SIEMENS REL-EOL Releasing End Line Module

SIEMENS REL-EOL-Releasing-End-Line-Module-product-image

Installation Instructions

MODEL REL-EOL
Releasing End of Line Module

The REL-EOL Releasing End of Line module (shown in Figure 1) comes with one diode that is preinstalled and an additional diode which is only used for releasing applications using the CRM-4 and CSM-4 (See Figure 2). Also contained are three end of line resistors to be field installed depending on use with the following releasing modules:

REL-EOL RESISTORS
Releasing Module Part Number Value
CSM-4 140-034679 2.2K, 1/2W
ZIC-4A 140-034677 24K, 1/2W
RX FS-REL

MPC-REL

140-034677

140-034677

24K, 1/2W

24K, 1/2W

XCI2 001-U1 140-034677 24K, 1/2W
RM-30U/RU 140-050720 5.6K, 1/2W

SIEMENS REL-EOL-Releasing-End-Line-Module-01RXTO BE FIELD INSTALLED DEPENDING ON MODEL USED WITH REFERENCE TO RELEASING MODULE INSTALLATION INSTRUCTIONS.
Figure 1
EOLR Detail

For specific wiring instructions, refer to the following installation instructions:

RELEASING INSTALLATION INSTRUCTIONS
System Releasing Module Installation Instruction
System 3 (CP-35) RM-30U/RU P/N 315-085100
MXL/MXLV CSM-4 P/N 315-090854
FireFinder XLS ZIC-4A P/N 315-033050
FS-250 FS-REL P/N 315-049570
MPC-6000 MPC-REL P/N 315-049570FA
FS-20 XCI2 001-U1 P/N A6V10315050

SIEMENS REL-EOL-Releasing-End-Line-Module-02
THIS ADDITIONAL DIODE IS ONLY TO BE USED FOR RELEASING APPLICATIONS USING THE CRM-4 AND CSM-4.
Figure 2
Diode Detail

Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
P/N 315-096357-6

Siemens Canada Limited
Building Technologies Division
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada

firealarmresources.com

Documents / Resources

SIEMENS REL-EOL Releasing End Line Module [pdf] Instruction Manual
REL-EOL, REL-EOL Releasing End Line Module, Releasing End Line Module, End Line Module, Line Module, Module

References

Leave a comment

Your email address will not be published. Required fields are marked *