SIEMENS REL-EOL Releasing End Line Module
Installation Instructions
MODEL REL-EOL
Releasing End of Line Module
The REL-EOL Releasing End of Line module (shown in Figure 1) comes with one diode that is preinstalled and an additional diode which is only used for releasing applications using the CRM-4 and CSM-4 (See Figure 2). Also contained are three end of line resistors to be field installed depending on use with the following releasing modules:
REL-EOL RESISTORS | |||
Releasing Module | Part Number | Value | |
CSM-4 | 140-034679 | 2.2K, 1/2W | |
ZIC-4A | 140-034677 | 24K, 1/2W | |
RX– | FS-REL
MPC-REL |
140-034677
140-034677 |
24K, 1/2W
24K, 1/2W |
XCI2 001-U1 | 140-034677 | 24K, 1/2W | |
RM-30U/RU | 140-050720 | 5.6K, 1/2W |
RX– TO BE FIELD INSTALLED DEPENDING ON MODEL USED WITH REFERENCE TO RELEASING MODULE INSTALLATION INSTRUCTIONS.
Figure 1
EOLR Detail
For specific wiring instructions, refer to the following installation instructions:
RELEASING INSTALLATION INSTRUCTIONS | ||
System | Releasing Module | Installation Instruction |
System 3 (CP-35) | RM-30U/RU | P/N 315-085100 |
MXL/MXLV | CSM-4 | P/N 315-090854 |
FireFinder XLS | ZIC-4A | P/N 315-033050 |
FS-250 | FS-REL | P/N 315-049570 |
MPC-6000 | MPC-REL | P/N 315-049570FA |
FS-20 | XCI2 001-U1 | P/N A6V10315050 |
THIS ADDITIONAL DIODE IS ONLY TO BE USED FOR RELEASING APPLICATIONS USING THE CRM-4 AND CSM-4.
Figure 2
Diode Detail
Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
P/N 315-096357-6
Siemens Canada Limited
Building Technologies Division
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada