the 40-Character Label of the Point
Clear Point Label (See Note 3)
Blanks the 40-Character Label of the Point
Edit Mode
Changes the Mode of Operation for the Point
(See Notes 1 and 2)
Notes:
1. This function not allowed for NAC and Relay points. 2. For a complete list of your choices for these edit functions, refer
to “Appendix A. Device and Point Types.” 3. To complete these functions, refer to their appropriate section
in this publication.
6-10
Configuring Digital and Analog Pseudo Points
Overview
Configuring Digital Pseudo Points
This section describes how to configure Digital and Analog Pseudo Points.
This section describes how to configure digital pseudo points P76 through P150. P1 through P75 are system points and cannot be edited. Use the following information to configure digital pseudo points in a 4010 FACP.
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm Operation mode.
Please Wait . . . Fire Alarm Operation Suspended
3. Press <ENTER> to continue. 4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is
displayed and then press <ENTER>. 5. Press <NEXT> or <PREVIOUS> to scroll through your choices until
<DIGITAL PSEUDOS> is displayed and then press <ENTER>. 6. Use <NEXT> or <PREVIOUS> to scroll through your points until the
desired point (P76 through P150) is displayed and then press Enter. 7. Press <NEXT> or <PREVIOUS> to scroll through your list of choices until
the desired option is displayed and then press Enter. Your choices are shown in Table 6-4.
Continued on next page
Programming
6-11
Configuring Digital and Analog Pseudo Points, Continued
Configuring Digital Pseudo Points (continued)
Configuring Analog Pseudo Points
Table 6-4. Digital Pseudo Point Configuration Choices
Function Edit Device Type (See Note 1) Edit Point Type (See Notes 2)
Edit Point Label (See Note 2) Clear Point Label (See Note 2) Edit Mode (See Note 1)
Description Changes the Hardware Device Type of the Point
Changes the Software Point Type of the Point. Your choices are:
· Utility Point · Fire Point · Trouble Point · Supervisory Changes the 40-Character Label of the Point
Blanks the 40-Character Label of the Point
Changes the Mode of Operation for the Point
Notes:
1. This function not allowed for Digital Pseudo points. 2. To complete these functions, refer to their appropriate section
in this publication.
This section describes how to configure analog pseudo points A27 through A50. A1 through A26 are system points and cannot be edited. Use the following information to configure analog pseudo points in a 4010 FACP.
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm Operation mode.
Please Wait . . . Fire Alarm Operation Suspended
3. Press <ENTER> to continue.
Continued on next page
6-12
Configuring Digital and Analog Pseudo Points, Continued
Configuring Analog Pseudo Points (continued)
4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is displayed and then press <ENTER>.
5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <ANALOG PSEUDOS> is displayed and then press <ENTER>.
6. Use <NEXT> or <PREVIOUS> to scroll through your points until the desired point (A27 through A50) is displayed and then press Enter.
7. Press <NEXT> or <PREVIOUS> to scroll through your list of choices until the desired option is displayed and then press Enter. Your choices are shown in Table 6-5.
Table 6-5. Analog Pseudo Point Configuration Choices
Function
Description
Edit Device Type (See Note 1)
Changes the Hardware Device Type of the Point
Edit Point Type (See Notes 2 and 3)
Changes the Software Point Type of the Point. Your choices are:
· Analog · Timer · Counter
Edit Point Label (See Note 3)
Changes the 40-Character Label of the Point
Clear Point Label (See Note 3)
Blanks the 40-Character Label of the Point
Edit Mode (See Note 1)
Changes the Mode of Operation for the Point
Notes:
1. This function not allowed for Analog Pseudo points. 2. For a complete list of your choices for these edit functions, refer
to “Appendix B. Hardware and Pseudo Points.” 3. To complete these functions, refer to their appropriate section
in this publication.
Programming
6-13
Configuring 24-Point I/O Points
Overview
Configuring 24-Point Input Points
The 4010 allows you to use the 4605 24-Point I/O card to monitor input points (switches) and control output points (Lamps, Tone-alerts, and Relays).
Use the following steps to configure input points on the 24-Point I/O card.
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm Operation mode.
Please Wait . . . Fire Alarm Operation Suspended
3. Press <ENTER> to continue. 4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is
displayed and then press <ENTER>. 5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <24
IO INPUTS> is displayed and then press <ENTER>. 6. Use <NEXT> or <PREVIOUS> to scroll through your points until the
desired point is displayed and then press Enter. 7. Press <NEXT> or <PREVIOUS> to scroll through your list of choices until
the desired option is displayed and then press Enter. Your options are shown in Table 6-6.
6-14
Configuring 24-Point I/O Points, Continued
Configuring 24-Point Input Points (continued)
Table 6-6. 24-Point Input Points Configuration Choices
Function
Description
Edit Device Type
Changes the Hardware Device Type of the Point. Choose Input or Output
Edit Point Type
Changes the Software Point Type of the Point. Your choices for Input points are:
· USWITCH (2-position unsupervised switch) · OSWITCH (2-position Open supervised switch) · SSWITCH (2-position Open/Short supervised
Switch) · TSWITCH (3-position supervised switch)
Edit Point Label*
Changes the 40-Character Label of the Point
Clear Point Label*
Blanks the 40-Character Label of the Point
Edit Mode
Changes the Mode of Operation for the Point. Your choices for modes are:
· SMPL (SMPL controlled) · Ack (Acknowledge) · Fire Ack (Fire alarm acknowledge) · Supv. Ack (Supervisory alarm acknowledge) · Trouble Ack (Trouble acknowledge) · Reset (System reset) · LTEST (Lamp test) · ONOFF (On/Off switch) · TOF (Toggle On Off switch) · PBT (Push button track) · PBH (Push button hold) · DE (Disable/enable) · TDE (Toggle disable/enable)
*This function not allowed for 24-Point Input points.
Continued on next page
Programming
6-15
Configuring 24-Point I/O Points, Continued
Configuring 24-Point Output Points
Use the following steps to configure output points on the 24-Point I/O card.
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm Operation mode.
Please Wait . . . Fire Alarm Operation Suspended
3. Press <ENTER> to continue. 4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is
displayed and then press <ENTER>.
5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <24 IO OUTPUTS> is displayed and then press <ENTER>.
6. Use <NEXT> or <PREVIOUS> to scroll through your points until the desired point is displayed and then press Enter.
7. Press <NEXT> or <PREVIOUS> to scroll through your list of choices until the desired option is displayed and then press Enter. Your options are shown in Table 6-7.
Continued on next page
6-16
Configuring 24-Point I/O Points, Continued
Configuring 24-Point Output Points (continued)
Table 6-7. 24-Point Output Point Configuration Choices
Function
Description
Edit Device Type
Changes the Hardware Device Type of the Point. Choose Input or Output
Edit Point Type Edit Point Label*
Changes the Software Point Type of the Point. Your choices for Output points are:
· LAMP (Lamp or LED output) · PIEZO (Piezo output) · RELAY (Generic relay) · RRELAY (Relay on `til reset)
Changes the 40-Character Label of the Point
Clear Point Label*
Blanks the 40-Character Label of the Point
Edit Mode
Changes the Mode of Operation for the Point. Your choices for modes are:
· SMPL (SMPL controlled) · Fire (Fire alarm LED) · Supervisory (Supervisory LED) · Trouble (Trouble LED) · Disable (Disable LED) · On (ON LED) · Off (OFF LED) · LF (Local fire acknowledge) · LS (Local supervisory acknowledge) · LT (Local trouble acknowledge)
*This function not allowed for 24-Point Output points.
Programming
6-17
Configuring List Points
Overview
This section describes how to configure a List.
Configure a List
Use the following steps to configure a List in the 4010 FACP.
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm Operation mode.
Please Wait . . . Fire Alarm Operation Suspended
3. Press <ENTER> to continue. 4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is
displayed and then press <ENTER>.
5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <LIST> is displayed and then press <ENTER>.
6. Use <NEXT> or <PREVIOUS> to scroll through your lists until the desired list is displayed and then press Enter.
7. Press <NEXT> or <PREVIOUS> to scroll through your list of choices until the desired option is displayed and then press Enter. Your choices are shown in Table 6-8.
Table 6-8. List Configuration Choices
Function
Description
Add Point (See Note 2)
Allows you to add specific point(s) to a List
Delete Point
Allows you to delete specific point(s) from a List
Delete ALL Points
Allows you to delete all points from a List
Edit Point Label (See Notes 1 and 3)
Clear Point Label (See Notes 1 and 3) Edit Point Type (See Notes 1, 2, and 3)
Allows you to change the 40-Character label of the List
Blanks the 40-Character Label of the List
Changes the Point Type for the List
Notes:
1. This function not allowed for all Lists. 2. For a complete list of your choices for these edit functions, refer
to “Appendix B. Hardware and Pseudo Points.” 3. To complete these functions, refer to their appropriate section
in this publication.
Continued on next page
6-18
Configuring List Points, Continued
Add a Point to a List
Device Type
Delete a Point from a List
Use the following steps to Add a point to a List on the 4010 FACP. A TrueAlarm point is used as an example in the following steps.
1. After selecting Lists as your option under the Configure Points menu, use <NEXT> or <PREVIOUS> to scroll through your lists until the desired list is displayed and then press <FUNCTION>.
2. Press <NEXT> or <PREVIOUS> until Add Point is displayed and then press Enter (Figure 6-2 is displayed).
IDNet Device: 3-1
[TrueAlarm]Add
1/130
Figure 6-2. Add a Point to a List Screen
3. Press <NEXT> or <PREVIOUS> to scroll through the device types shown in the focus brackets ([ ]) until the desired device type is displayed (in this example, TrueAlarm).
4. Press the Right Arrow to move the focus brackets ([ ]) to the Add option. 5. Press <NEXT> or <PREVIOUS> to scroll through the points you wish to
add to the list. 6. Once the correct point is displayed, press Enter to add that point to the list.
Repeat Steps 5 and 6 to Add all desired points to your chosen List.
Use the following steps to Delete a point from a List on the 4010 FACP. A TrueAlarm point is used as an example in the following steps.
1. After selecting Lists as your option under the Configure Points menu, use <NEXT> or <PREVIOUS> to scroll through your lists until the desired list is displayed and then press Enter.
2. Press <NEXT> or <PREVIOUS> until the point you wish to delete is displayed and then press Enter.
3. Press <NEXT> or <PREVIOUS> until Delete Point is displayed and then press Enter.
4. Follow the prompts to confirm this action.
Continued on next page
Programming
6-19
Configuring List Points, Continued
Delete ALL Points from a List
Use the following steps to Delete ALL points from a List on the 4010 FACP.
1. After selecting Lists as your option under the Configure Points menu, use <NEXT> or <PREVIOUS> to scroll through your lists until the desired list is displayed and then press <FUNCTION>.
2. Press <NEXT> or <PREVIOUS> until Delete ALL Points is displayed and then press Enter.
3. Follow the prompts to confirm this action.
6-20
Configuring User-Defined SW/LED
Overview
Configure a User-Defined Switch or LED
This section describes how to configure a User-Defined Switches and LEDs. The following assumes that you have chosen User Defined SW/LED as your option after entering the Configure Points menu.
Use the following steps to configure a User-Defined Switch or LED in the 4010 FACP.
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm Operation mode.
Please Wait . . . Fire Alarm Operation Suspended
3. Press <ENTER> to continue. 4. Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is
displayed and then press <ENTER>. 5. Press <NEXT> or <PREVIOUS> to scroll through your choices until
<USER DEFINED SW/LED> is displayed and then press <ENTER>. 6. Press <NEXT> or <PREVIOUS> to scroll through the choices listed
below. Once your choice is displayed, press Enter.
– User LED 1 – User LED 2 – User LED 3 – User Defined Key 1 – User Defined Key 2
7. Press <NEXT> or <PREVIOUS> to scroll through your list of choices until the desired option is displayed and then press Enter. Your choices are shown in Table 6-9.
Continued on next page
Programming
6-21
Configuring User-Defined SW/LED, Continued
Configure a User-Defined Switch or LED (continued)
Table 6-9. User-Defined SW/LED Configuration Choices
Function
Description
Edit Device Type Changes the Hardware Device Type of the Point (See Notes 1 and 2)
Edit Point Type (See Note 2)
Changes the Software Point Type of the Point
Edit Point Label (See Note 1)
Changes the 40-Character Label of the Point
Clear Point Label (See Note 1)
Blanks the 40-Character Label of the Point
Edit Mode
Changes the Mode of Operation for the Point
Notes:
1. This function not allowed for User-Defined SW/LED. 2. Your Point Type choices for LEDs are Yellow LED or NON-
Yellow LED. The switches default to USWITCH point type and is not editable.
Edit a Mode of a User-Defined SW/LED
This section describes how to edit the mode of a User-Defined SW/LED. Use the following steps to edit the mode of a User-Defined Switch or LED in the 4010 FACP.
1. After selecting User Defined SW/LED as your option under the Configure Points menu, press <NEXT> or <PREVIOUS> to scroll through the choices listed below. Once your choice is displayed, press Enter. · User LED 1 · User LED 2 · User LED 3 · User Defined Key 1 · User Defined Key 2
2. Press <NEXT> or <PREVIOUS> to scroll through your list of choices until Edit Mode is displayed and then press Enter. Your modes for Switches and LEDs are shown in Table 6-10.
Continued on next page
6-22
Configuring User-Defined SW/LED, Continued
Edit a Mode of a User-Defined SW/LED (continued)
Table 6-10. User-Defined SW/LED Modes
User-Defined SW/LED Switch Modes
LED Modes
Modes
· SMPL · Ack · Fire Ack · Supv. Ack · Trouble Ack · Reset · Silence · LTEST · ON-OFF · TOF · PBT · PBH · DE · TDE
· SMPL · Fire · Supervisory · Trouble · Disable · On · Off · LF · LS · LT
3. Select the appropriate mode and then press Enter. 4. Follow the prompts to confirm this action.
Programming
6-23
This is blank
Overview In this Chapter
Chapter 7 System Options
This chapter describes how to set system options such as Time/Date Format, Active Status Reminder, etc. These options are custom functions for the 4010. The System Options (shown in Figure 7-1) can also be set from the Quick-CFIG menus.
This chapter discusses the following topics:
Topic System Options Menu Time/Date Format Active Status Reminder Silence/Reset Inhibit Alarm Cut-Out Timer Door Drop on Alarm Door Drop on AC Loss Audible and Visual NAC Operation QuickAlert Horn Operation Depleted Battery Cut-Out Stagger Start AHUs Enable City Circuit Expansion Power Single Station Suppression Release
See Page # 7-2 7-3 7-4 7-5 7-6 7-7 7-8 7-9 7-10 7-11 7-12 7-13 7-14 7-15 7-16
Programming
7-1
System Options Menu
Introduction
All 4010 system options are accessed via the System Options menu choice, which is located in the Programming menu tree. Figure 7-1 shows the structure of the System Options menu.
Programming Menus
Configure Cards
System Options
Custom Control
· Time/Date Format · Active Status
Reminder · Silent/Reset
Inhibit · Alarm Cut-Out Timer · Door Drop on Alarm · Door Drop on AC
Loss · Audible NAC
Operation · Visual NAC
Operation · Depleted Batt.
Cutout · Stagger Start AHUs · Enable City Circuit · Expansion Power · Single Station · Suppression Release · QuickAlert Horn
Operation
Figure 7-1. System Options Menu
7-2
Time/Date Format
Overview
Setting the Time Format
When setting the Time/Date Format, you are only setting the Time format in 12 or 24-hour format. That is, the time is displayed in 12-hour format with the AM (morning) or PM (afternoon) indications or in 24-hour (military style) format. The date is always displayed in the following format and cannot be changed:
Wed 27-Aug-97
Day of week, date, month, year
The Time format directly affects how time is displayed on the 4010 not only at the high-level status screen but in the Historical Logs.
Use the following steps to set the Time format on the 4010 FACP.
1. Press <MENU>. 2. Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is no longer in the Fire Alarm Operation mode. 3. Press <ENTER> to continue. 4. Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is displayed and then press <ENTER>. 5. Press <NEXT> or <PREVIOUS> to scroll through your choices until <TIME/DATE FORMAT> is displayed and then press <ENTER>. 6. Press <NEXT> or <PREVIOUS> to scroll through the options until 12 Hour or 24 Hour is displayed and then press Enter. 7. Follow the prompts to confirm this action.
Programming
7-3
Active Status Reminder
Documents / Resources
![]() |
Simplex 4010 Fire Alarm Control Panel [pdf] Instruction Manual 4010, 4004, 4010 Fire Alarm Control Panel, 4010, Fire Alarm Control Panel, Alarm Control Panel, Control Panel |